CM-MPS.31S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x160-300VAC CM-MPS.31S RELe CTRL TRIFaSICO 2 C/C TOR

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779851855
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112205D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132608_EPLAN
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.142 kg
Technical
FunctionPhase failure detection
Phase sequence monitoring
Over- and undervoltage monitoring
Phase unbalance detection
Measuring Range(L-L) 160 ... 300 V AC
Time RangeTripping Delay (ON or OFF) 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-L) 160 ... 300 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 C/O Contacts
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 6 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 600 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
Recommended Screw Driver0.8 x 4
4.5
Pozidriv 1
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 1x 20-12 AWG
Rigid 2x 20-14 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIP161ecf46-bb4d-443c-a7bf-c90502f2ef75 Germany
Simplified SCIPbbfabfb2-8954-4f0d-8a46-b2224af45180 Hungary
278d1c84-99be-4e11-a323-dac6423b63be Belgium
d412280b-1bcc-4683-82b2-7773962793e3 Germany
41a08d38-dfc4-47bb-82b4-0009fb31dd27 Germany
03c9f87c-1a8b-48f6-842a-de1c87a0e7ca Poland
9ddba312-e8b2-4a1e-bbac-548cefe8c4a4 Sweden
d397cca7-7a80-4119-8adb-230c8be8c1b5 Sweden
350211ca-4e69-4524-83fe-c3de2192f4f1 France
e855af62-1384-476b-ae3c-34e8d6061fcc France
1100768b-5109-4acd-839c-5fa8132f8e8a Spain
18f87fa9-5eba-42ab-a9bf-0543ef83ba13 Estonia
1beecda2-6c8d-44e7-b829-cc13f8043ec8 Poland
d4da78ed-36b5-4ec6-b160-515c0c1358ac Croatia
05bda9cf-ea8a-4ca3-84bb-b3c6eb3f4390 Hungary
9428c9e4-4bb8-456d-930b-1594a7d3d79e Greece
da72cb2d-71a7-4984-913f-ec6723b5e253 Netherlands
4c490396-6d38-4a29-a8f7-d2b83bd6cbea Portugal
06fbbf93-6e48-45ee-9af6-f0626a92ff78 Bulgaria
78d3c375-82b1-4093-b714-9666361aa0de Italy
dbc417fc-64e1-47a8-8a84-78c092500052 Germany
bde7c891-8924-467c-b22c-dc406cb47819 Czech Republic
afc39b73-4813-4415-887b-fe84fc7bc4a5 Norway
25c7a810-5542-4658-a33f-ad18c464e92c Finland
6cb0e026-d46b-493f-8f17-1f77a4b93775 Poland
457a370e-0d3c-481b-ab65-3add7722ee7f Denmark
55d03466-6a6b-41b3-a1ff-81f3bd269ded Germany
c1eed103-7242-4afe-ab9e-460677acb3b2 Belgium
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
ABB EcoSolutionsYes
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CB CertificateCB_DK-27947-UL
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
DNV GL CertificateDNV_GL_TAA000017D
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.167 kg
Package Level 1 EAN4016779851855
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712276
E-Number (Norway)4188134
E-Number (Sweden)3860586

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.