ABB 1SVR730885R3300 1SVR730885R3300 ABB CM-MPS.21S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3-N 3x180-280VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR730885R3300 ABB CM-MPS.21S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3-N 3x180-280VAC

1SVR730885R3300

730885

ABB

1 Pcs.

CM-MPS.21S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3-N=3x180-280VAC CM-MPS.21S RELe CTRL TRIFaSICO 2 C/C TOR

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779851893
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112206D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.146 kg
Technical
FunctionOver- and undervoltage monitoring
Phase failure detection
Phase unbalance detection
Phase sequence monitoring
Interrupted neutral monitoring
Measuring Range(L-N) 180 ... 280 V AC
Time RangeTripping Delay (ON or OFF) 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-N) 180 ... 280 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 c/o (SPDT) contacts
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 6 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 600 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
Recommended Screw Driver4.5
0.8 x 4
Pozidriv 1
Mounting Position1 ... 6
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 2x 20-14 AWG
Rigid 1x 20-12 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIPeca471ea-b2ec-42a3-a10d-98ecd0c53f85 Germany
Simplified SCIP10940a4a-e940-4cb4-ab1a-14fa0ca5d858 Finland
6c9668f9-700c-4253-94bb-447f49479950 Bulgaria
2a085096-4e94-4ec3-beed-fa4546cd11ce Germany
d775775a-b045-470e-b14d-d02a1569f386 France
3baf56c9-183b-4af5-96dd-f295b02b612b Belgium
6f35dfe6-5cb0-4ceb-804f-cd0f88553cf1 Hungary
908b5687-8ae8-4dec-a612-c87d194295e1 Portugal
9812ee27-0ec8-4d3b-9af7-ec11d2c0e745 Spain
6b52f8db-a754-4834-bd77-f23da8c521dc Sweden
ced1c277-2ab0-476e-9009-69c57b1c56ec France
387fe0a5-5087-4437-900a-1e56e10080e5 Belgium
cc119799-5e6b-4c26-91df-e2720ad644a7 Hungary
fba9cca7-aa0c-42d8-9355-255eb8c0c279 Germany
1a5edcf2-b120-4c20-93a6-74da1d7751dd Poland
54db8fa0-c077-481a-9271-59fdbeae141b Denmark
989a969e-61ba-4676-8324-a392a41454a1 Czech Republic
9fb297f2-f95a-4142-b180-799094d1462d Germany
c8742e04-7769-46c7-aa2a-386a3b27ad0b Netherlands
70a40233-c45e-4bb3-a847-1e303a6ace18 Germany
1e5d7778-a702-4565-bdaf-9cd6988e05a2 Italy
9ecb932a-f3b1-4f09-9b92-55ddc37bbc08 Croatia
075ab626-1a3a-44bb-a7cf-115b7e8d66ad Norway
69e65afe-7e9e-4d2a-9e87-354fb67d26ba Poland
3c53ecec-aa37-4f52-94a3-16643936547b Estonia
20c0b904-4dc3-4f79-bf25-8466e75c6d63 Poland
c35e213a-4a38-4ad2-b45c-f5e3b8472e04 Sweden
edf05874-9a61-4c68-8689-9f052b0ef195 Greece
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
ABB EcoSolutionsYes
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CB CertificateCB_DK-27947-UL
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
DNV GL CertificateDNV_GL_TAA000017D
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.171 kg
Package Level 1 EAN4016779851893
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712272
E-Number (Norway)4188132
E-Number (Sweden)3860590

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.