ABB 1SVR740794R2300 1SVR740794R2300 ABB CM-PVS.81P Three-phase monitoring relay 2c/o, 0,0,1-30s, L1-L2-L3 3x200-400VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR740794R2300 ABB CM-PVS.81P Three-phase monitoring relay 2c/o, 0,0,1-30s, L1-L2-L3 3x200-400VAC

1SVR740794R2300

740794

ABB

1 Pcs.

CM-PVS.81P Three-phase monitoring relay 2c/o, 0,0,1-30s, L1-L2-L3=3x200-400VAC CM-PVS.81P RELe CTRL THREE-PHASE 2 C/C RES

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779876490
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112202D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132603_EPLAN
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.128 kg
Technical
FunctionPhase failure detection
Phase sequence monitoring
Over- and undervoltage monitoring
Measuring Range(L-L) 200 ... 400 V AC
Time RangeTripping Delay (ON or OFF) 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-L) 200 ... 400 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 c/o (SPDT) contacts
Terminal TypeScrewless Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 6 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 600 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length8 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 2x 18-16 AWG
Rigid 2x 20-16 AWG
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIPa513a9d5-1f93-49b3-9fcd-71c510abb94f Germany
Simplified SCIPdf670018-61e5-4183-a3de-4ea5a5decc84 Czech Republic
7743ec17-fe28-4318-ae9a-bef52730628d Germany
cc5f5c9b-80db-425d-b590-5db2e808ce9c Germany
4e5d0ed3-040c-4f97-8b35-e9798a35e950 France
e7cb5af0-629e-46dc-bc12-949d3d047434 Germany
763b7b7d-caf3-4084-ae3b-46e1f3f0759e Italy
6899c11a-5016-430f-9bf1-c4bb0a8ce629 Finland
3c6ff47f-7b58-4000-95ef-23bc69f5fbc8 Poland
4dc32959-d43b-4d7d-9f20-43351228d5ce Norway
6d0cfbe9-c4c2-4524-8145-52a1189d23a4 Belgium
de9556cc-aa5b-4f86-974a-5799805c3c50 Denmark
a4169849-70b8-4de3-8a46-b7890fba221f Spain
6a55a21b-cd0d-41df-a024-ce8c6c08c14d Hungary
615da9cb-451f-4390-8445-30e3109228c7 Belgium
f06bdaf0-4693-43e8-9136-c1492d5b2ecb Sweden
1a4162de-a14f-4c51-99fe-3d9a6924a41c Sweden
20c0fa5d-29e9-498a-a2a5-17c8b064acf3 Germany
05f66539-c562-4901-b9c5-9ef875bf544b France
701fc858-9a3d-46f4-be67-bf0051b31b4b Poland
f7571115-aa20-48cf-bc63-f63c1f65b317 Poland
861c9b80-73d2-429e-9ab2-6c343d5ab1ab Estonia
36b56e54-fa21-44cd-95b5-fff79997c8e7 Croatia
b65e90bc-6967-4a41-a789-0b27f0eaa3ea Hungary
8498d0d8-6b2a-45cf-9db9-5d6666c1b80e Netherlands
7021a396-54c9-459d-bf90-1c9ff93c2cd2 Bulgaria
4d65755d-fc85-461c-b3e2-6346e82c233f Portugal
5767b088-ecfe-4521-9fd4-072f4d029274 Greece
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.153 kg
Package Level 1 EAN4016779876490
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712295
E-Number (Norway)4188158
E-Number (Sweden)3860604

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.