ABB 1SVR730831R1300 1SVR730831R1300 ABB CM-ESS.1S Voltage monitoring relay 1c/o, B-C 3-600VRMS, 220-240VAC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR730831R1300 ABB CM-ESS.1S Voltage monitoring relay 1c/o, B-C 3-600VRMS, 220-240VAC

1SVR730831R1300

730831

ABB

1 Pcs.

CM-ESS.1S Voltage monitoring relay 1c/o, B-C=3-600VRMS, 220-240VAC CM-ESS.1S RELe CTL TENSIoN MONOF 1 C/C T

Automation > Voltage monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A voltage monitoring relay is deployed in electrical distribution networks to supervise voltage fluctuations, protecting sensitive loads from potential brownouts or excessive voltage spikes. ABB part number 1SVR730831R1300 delivers precise monitoring performance with adjustable timing functions to suit diverse installation requirements.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Type of electric connection (EF003961): Screw connection
  • Voltage measuring range 1 (EF006134): 3 V
  • Voltage measuring range 2 (EF006135): 3 V
  • Type of voltage measuring range (EF003399): AC/DC
  • Response value voltage (EF008193): 3 V
  • Min. adjustable delay-on energization time (EF008190): 1 s
  • Min. adjustable off-delay time (EF008192): 1 s
  • Width (EF000008): 22.5 mm
  • Height (EF000040): 85.6 mm
  • Depth (EF000049): 103.7 mm

More info

▲

The CM-ESS.1S is a single-functional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 220 - 240 V AC and has a 1 c/o (SPDT) output contact rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 3-60 A, 30-300 V and 60-600 V and works according to the open-circuit principle. The CM-ESS.1S is configurable for over- or undervoltage monitoring, the hysteresis is adjustable within a range of 3 to 30 % of the threshold value. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.

Ordering

  • EAN:
    4016779852203
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    97 mm
  • Package Level 1 Height:
    109 mm
  • Package Level 1 Length:
    30 mm
  • Package Level 1 Gross Weight:
    0.186 kg

Dimensions

  • Product Net Width:
    22.5mm
  • Product Net Depth:
    103.7mm
  • Product Net Height:
    85.6mm
  • Product Net Weight:
    0.164kg

Technical

  • Function:
    Over- or undervoltage monitoring
  • Measuring Range:
    3 ... 30 V
    6 ... 60 V
    30 ... 300 V
    60 ... 600 V
  • Rated Control Supply Voltage (Us):
    220 ... 240 V AC
  • Output:
    1 c/o (SPDT) contact
  • Terminal Type:
    Screw Terminals
  • Rated Operational Current AC-12 (Ie):
    (230 V) 4 A
  • Rated Operational Current AC-15 (Ie):
    (230 V) 3 A
  • Rated Operational Current DC-12 (Ie):
    (24 V) 4 A
  • Rated Operational Current DC-13 (Ie):
    (24 V) 2 A
  • Minimum Switching Capacity:
    24 V
    10 mA
  • Rated Insulation Voltage (Ui):
    Measuring Circuit / Output Circuit 600 V
    Output Circuit 1 / Output Circuit 2 250 V
    Supply Circuit / Measuring Circuit 600 V
    Supply Circuit / Output Circuit 250 V
  • Rated Impulse Withstand Voltage (Uimp):
    Measuring Circuit / Output Circuit 6 kV
    Output Circuit 1 / Output Circuit 2 4 kV
    Supply Circuit / Measuring Circuit 6 kV
    Supply Circuit / Output Circuit 4 kV
  • Degree of Protection:
    Housing IP50
    Terminals IP20
  • Overvoltage Category:
    III
  • Pollution Degree:
    3
  • Short-Circuit Protective Devices:
    Output Circuit NC - F Type Fuses 6 A
    Output Circuit NO - F Type Fuses 10 A
  • Electrical Durability:
    AC-12 100000 cycle
  • Mechanical Durability:
    30000000 cycle
  • Connecting Capacity:
    Flexible with Ferrule 1x 0.5 ... 2.5 mm²
    Flexible with Ferrule 2x 0.5 ... 1.5 mm²
    Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
    Flexible 1x 0.5 ... 2.5 mm²
    Flexible 2x 0.5 ... 1.5 mm²
    Rigid 1x 0.5 ... 4 mm²
    Rigid 2x 0.5 ... 2.5 mm²
  • Tightening Torque:
    0.6 ... 0.8 N·m
  • Wire Stripping Length:
    8 mm
  • Mounting Position:
    Any
  • Mounting on DIN Rail:
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Standards:
    IEC/EN 60255-1
    IEC/EN 60255-27
    EN 50178

Environmental

  • Ambient Air Temperature:
    Operation -20 ... +60 °C
    Storage -40 ... +85 °C
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Output Circuit 300 V AC
  • Contact Rating UL/CSA:
    B300
  • Connecting Capacity UL/CSA:
    Flexible 1x 18 ... 14 AWG
    Flexible 2x 18 ... 16 AWG
    Rigid 1x 20 ... 12 AWG
    Rigid 2x 20 ... 14 AWG
  • Tightening Torque UL/CSA:
    7.08 in·lb

Certificates and Declarations (Document Number)

Classifications

  • Object Classification Code:
    B
  • E-nummer:
    3860623
  • ETIM 4:
    EC001438 - Voltage monitoring relay
  • ETIM 5:
    EC001438 - Voltage monitoring relay
  • eClass:
    7.0 27371801

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.