ABB 1SVR730794R3300 1SVR730794R3300 ABB CM-PVS.41S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x300-500VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR730794R3300 ABB CM-PVS.41S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x300-500VAC

1SVR730794R3300

730794

ABB

1 Pcs.

CM-PVS.41S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC CM-PVS.41S CTRL THREE-PHASE 2 C/C TOR RELAY

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779851848
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112211D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132603_EPLAN
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.139 kg
Technical
FunctionPhase failure detection
Phase sequence monitoring
Over- and undervoltage monitoring
Measuring Range(L-L) 300 ... 500 V AC
Time RangeTripping Delay (ON or OFF) ≤ 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-L) 300 ... 500 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 C/O Contacts
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 6 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 600 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
Recommended Screw Driver0.8 x 4
4.5
Pozidriv 1
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 1x 20-12 AWG
Rigid 2x 20-14 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIP797a163d-ab29-43ea-9dd5-03be208771d8 Germany
Simplified SCIP1cd92904-859c-4085-bf02-e18fe1180feb Germany
e58827e3-c908-460f-89ef-285a46e8a67c Bulgaria
589a0051-11b3-4125-9220-b1742cc45378 Germany
86282214-393a-4bc5-bb76-a814d7a36246 France
1e25fb1e-7930-4e05-8c03-ccb75167c3a8 Poland
051b7c73-649c-41f8-97b9-ba8fb2a36683 Belgium
b9581ee5-752d-4ecd-bf85-0b2906e2bb93 Belgium
dde83d83-7df4-4741-a15e-cbf08b8ffe5c Hungary
332a0327-adfd-4853-b969-623c6d7e116f Portugal
21cc156d-9d6f-4555-a33e-fe8d5dd295fd Estonia
c0403525-bfd1-490c-8640-0d865fc05ecc Sweden
56a1db4a-ed01-4c12-916b-b1617e67a7d5 Spain
893898c7-7f7e-4fe7-bf3e-4ebb8b4ff1fa Hungary
4ed91314-22a1-44fa-91d1-1f11933a7fb2 Poland
cb699b4f-8f13-4448-99a4-3714542bfad4 Poland
30e49a4a-8db5-4a4e-a5cb-4ebeecf49cda Sweden
4dc73937-01fc-4849-9eb3-aa162a6d8f84 France
9e518d27-683f-424d-87ac-34b363b16c32 Greece
f1eb9aad-313f-4977-bc80-8d76794ab504 Croatia
9c15b816-7275-44f6-8d7d-dd2b8412f7a5 Norway
c648a14a-9632-4ed8-ba81-34c6f98fdaef Netherlands
3393e3cc-e464-400f-a544-23a7ee162bf4 Germany
ec37b5b4-9f91-4f2d-bec9-3418c31fff74 Italy
adc11d9e-e621-4733-89fc-884e44a8c57c Finland
543b093a-e86c-4d99-ac53-781ffb58516f Czech Republic
18106b95-0e3f-4960-ba13-eafebc85ee1b Germany
9f9616e3-58ed-4dbe-8e7a-d2af479f4833 Denmark
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
ABB EcoSolutionsYes
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
DNV GL CertificateDNV_GL_TAA000017D
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.164 kg
Package Level 1 EAN4016779851848
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712294
E-Number (Norway)4188155
E-Number (Sweden)3860584

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.