ABB AF80-40-00-41 AF80-40-00-41 1SBL397201R4100 ABB AF80-40-00-41 24-60V50/60HZ Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AF80-40-00-41 1SBL397201R4100 ABB AF80-40-00-41 24-60V50/60HZ Contactor

AF80-40-00-41

1SBL397201R4100

ABB

1 Pcs.

AF80-40-00-41 24-60V50/60HZ Contactor AF80-40-00-41 24-60V CONT 4P BOB. AC

Automation > Power contactor, AC switching
AF contactors 40A to 100A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Engineered as a heavy-duty contactor, the ABB AF80-40-00-41 unit controls high-capacity electrical loads within industrial automation and power systems. Large contactors are vital for operating heavy machinery, large motor loads, and industrial heating applications with reliable remote switching.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of Main Contacts NO: 4
  • Number of Main Contacts NC: 0
  • Number of Auxiliary Contacts NO: 0
  • Number of Auxiliary Contacts NC: 0
  • Rated Operational Voltage: Main Circuit 690 V
  • Rated Frequency (f): Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (I th ): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
  • Rated Operational Current AC-1 (I e ): (690 V) 40 °C 125 A (690 V) 60 °C 105 A (690 V) 70 °C 90 A
  • Maximum Electrical Switching Frequency: AC-1 600 cycles per hour
  • Rated Insulation Voltage (U i ): acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
  • Rated Impulse Withstand Voltage (U imp ): 8 kV
  • Maximum Mechanical Switching Frequency: 3600 cycles per hour
  • Rated Control Circuit Voltage (U c ): 50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation - V
  • Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 6...50 mm² Rigid 1x 6...70 mm² Rigid 2x 6...50 mm²
  • Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1...2.5 mm²
  • Wire Stripping Length: Main Circuit 17 mm

More info

▲

AF80 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated - Accessories: a wide range of accessories is available.

Ordering

  • EAN:
    3471523133709
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    90mm
  • Product Net Depth:
    116mm
  • Product Net Height:
    125.5mm
  • Product Net Weight:
    1.49kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    150 mm
  • Package Level 1 Length:
    150 mm
  • Package Level 1 Height:
    103 mm
  • Package Level 1 Gross Weight:
    1.62 kg
  • Package Level 1 EAN:
    3471523133709

Technical

  • Number of Main Contacts NO:
    4
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Rated Frequency (f):
    Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 125 A
    (690 V) 60 °C 105 A
    (690 V) 70 °C 90 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 60 °C 80 A
    (380 / 400 V) 60 °C 80 A
    (415 V) 60 °C 80 A
    (440 V) 60 °C 80 A
    (500 V) 60 °C 65 A
    (690 V) 60 °C 49 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 22 kW
    (380 / 400 V) 37 kW
    (415 V) 45 kW
    (440 V) 45 kW
    (500 V) 45 kW
    (690 V) 45 kW
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 24 ... 60 V
    60 Hz 24 ... 60 V
    DC Operation - V
  • Connecting Capacity-Main Circuit:
    Flexible with Ferrule 1/2x 6...50 mm²
    Rigid 1x 6...70 mm²
    Rigid 2x 6...50 mm²
  • Connecting Capacity-Control Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
    Rigid 1/2x 1...2.5 mm²
  • Wire Stripping Length:
    Main Circuit 17 mm
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60...+80 °C
    Near Contactor for Operation in Free Air -40 ... +70 °C
  • Maximum Operating Altitude Permissible:
    3000 m

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 105 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 7-1/2 Hp
    (240 V AC) Single Phase 15 Hp
    (200 ... 208 V AC) Three Phase 25 Hp
    (220 ... 240 V AC) Three Phase 30 Hp
    (440 ... 480 V AC) Three Phase 60 Hp
    (550 ... 600 V AC) Three Phase 75 Hp

Certificates and Declarations (Document Number)

Classifications

  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • UNSPSC:
    39121529