View larger
1SVR730740R9300 ABB CM-TCS.23S Temperature monitoring relay Temp.-range 0...+200°C, 24VAC/DC
1SVR730740R9300
730740
ABB
1 Pcs.
Automation > Temperature monitoring relay
Monitoring
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB temperature monitoring relay, designated as 1SVR730740R9300, is deployed in electrical panels to safeguard equipment from thermal overloads by tracking sensor inputs. When temperatures move outside acceptable thresholds, the relay switches internal contacts to initiate protective interlocks or alarms.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- EAN: 4016779852760
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 2CDC112199D0201
- Instructions and Manuals: 1SVC730560M1001
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 22.5 mm
- Product Net Height: 85.6 mm
- Product Net Depth / Length: 103.7 mm
- Product Net Weight: 0.138 kg
- Function: Overtemperature monitoring
- Measuring Range: 0 ... 200 °C
- Sensor Type: PT100
- Rated Control Supply Voltage (U s ): 24 V AC/DC
- Rated Frequency (f): Supply Circuit 50 Hz
- Output: 2 x 1 c/o or 1 x 2 c/o contacts, configurable
More info
▲| Ordering | |
|---|---|
| EAN | 4016779852760 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC112199D0201 |
| Instructions and Manuals | 1SVC730560M1001 |
| 1SVC730560M0001 | |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 22.5 mm |
| Product Net Height | 85.6 mm |
| Product Net Depth / Length | 103.7 mm |
| Product Net Weight | 0.138 kg |
| Technical | |
| Function | Overtemperature monitoring |
| Undertemperature monitoring | |
| Over- and undertemperature monitoring | |
| Measuring Range | 0 ... 200 °C |
| Sensor Type | PT100 |
| Rated Control Supply Voltage (Us) | 24 V AC/DC |
| Rated Frequency (f) | Supply Circuit 50 Hz |
| Supply Circuit 60 Hz | |
| Supply Circuit DC | |
| Output | 2 x 1 c/o or 1 x 2 c/o contacts, configurable |
| Terminal Type | Screw Terminals |
| Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
| Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
| Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
| Minimum Switching Capacity | 24 V |
| 10 mA | |
| Rated Impulse Withstand Voltage (Uimp) | Measuring Circuit / Output Circuit 4 kV |
| Output Circuit 1 / Output Circuit 2 4 kV | |
| Supply Circuit / Measuring Circuit 4 kV | |
| Supply Circuit / Output Circuit 4 kV | |
| Rated Insulation Voltage (Ui) | Measuring Circuit / Output Circuit 300 V |
| Output Circuit 1 / Output Circuit 2 300 V | |
| Supply Circuit / Measuring Circuit 300 V | |
| Supply Circuit / Output Circuit 300 V | |
| Degree of Protection | Housing IP50 |
| Terminals IP20 | |
| Overvoltage Category | III |
| Pollution Degree | 3 |
| Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 6 A |
| Output Circuit NO - F Type Fuses 10 A | |
| Electrical Durability | AC-12 100000 cycle |
| Mechanical Durability | Nr. Operations 30000000 cycle |
| Connecting Capacity | Flexible with Ferrule 1x 0.5 ... 2.5 mm² |
| Flexible with Ferrule 2x 0.5 ... 1.5 mm² | |
| Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² | |
| Flexible 1x 0.5 ... 2.5 mm² | |
| Flexible 2x 0.5 ... 1.5 mm² | |
| Rigid 1x 0.5 ... 4 mm² | |
| Rigid 2x 0.5 ... 2.5 mm² | |
| Tightening Torque | 0.6 ... 0.8 N·m |
| Wire Stripping Length | 8 mm |
| Recommended Screw Driver | 0.8 x 4 |
| 4.5 | |
| Pozidriv 1 | |
