View larger
1SDA070823R1
070823
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | e28bbf97-64d4-4344-877a-ac0d76317ba2 India |
| Simplified SCIP | 1a82aa32-c806-416f-b975-6c2a8b566ed8 Estonia |
| 7e77ecce-9019-4a84-9892-dde23ddcd1e9 Sweden | |
| 8af624d9-5f09-45cf-a62c-bfe8fb9d7527 Poland | |
| 91aa1d45-9ab4-4623-b4a0-2c2afb61e7ca Greece | |
| 699ce3ff-4495-4e4b-9e2d-e105a5f26397 Portugal | |
| b77b7d18-56ad-4cfc-ae73-60ee98b95dd2 Germany | |
| ffab58cf-49a3-4f51-a634-d15950e1c962 France | |
| c7a17ccc-a565-484c-8b51-5977948633d4 Bulgaria | |
| 1e8386de-4dc4-419a-8ed2-1b57d81afa9d Germany | |
| 8e446c6a-891a-4d46-99da-e49d666a7964 Sweden | |
| 59280a2c-3f2b-4dde-9843-3b031ebf76a9 France | |
| bbce25e6-dbbe-44a0-9fab-59424f62f446 Poland | |
| c3b7d0ad-857c-4047-a96b-ccbc02451e0f Germany | |
| bb081824-8c95-4f69-97fc-d5043d463c3d Finland | |
| af72991e-fde3-49ac-bb81-eb0d1016c4f1 Denmark | |
| bcdb9c0e-639c-46b9-a9b8-68bac5d22bd6 Germany | |
| b992e72c-511b-4b27-87da-126c63537caa Belgium | |
| 172e1483-2aa2-4faf-9763-fced95effcd6 Norway | |
| 9615d2eb-509b-4414-b603-904a34e85634 Germany | |
| 15402749-b744-493f-835b-8119a2a06e2c Netherlands | |
| 022fc121-53f1-4f84-b71a-480010bac506 Hungary | |
| 5440dc5a-210b-43c5-bdda-1dec314786e8 Poland | |
| 78f6b6ea-9605-482d-af38-c5a35bd6b3db Czech Republic | |
| cdc10fa4-a0b4-4267-89ff-035cb23caf48 Croatia | |
| 9f24c31a-519b-493e-bd48-84d1fd682e9b Hungary | |
| c1f18939-4466-410a-a4f2-5eabf4b65182 Spain | |
| ad226ba1-dfd7-48c6-8193-03d92c751490 Belgium | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1BREHBC000A000000XX |
| EAN | 8015644746735 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 14 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 16 kg |
| Package Level 1 EAN | 8015644746735 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0001 |
| Technical | |
| Connecting Capacity | 1000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 122 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1250 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 42 kA |
| Overload release current setting (EF002336) | 1250 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 12500 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1875.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |