View larger
2CSR246040R3164 ABB DS203NC L C16 AC300 RCBO
2CSR246040R3164
246040
ABB
1 Pcs.
Automation > Earth leakage circuit breaker
DS200
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing multi-pole circuit security, the Abb 2CSR246040R3164 ABB DS203NC L C16 AC300 RCBO integrates overcurrent breaking and residual current detection into a compact assembly. Such protective devices are widely utilized in industrial environments to prevent electrical fires and safeguard distribution wiring.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 83.26 %
- Sustainable Material Content in Packaging (wt. %): Recycled Paper - 00 %
- Extended Product Lifetime: Product Durability
- End Of Life Disassembling Instructions: 9AKK108469A7475
- Environmental Product Declaration - EPD: 9AKK108469A9830
- Type of Residual Current: Type AC
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): 6 kA
- Maximum Surge Current: 0.25 kA
- Power Supply Connection: Arbitrary
- Energy Limiting Class: 3
- Electrical Endurance: 10000 cycle
- Mechanical Endurance: 20000 cycle
- Number of Protected Poles: 3
- Number of Poles: 3P+N
- Operating Characteristic: Instantaneous
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 83.26 % |
| Sustainable Material Content in Packaging (wt. %) | Recycled Paper - 00 % |
| Recycled Cardboard - 92 % | |
| Recycled Paper - 00 % | |
| Extended Product Lifetime | Product Durability |
| End Of Life Disassembling Instructions | 9AKK108469A7475 |
| Environmental Product Declaration - EPD | 9AKK108469A9830 |
| Technical | |
| Type of Residual Current | Type AC |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 6 kA |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 4.5 kA |
| Maximum Surge Current | 0.25 kA |
| Power Supply Connection | Arbitrary |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 3 |
| Number of Poles | 3P+N |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Earthing Switch Type | Undelayed |
| Options Provided | None |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10 mm² |
| Rigid 25 ... 25 mm² | |
| Flexible 25 ... 25 mm² | |
| Rated Cross-Section | 1 - Solid-Core 25 … 25 mm² |
| 4 - Multi-Wired 1 … 25 mm² | |
| Electrical | |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 415 V |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 16 A |
| Rated Residual Current | 300 mA |
| Rated Short-Circuit Capacity | 4.5 kA |
| Rated Conditional Short-Circuit Current (Inc) | 6 kA |
| Rated Frequency (f) | 50/60 Hz |
| Power Loss | Total 10 W |
| Overvoltage Category | III |
| Material Compliance | |
| RoHS Declaration | 9AKK106713A5597 |
| RoHS Information | Following EU Directive 2011/65/EU |
| RoHS Date | 20150415 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Environmental | |
| Ambient Air Temperature | Operation -25 … 55 °C |
| Degree of Protection | IP2X |
| Pollution Degree | 2 |
| Environmental Information | refer to RoHS information |
| Dimensions | |
| Width in Number of Modular Spacings | 4 |
| Product Net Width | 71 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 480 g |
| Built-In Depth (t2) | 69 mm |
| Engineering | |
| EPLAN Data | 9AAC181437_EPLAN |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.530 kg |
| Certificates and Declarations | |
| CCC Certificate | 2021980307001650 |
| Declaration of Conformity - CE | 9AKK106713A5597 |
| Installation | |
| Instructions and Manuals | 9AKK106713A8790 |
| Mounting Type | DIN-Rail |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CSC423030B0201 |
| External Classifications and Standards | |
| ETIM 9 | EC000905 - Earth leakage circuit breaker |
| ETIM 10 | EC000905 - Earth leakage circuit breaker |
| UNSPSC | 39121601 |
| eClass | V11.0 : 27142207 |
| Object Classification Code | F |
| Standards | IEC 61009-1 |
| IEC 61009-2-1 | |
| EN 61009-1 | |
| EN 61009-2-1 | |