| Mounting Position | 1 ... 6 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Standards | CAN/CSA C22.2 No.60947-5-1 |
| IEC/EN 60255-26 | |
| IEC/EN 60255-27 | |
| IEC/EN 61000-6-2 | |
| IEC/EN 61000-6-3 | |
| IEC/EN 63000 | |
| UL 60947-5-1 | |
| IEC/EN 60947-5-1 | |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
| Contact Rating UL/CSA | B300 |
| Connecting Capacity UL/CSA | Flexible 1x 18-14 AWG |
| Flexible 2x 18-16 AWG | |
| Rigid 1x 20-12 AWG | |
| Rigid 2x 20-14 AWG | |
| Tightening Torque UL/CSA | 7.08 in·lb |
| Pilot Duty UL/CSA | B300 |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... +60 °C |
| Storage -40 ... +85 °C | |
| Maximum Operating Altitude Permissible | Without Derating 2000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SVD981001-4501 |
| RoHS Declaration | 1SVD981001-4401 |
| SCIP | 98236fa5-702a-4722-85bf-00d75072a8f8 Germany |
| Simplified SCIP | 8a3f8e91-cd9e-4ccd-9460-373a18fba8c0 Germany |
| f5128662-bcbb-4f2f-a47d-14eb073516ad Bulgaria | |
| bb3ea09f-4d0f-41bc-8ee4-0b685649f4d4 Poland | |
| 9c7fcb81-ccb8-4c78-971f-fa0c31ca1638 Germany | |
| db41f34b-5483-4896-ad68-e0eeab5aa255 Poland | |
| a650979a-ba16-472c-a441-6bf886fe2bfa Denmark | |
| 805a1610-49c3-4071-a4d0-382f09806a01 Germany | |
| e31430ed-c0e1-4d2e-8a8c-0d4bc55f26ce Czech Republic | |
| 3bdab034-0150-4731-a811-fb77be2c2bd0 Finland | |
| c8f3161a-fa8c-44b4-b312-fb68cab733e9 Italy | |
| 418f73f7-8530-4232-9d7b-cc2ebeed89f8 Germany | |
| fbb1ae95-4fcf-4431-a5a8-24d01074da6d Netherlands | |
| 5637ce2d-435b-4858-a210-5f0ee4f31a1f Norway | |
| 26ed4a02-578c-4fc0-808f-67e934ee5b30 Croatia | |
| a74e32ab-5b2c-48be-93b7-f0b573a94f0c Sweden | |
| eb2ba93c-dad2-48dc-b9c4-d828d2076c43 Greece | |
| bd321eae-83da-420a-b8c6-373245000fa3 Portugal | |
| 34910958-4d9f-4ed7-b92d-eb3b41d65d0d Hungary | |
| 194eb16e-443a-4e40-8877-18c0e91ab017 Belgium | |
| d7280700-a44e-46cb-9d86-ccec7c224e29 Hungary | |
| cb2e58f4-334b-498b-aac5-6ebe890f563b France | |
| 76b0c962-9af8-4536-91c4-5241be2f60d3 Spain | |
| 2386d9e4-6ee0-4067-b1fa-b87806308a33 Estonia | |
| 91e3c7c1-bdba-4afb-8324-3222614bd104 Sweden | |
| 5d131f6b-f4ae-4370-b245-21f09067f0f6 Poland | |
| da1534c4-2bdc-40b3-88e2-6510cf249bf7 France | |
| 8b36b77c-6ffe-4c68-958a-8df9cb076256 Belgium | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006536 |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| Environmental Product Declaration - EPD | 1SAC200438H0001 |
| Certificates and Declarations | |
| CCC Certificate | CCC_2018010303056014 |
| CQC Certificate | CQC2007010303243843 |
| cULus Certificate | cULus60947-5-1_20170922-E140448 |
| Declaration of Conformity - CCC | 2020980303000196 |
| Declaration of Conformity - CE | 1SVD981015-00 |
| Declaration of Conformity - UKCA | 1SVD981015-10 |
| DNV GL Certificate | DNV_GL_TAA000021M |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 97 mm |
| Package Level 1 Depth / Length | 30 mm |
| Package Level 1 Height | 109 mm |
| Package Level 1 Gross Weight | 0.163 kg |
| Package Level 1 EAN | 4016779852760 |
| External Classifications and Standards | |
| Object Classification Code | B |
| ETIM 7 | EC001446 - Temperature monitoring relay |
| ETIM 8 | EC001446 - Temperature monitoring relay |
| ETIM 9 | EC001446 - Temperature monitoring relay |
| eClass | V11.0 : 27371810 |
| UNSPSC | 39122331 |
| E-Number (Finland) | 2712332 |
| E-Number (Norway) | 4187813 |
| E-Number (Sweden) | 3860668 |