ABB 1SVR760488R8300 1SVR760488R8300 ABB CM-MPN.62P Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x450-720VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR760488R8300 ABB CM-MPN.62P Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x450-720VAC

1SVR760488R8300

760488

ABB

1 Pcs.

CM-MPN.62P Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x450-720VAC CM-MPN.62P RELe CTRL TRIFaSICO 2 C/C RES

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779852104
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112177D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132608_EPLAN
Dimensions
Product Net Width45 mm
Product Net Height85.6 mm
Product Net Depth / Length104.8 mm
Product Net Weight0.225 kg
Technical
FunctionAutomatic phase sequence correction
Over- and undervoltage monitoring
Phase failure detection
Phase unbalance detection
Phase sequence monitoring
Measuring Range(L-L) 450 ... 720 V AC
Time RangeTripping Delay (ON or OFF) 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-L) 450 ... 720 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2 x 1 c/o or 1 x 2 c/o contacts, configurable
Terminal TypeScrewless Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 8 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 1000 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length8 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 2x 18-16 AWG
Rigid 2x 20-16 AWG
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIP7c323206-696d-47a1-976c-f10fdb421351 Germany
Simplified SCIP184b01b7-656a-4519-816c-8094e3b688c5 Portugal
8222aa99-4beb-4563-83b6-827887785158 Germany
4094d87b-b40e-4e93-8511-ffd1bb0b97e6 Belgium
674a99a6-73aa-4693-b6cd-70a4cf524253 Finland
3112a3e0-f996-453b-8979-be56bbba4fbd Norway
64a572eb-42e0-4026-8746-ad6d8f7fa26c Germany
8c052e8c-0fa1-495b-bc41-9e36d158dbbf Poland
f2f6ff90-6bce-4145-8e24-f55282293e44 Poland
5e8e7e18-40c1-4107-8007-7971ad89cd42 Estonia
40770b0b-40ff-4684-868c-0e1a69f96f47 Denmark
a338b395-f0a8-4235-8b4a-035e9ba73065 Czech Republic
6a178e51-7c68-4bd9-aa1b-12ee499d1b41 Croatia
ab9f307e-40bf-4f15-ad26-9765a1f3709c Germany
873e2954-c963-42ba-8a55-8a0f9aed190b Italy
6096b800-762f-4f38-a6c6-6b25773e5af6 Spain
b0b757a3-f385-441f-a051-7a955009922f Hungary
d6663540-1f30-4362-a1a0-5d04da1db53e Netherlands
c0f51e9f-e446-4acb-aba9-455a9f9c5fd0 Poland
1cbc2d51-7159-40e8-be41-a01db17b10d2 France
c8782d97-7121-4806-b22e-d696ce006c1a Sweden
7541b1f4-cce9-42d2-a044-890375d1c900 Germany
334686cc-b579-4d7c-908e-11d3f402f884 Sweden
6cc6a9e2-7122-4c8b-af59-ff65b244f087 Bulgaria
3108c35c-f506-4f95-ae2c-077e56394df2 Hungary
08a4edc6-5ef5-4da6-8199-f17f386b120b Belgium
a1a4ba10-7bf5-4207-9adb-cbbfe40cc19f France
e1dca41c-0a4f-4110-8c9b-30cf061f3a94 Greece
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CB CertificateCB_DK-27946-UL
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
DNV GL CertificateDNV_GL_TAA000017D
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length52.5 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.25 kg
Package Level 1 EAN4016779852104
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712265
E-Number (Norway)4188145
E-Number (Sweden)3860612

Product Datasheet