ABB 1SBL407001R1411 1SBL407001R1411 ABB AF96-30-11-14 250-500V50/60HZ-DC Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SBL407001R1411 ABB AF96-30-11-14 250-500V50/60HZ-DC Contactor

1SBL407001R1411

407001

ABB

1 Pcs.

AF96-30-11-14 250-500V50/60HZ-DC Contactor AF96-30-11-14 CONT. 3P B. 250-500VAC-DC

Automation > Power contactor, AC switching
AF contactors 40A to 100A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
EPLAN Data9AAC175976_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals1SBC101036M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width82 mm
Product Net Depth / Length116 mm
Product Net Height125.5 mm
Product Net Weight1.21 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 1000 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 130 A
(690 V) 60 °C 105 A
(690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 96 A
(440 V) 60 °C 96 A
(500 V) 60 °C 80 A
(690 V) 60 °C 57 A
(1000 V) 60 °C 30 A
(380 / 400 V) 60 °C 105 A
(220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 96 A
(440 V) 60 °C 96 A
(500 V) 60 °C 80 A
(690 V) 60 °C 57 A
(380 / 400 V) 60 °C 105 A
(220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 125 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 130 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 130 A
(110 V) 2 Poles in Series, 60 °C 105 A
(110 V) 2 Poles in Series, 70 °C 90 A
(110 V) 3 Poles in Series, 40 °C 130 A
(110 V) 3 Poles in Series, 60 °C 105 A
(110 V) 3 Poles in Series, 70 °C 90 A
(220 V) 3 Poles in Series, 40 °C 130 A
(220 V) 3 Poles in Series, 60 °C 105 A
(220 V) 3 Poles in Series, 70 °C 90 A
(72 V) 1-Pole, 40 °C 130 A
(72 V) 1-Pole, 60 °C 105 A
(72 V) 1-Pole, 70 °C 90 A
(72 V) 2 Poles in Series, 40 °C 130 A
(72 V) 2 Poles in Series, 60 °C 105 A
(72 V) 2 Poles in Series, 70 °C 90 A
(72 V) 3 Poles in Series, 40 °C 130 A
(72 V) 3 Poles in Series, 60 °C 105 A
(72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 1.1 A / 121 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)(415 V) 55 kW
(440 V) 55 kW
(500 V) 55 kW
(690 V) 55 kW
(1000 V) 40 kW
(380 / 400 V) 45 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 25 kW
(220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)(415 V) 55 kW
(440 V) 55 kW
(500 V) 55 kW
(690 V) 55 kW
(380 / 400 V) 45 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 25 kW
(220 / 230 / 240 V) 30 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 1000 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Coil ConsumptionAverage Holding Value 50 / 60 Hz 4 V·A
Average Holding Value 50 Hz 4 V·A
Average Holding Value 60 Hz 4 V·A
Average Holding Value DC 2 W
Average Holding Value, from Warm State 2 W
Power Lossat 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 8.2 W
at Rated Operating Conditions AC-3 per Pole 4.5 W
Operate TimeBetween Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M4 or 2 x M6 Screws Placed Diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 6 ... 50 mm²
Flexible with Insulated Ferrule 1/2x 6 ... 50 mm²
Rigid Stranded 1x 6 ... 70 mm²
Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 17 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw DriverPozidriv PZ
Tightening TorqueAuxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 6 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 115 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 7-1/2 hp
(200 ... 208 V AC) Three Phase 30 hp
(220 ... 240 V AC) Three Phase 40 hp
(240 V AC) Single Phase 20 hp
