ABB 1SVR730850R2200 1SVR730850R2200 ABB CM-ENS.23S Liquid level monitoring relay 1c/o, sensitivity 0.1-1000kOhm View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SVR730850R2200 ABB CM-ENS.23S Liquid level monitoring relay 1c/o, sensitivity 0.1-1000kOhm

1SVR730850R2200

730850

ABB

1 Pcs.

CM-ENS.23S Liquid level monitoring relay 1c/o, sensitivity 0.1-1000kOhm CM-ENS.23S LIQ LEVEL CONTROL RELAY.

Automation > (Fill) level monitoring relay
Monitoring

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
EAN4013614502897
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC112229D0201
Instructions and Manuals1SVC730680M1001
1SVC730680M0001
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132575_EPLAN
Dimensions
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.154 kg
Technical
FunctionFilling or draining monitoring
Number of Electrodes3
Measuring Range0
1 ... 1000 kΩ
Rated Control Supply Voltage (Us)110 ... 130 V AC
220 ... 240 V AC
Rated Frequency (f)Supply Circuit 50/60 Hz
Output1 C/O (SPDT) Contact
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity12 V
10 mA
Rated Impulse Withstand Voltage (Uimp)Measuring Circuit / Output Circuit 4 kV
Output Circuit 1 / Output Circuit 2 4 kV
Supply Circuit / Measuring Circuit 4 kV
Supply Circuit / Output Circuit 4 kV
Rated Insulation Voltage (Ui)Measuring Circuit / Output Circuit 300 V
Output Circuit 1 / Output Circuit 2 300 V
Supply Circuit / Measuring Circuit 300 V
Supply Circuit / Output Circuit 300 V
Degree of ProtectionHousing IP50
Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 6 A
Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 1000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Control Circuit 0.9 N·m
Main Circuit 1 N·m
Wire Stripping Length8 mm
Main Circuit 10 mm
Recommended Screw Driver0.8 x 4
4.5
Pozidriv 1
Mounting Position1 ... 5
1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG
Flexible 2x 18-16 AWG
Rigid 1x 20-12 AWG
Rigid 2x 20-14 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
SCIPa02af647-a634-4433-a0d2-5db5f105a229 Germany
Simplified SCIP820f4393-360c-4766-bd04-7d334fa889c7 Estonia
ccf2fd05-9bec-4e30-ab2e-1296dc91fc78 Sweden
f0fea5e9-3030-45c6-aaa8-7a64df1872d8 Poland
41d3ad15-a19b-4d95-8d0a-3a28fa8a51d3 Greece
bd03a70d-0819-43da-a9b5-13dcb1368815 Netherlands
6f2594f8-1a38-4d90-827a-77d4ce2cd586 Sweden
54935558-12fc-4f3e-ad91-10379582d962 France
b31a02bc-264c-4f88-8d9e-57fff6af1269 Norway
f4b3745c-37da-4cd7-981a-906a59083eca Croatia
aa0c0e5a-10e6-46f9-a6e9-8a1d5fd3bb6a Spain
1de84df5-9fc0-4c30-9ccd-711909ae0882 Portugal
c7524b58-dfb0-4c8d-8d94-15ee19e302b3 Hungary
9452fd5f-9ccf-4cd6-a26f-9b0b000d63b8 Belgium
3eaf3016-4393-480e-8a87-6212081070c5 Italy
f85bd40c-c3a2-4045-9747-4aed91621ae5 Germany
dc460f81-5b96-4edb-9763-7e7e4e69361a Germany
83af4f6f-460a-4f8c-9e0c-9bb6a4742e32 Czech Republic
09475ef6-bd8a-438d-99bc-d9d0b9144c01 Poland
1467fc13-7ac0-4702-a861-fee8d37ba02f Denmark
475f6b4e-e0f0-4e58-972e-66240cf72049 Hungary
8aa9a114-3b6d-4e95-8b2a-7d2980ed4e42 Bulgaria
9ebd46d1-7b85-49f2-9066-12160f2fc3d1 France
c21c3cb5-05ef-476d-8348-86fd17f7bb95 Germany
fd0ddc47-2fb5-4ffb-b047-b74ff21f3960 Germany
fe6b355c-27b2-46cf-95b7-6971e37c70cf Poland
d76da423-3288-45b2-b2b0-3f75be118675 Belgium
28b74c3e-eb36-4da3-b498-98d850e88a4c Finland
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutions
ABB EcoSolutionsYes
Environmental Product Declaration - EPD1SAC200438H0001
Certificates and Declarations
CQC CertificateCQC2015010303819793
cULus CertificatecULus508_20150627-E140448
Declaration of Conformity - CCC2020980303000198
Declaration of Conformity - CE1SVD981005-00
Declaration of Conformity - UKCA1SVD981005-10
DNV GL CertificateDNV_GL_TAA00000RW
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.179 kg
Package Level 1 EAN4013614502897
External Classifications and Standards
Object Classification CodeB
ETIM 7EC001447 - (Fill) level monitoring relay
ETIM 8EC001447 - (Fill) level monitoring relay
ETIM 9EC001447 - (Fill) level monitoring relay
eClassV11.0 : 27371813
UNSPSC39122331
E-Number (Finland)2712570
E-Number (Norway)4189437

ETIM for 1SVR730850R2200 Relays (EC001447)
Feature Name Feature Value
Type of electric connection (EF003961) Screw connection
With detachable clamps (EF003340) No
Number of inputs for electrodes (EF003427) 3
Min. adjustable operate delay time (EF008195) 0 s
Max. permitted operate delay time (EF008194) 0 s
Min. adjustable off-delay time (EF008192) 0 s
Max. permitted off-delay time (EF008191) 0 s
Response value sensitivity adjustable (EF003429) Yes
Physical measurement principle (EF008238) Conductive
Cascadable (EF000507) Yes
Width (EF000008) 22.5 mm
Height (EF000040) 85.6 mm
Depth (EF000049) 103.7 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.