ABB 1SVR750487R8300 1SVR750487R8300 ABB CM-MPN.52S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x350-580VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR750487R8300 ABB CM-MPN.52S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3 3x350-580VAC

1SVR750487R8300

750487

ABB

1 Pcs.

CM-MPN.52S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x350-580VAC CM-MPN.52S CTRL THREE-PHASE 2 C/C TOR RELAY

Automation > Phase monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4016779851916
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112177D0201
Instructions and Manuals1SVC730730M1000
1SVC730730M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132608_EPLAN
Dimensions
Product Net Width45 mm
Product Net Height85.6 mm
Product Net Depth / Length104.8 mm
Product Net Weight0.23 kg
Technical
FunctionAutomatic phase sequence correction
Over- and undervoltage monitoring
Phase failure detection
Phase unbalance detection
Phase sequence monitoring
Measuring Range(L-L) 350 ... 580 V AC
Time RangeTripping Delay (ON or OFF) 0 second [unit of time]
Rated Control Supply Voltage (Us)(L-L) 350 ... 580 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output2x 1 C/O or 1x 2 C/O Contact, Configurable
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Input Circuit 8 kV
Output Circuit 4 kV
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 1000 V
Output Circuit 1 / Output Circuit 2 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
Recommended Screw Driver4.5
0.8 x 4
Pozidriv 1
Mounting Position1 ... 6
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 2x 20-14 AWG
Rigid 1x 20-12 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIP18ca17d6-2ee2-4032-8491-bbfa958e51cd Germany
Simplified SCIP0e8d140a-937f-490c-aaa1-0d2675327dbe Czech Republic
9db76a38-00e0-4331-9ba4-5489d0f46a19 Germany
98aec040-4c44-4d48-b6c9-f076cd3f785c Finland
87860bd9-4538-4d3a-bd8b-7c761476ee37 Poland
9fa1c523-b851-4718-a2dd-9fed569baab0 Germany
5cc49002-4a32-4aa0-b32c-d4bcf078c6e0 Belgium
ebffd709-3f87-46af-ab38-c8517d5d8aab Germany
2fd6b0ae-dc89-4d32-81b4-6fd797e5ade7 Norway
12e64027-c1cd-4942-acaa-1d8b2f27a2c9 Belgium
d64404c3-0234-4979-9ee9-86daf9e2e89d Hungary
74aaa3b9-d593-42c3-bdf9-ca434af5fcf9 Poland
a3a6ccda-47b1-432e-b916-a01e89e3ea15 Sweden
84baa07f-dfb9-4d85-b601-6beff13fa492 Sweden
dd0df817-d5e6-4fb9-ac4a-ad63718732d2 Germany
51ec9fe5-ca65-4af0-8be2-73e1ab10c705 France
9f5ff44b-412d-4352-b3db-485f0b2a0977 France
0c5d8c44-6e36-4f3d-80c3-31ee3622a7d7 Spain
4fe377c8-26aa-4921-a25b-9ae384da6a85 Netherlands
64113f20-dc6d-425e-a181-10f390a6e3cb Hungary
08c5cdf9-4732-42e6-961b-ebb72f070eac Greece
70098e21-6e9d-4ec6-86f6-fdb3034334eb Poland
a5389ac7-a89e-42c1-8824-ad3f6e898f59 Estonia
c5cb26f3-8f08-4aae-ad5c-bdd02ebd7134 Croatia
d2db2f11-2993-443b-ab77-9a6189a79de3 Portugal
242adf74-365a-47c9-a83f-517adbf053c5 Bulgaria
4f59d0f0-b0a7-4bb9-9296-5b7a91fe1e71 Denmark
a9ad2a4b-c9ab-49a5-a6a1-00610818fa56 Italy
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
ABB EcoSolutionsYes
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CB CertificateCB_DK-27946-UL
CQC CertificateCQC2009010303326655
cULus CertificatecULus508_20120829-E140448
Declaration of Conformity - CCC2020980303000197
Declaration of Conformity - CE1SVD981014-00
Declaration of Conformity - UKCA1SVD981014-10
DNV GL CertificateDNV_GL_TAA000017D
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length52.5 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.255 kg
Package Level 1 EAN4016779851916
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001441 - Phase monitoring relay
ETIM 8EC001441 - Phase monitoring relay
ETIM 9EC001441 - Phase monitoring relay
eClassV11.0 : 27371803
UNSPSC39122332
E-Number (Finland)2712264
E-Number (Norway)4188142
E-Number (Sweden)3860592

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.