(440 ... 480 V AC) Three Phase 75 hp
(550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSARigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 53 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 80 A
(200 ... 208 V AC) Three Phase 92 A
(220 ... 240 V AC) Three Phase 80 A
(240 V AC) Single Phase 88 A
(440 ... 480 V AC) Three Phase 77 A
(550 ... 600 V AC) Three Phase 77 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Resistance to Vibrations3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree3
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP5c718d5a-8940-4272-b649-5a1dc758d49c China
Simplified SCIP0f4b2ff6-641d-47b1-9b39-1084d8224fdf Hungary
ec1679bf-566b-4b69-a0b4-852d2389de43 Norway
dd9299ba-fed0-4adc-9258-e4aeaac22b77 Czech Republic
465cbee0-c9f0-4718-93b9-9cd8bd931539 Belgium
8e7c0c74-d491-4374-a147-8e87ff0b8af8 Spain
38d1681e-edf3-49a2-aa4f-8092388318a0 Croatia
cfdad1f7-de6f-4fac-b0ab-3f6604490805 Germany
803596bd-cb02-4000-b4a8-636e0b793965 Sweden
11f3aeea-9e98-428e-8ecb-7bf2532b6698 Germany
e06df6e1-653f-4116-aa3b-31edada9dc7e France
3bb36295-3c61-4c79-a27d-90b3fad16f5a France
447f0cc3-5d4c-47f1-adc2-42cf613bedf4 Poland
fa2afb22-271c-45d9-86e4-fa411574b766 Germany
f2fb39d2-2153-46e9-8bb1-b063a4f95c7a Denmark
d1f6b9bd-3fac-4436-a52d-2dda1a37aa76 Germany
38d6096f-e579-4175-82cd-132a49f26cab Sweden
faebf08a-16e6-4bdb-b285-45dd12850e58 Germany
a17324b8-c69f-4f56-892a-48ee4b645a24 Portugal
6afe9b54-e758-418d-a3de-8017c9a31f65 Belgium
76aa757d-ec7d-4e5e-9c19-1112ff6a9611 Greece
cf70b992-6d7d-41ab-b146-e4467675a042 Bulgaria
69ff1aaa-00b4-48e9-9259-a06e954280cf Poland
cfcfa10f-41fd-4c83-a5af-96039c57f9e3 Netherlands
aff01397-b690-49fb-a1a1-1c663f3b4c0a Poland
f3769d54-d199-4fea-be86-53b25f420a9c Finland
0deda286-7af2-40e3-8e30-a174ea042b2f Estonia
4698e9a0-1267-4519-a455-cf78a5301e9c Hungary
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutionsYes
End Of Life Disassembling Instructions1SBC101081M6801
Environmental Product Declaration - EPD1SBD250584E1000
Certificates and Declarations
A2L Certificate – UL9AKK108469A4890
9AKK108469A4892
ABS CertificateABS_20-2060694-PDA
BV CertificateBV_2634H36994A
CB CertificateCB_SE-116522
CCC CertificateCCC_2024010304656667
Declaration of Conformity - CCC2020980304001255
Declaration of Conformity - CE1SBD250000U1000
Declaration of Conformity - UKCA1SBD250031U1000
DNV CertificateDNV_TAE00001AF-4
KC CertificateKC_HW02016-15011C
LR CertificateLRS_LR23403517TA-02
RINA CertificateRINA_ELE084013XG
RMRS CertificateRMRS_1802705280
UL CertificateUL-US-L312527-1141-10303102-19
UL-CA-L312527-4141-10303102-19
UL Listing CardUL_E312527
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width150 mm
Package Level 1 Depth / Length150 mm
Package Level 1 Height103 mm
Package Level 1 Gross Weight1.33 kg
Package Level 1 EAN3471523133341
Package Level 2 Unitsbox 8 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height300 mm
Package Level 2 Gross Weight10.64 kg
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3707143

ETIM for 1SBL407001R1411 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 250 V
Rated control supply voltage AC 60 Hz (EF003979) 250 V
Rated control supply voltage DC (EF003980) 250 V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 130 A
Rated operation current Ie at AC-3, 400 V (EF001392) 105 A
Rated operation power at AC-3, 400 V (EF001364) 45 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.