| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 1fd3b46f-d721-43d7-91b7-03627b8a514b China |
| Simplified SCIP | 6c7e4a29-56e9-499d-b34b-7661518da835 Denmark |
| 6d7af061-a21d-432f-a59e-1ee4389da29c Finland | |
| f314b971-b47d-4146-a25f-0b4a24d5800b Germany | |
| 320bda71-6630-464a-abc4-85143ebd06fd Sweden | |
| 692639ab-a021-4053-862a-c681a209a1d5 France | |
| 395b6ef6-bdd3-4208-a045-60c3261f53a1 Poland | |
| 1ec02744-7618-458f-9af9-56f0443e6262 Estonia | |
| 8bad524c-606b-4f76-b01d-dc21c0130371 Hungary | |
| 1562629d-a801-40b8-9542-d8c0f680b842 Greece | |
| a8d555a1-e638-43e0-9c87-886bd76bf7bb Norway | |
| f1c4846a-d28a-41c6-9fc0-3dff95448241 Germany | |
| c542c9fc-7a49-479c-a0ac-fe77cacb3a6c Germany | |
| e7383132-c68e-4121-86bc-e409f891b38a Croatia | |
| 46d3cc75-8464-431f-a5a9-ec8c6dee5f58 Hungary | |
| d66a7e1c-8c99-45be-9a84-ab73d878014e Belgium | |
| 8f5f1247-73bf-46a6-b8ef-fa39fd1c9d8d Poland | |
| 786a1f9c-152b-428e-9581-b4ae08713fd0 Spain | |
| e81b4ee4-94e3-4d5a-b172-3488f622eaee Portugal | |
| be612e78-299c-4bed-8e9c-be214c23115f Bulgaria | |
| 94184ce6-e20d-4445-91e7-b3cf343e7c03 Sweden | |
| 3ed08fbc-0a53-429a-b9e7-dd81d6696e0d Czech Republic | |
| 59150e82-1c3d-4dae-b43d-81f0720479fd Germany | |
| 16eb6328-a54d-457f-bd45-0d683cc3da7a Poland | |
| 8a4f3b23-fc3f-4f64-b222-c705b90dd0b1 Netherlands | |
| a3027123-c089-4933-90e5-70b9d694f754 Belgium | |
| 79f276c7-dc59-4275-a0d6-895146c894a6 France | |
| b8d4d884-37a1-45f7-a4d7-e4f5509eda84 Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZABNEEBB000A000000XX |
| EAN | 8015644751821 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644751821 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 400 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 31 W |
| Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 630 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 630 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 42 kA |
| Overload release current setting (EF002336) | 252.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 378.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 945.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |