ABB 1SVR740700R2200 1SVR740700R2200 ABB CM-MSS.23P Therm. motor protec. relay 2c/o, 110-130VAC/220-240VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR740700R2200 ABB CM-MSS.23P Therm. motor protec. relay 2c/o, 110-130VAC/220-240VAC

1SVR740700R2200

740700

ABB

1 Pcs.

CM-MSS.23P Therm. motor protec. relay 2c/o, 110-130VAC/220-240VAC CM-MSS.23P MOTOR CONTROL RELAY x PTC

Automation > Relay for thermistor protection (PTC)
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4013614496585
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112220D0201
Instructions and Manuals1SVC730700M1000
1SVC730700M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132589_EPLAN
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.163 kg
Technical
Function1 sensor circuit
Auto
manual or remote reset
Rated Control Supply Voltage (Us)110 ... 130 V AC
220 ... 240 V AC
Rated Operational VoltageAuxiliary Circuit 250 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 C/O Contacts
Terminal TypeScrewless Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Output Circuit 1 / Output Circuit 2 4 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Measuring Circuit / Output Circuit 300 V
Output Circuit 1 / Output Circuit 2 300 V
Supply Circuit / Measuring Circuit 300 V
Supply Circuit / Output Circuit 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 10 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible 2x 0.5 ... 1.5 mm²
Rigid 2x 0.5 ... 1.5 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m
Main Circuit 2.5 ... 2.7 N·m
Wire Stripping Length8 mm
Auxiliary Circuit 9 mm
Main Circuit 12 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60947-5-1
IEC/EN 60947-8
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSA(NC:) Q600
(NO:) Q600
(NC:) B600
(NO:) D300
B300
Connecting Capacity UL/CSAFlexible 2x 18-16 AWG
Rigid 2x 20-16 AWG
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG
Pilot Duty UL/CSAB300
NC B600
NC Q600
NO D300
NO Q600
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIPfd452e15-cc12-426e-8a4f-ede1a96d25e6 Germany
Simplified SCIP65d9f153-0552-431a-a2dc-d3c229791adf Germany
9b9540e0-57a5-444d-bbcf-2e8875c2835f Czech Republic
41971a59-c36a-410b-a109-7305fd8d5a5f Germany
70d5a87e-58ef-48e5-a63e-51fe05f10a90 Denmark
56d60864-ffa2-4f56-988f-72aab055434c Poland
dd9f62e0-49a7-47ba-8bb4-a9a59d2599e0 Finland
b104187c-d73c-4d03-8dee-49f5796f7e83 Croatia
f5ac5ad8-c250-4389-9c85-89e33d36f621 Norway
91f02c56-7d2d-4120-8a28-5d7b9e7aacd1 Greece
d69f383f-313d-4d3c-a85b-aff26fe53130 Portugal
90c2061e-8a33-46b1-8223-953b5d61818c Sweden
7398de06-30e4-4174-9136-56f684597fa2 France
89fa2de5-2926-4f58-a0da-bd3813b3daa1 Netherlands
bdcbbb63-e46a-46fd-975d-8b98c054e61f Germany
f476a14f-1baa-4dbb-bab8-62b93edc8a81 Italy
7a784ef8-a117-4854-af53-1a052f41e75d Sweden
32586716-bcd3-45f7-b2cb-80908f6be783 Poland
5a38623d-4f93-4063-b055-e70326581de3 Belgium
a7f8ae17-7e01-4051-bd5b-f6da67df4021 Hungary
ab9f2c72-4746-4922-b7f8-c992805fc058 Belgium
73ea5b6a-719a-402a-9ba7-177e5ba4d21f Spain
7132dee5-9673-4bb6-aee7-de978509a1be Hungary
a7b0f9db-18ab-4700-a08a-e66d5b8439c2 Estonia
4fddda4e-21df-4dc5-8e08-2a15c8798e33 Germany
152126cf-3007-4447-8b07-6c26cd171095 France
a2d580b0-b40c-429a-9afb-ee3e9f57daea Bulgaria
2d62c0e8-f5aa-4af2-9128-336bff244f80 Poland
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CB CertificateCB_DK-40837-UL
CCC CertificateCCC_2005010303165479
CQC CertificateCQC2005010303165479
cULus CertificatecULus508_20140912-E140448
Declaration of Conformity - CCC2020980303000194
Declaration of Conformity - CE1SVD981006
Declaration of Conformity - UKCA1SVD981006-10
DNV GL CertificateDNVGL_TAE00003W4
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.187 kg
Package Level 1 EAN4013614496585
External Classifications and Standards
Object Classification CodeB
ETIM 7EC002568 - Relay for thermistor protection (PTC)
ETIM 8EC002568 - Relay for thermistor protection (PTC)
ETIM 9EC002568 - Relay for thermistor protection (PTC)
eClassV11.0 : 27371503
UNSPSC39122331
E-Number (Finland)2712503
E-Number (Norway)4188166
E-Number (Sweden)3860725

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.