ABB 1SBL387001R1222 1SBL387001R1222 ABB AF65-30-22-12 48-130V50/60HZ-DC Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SBL387001R1222 ABB AF65-30-22-12 48-130V50/60HZ-DC Contactor

1SBL387001R1222

387001

ABB

1 Pcs.

AF65-30-22-12 48-130V50/60HZ-DC Contactor AF65-30-22-12 CONT. 3P B. 48-130VAC-DC

Automation > Power contactor, AC switching
AF contactors 40A to 100A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Instructions and Manuals1SBC101036M6801
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width55 mm
Product Net Depth / Length144 mm
Product Net Height125.5 mm
Product Net Weight1.02 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 105 A
(690 V) 60 °C 90 A
(690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 65 A
(440 V) 60 °C 65 A
(500 V) 60 °C 55 A
(690 V) 60 °C 39 A
(380 / 400 V) 60 °C 65 A
(220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 65 A
(440 V) 60 °C 65 A
(500 V) 60 °C 55 A
(690 V) 60 °C 39 A
(380 / 400 V) 60 °C 65 A
(220 / 230 / 240 V) 60 °C 65 A
Rated Operational Power AC-3 (Pe)(400 V) 30 kW
(415 V) 37 kW
(440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
(380 / 400 V) 30 kW
(220 / 230 / 240 V) 18.5 kW
Rated Operational Power AC-3e (Pe)(415 V) 37 kW
(440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
(380 / 400 V) 30 kW
(220 / 230 / 240 V) 18.5 kW
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 105 A
(110 V) 2 Poles in Series, 60 °C 90 A
(110 V) 2 Poles in Series, 70 °C 80 A
(110 V) 3 Poles in Series, 40 °C 105 A
(110 V) 3 Poles in Series, 60 °C 90 A
(110 V) 3 Poles in Series, 70 °C 80 A
(220 V) 3 Poles in Series, 40 °C 105 A
(220 V) 3 Poles in Series, 60 °C 90 A
(220 V) 3 Poles in Series, 70 °C 80 A
(72 V) 1-Pole, 40 °C 105 A
(72 V) 1-Pole, 60 °C 90 A
(72 V) 1-Pole, 70 °C 80 A
(72 V) 2 Poles in Series, 40 °C 105 A
(72 V) 2 Poles in Series, 60 °C 90 A
(72 V) 2 Poles in Series, 70 °C 80 A
(72 V) 3 Poles in Series, 40 °C 105 A
(72 V) 3 Poles in Series, 60 °C 90 A
(72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 105 A
(110 V) 2 Poles in Series, 60 °C 90 A
(110 V) 2 Poles in Series, 70 °C 80 A
(110 V) 3 Poles in Series, 40 °C 105 A
(110 V) 3 Poles in Series, 60 °C 90 A
(110 V) 3 Poles in Series, 70 °C 80 A
(220 V) 3 Poles in Series, 40 °C 105 A
(220 V) 3 Poles in Series, 60 °C 90 A
(220 V) 3 Poles in Series, 70 °C 80 A
(72 V) 1-Pole, 40 °C 105 A
(72 V) 1-Pole, 60 °C 90 A
(72 V) 1-Pole, 70 °C 80 A
(72 V) 2 Poles in Series, 40 °C 105 A
(72 V) 2 Poles in Series, 60 °C 90 A
(72 V) 2 Poles in Series, 70 °C 80 A
(72 V) 3 Poles in Series, 40 °C 105 A
(72 V) 3 Poles in Series, 60 °C 90 A
(72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 105 A
(110 V) 2 Poles in Series, 60 °C 90 A
(110 V) 2 Poles in Series, 70 °C 80 A
(110 V) 3 Poles in Series, 40 °C 105 A
(110 V) 3 Poles in Series, 60 °C 90 A
(110 V) 3 Poles in Series, 70 °C 80 A
(220 V) 3 Poles in Series, 40 °C 105 A
(220 V) 3 Poles in Series, 60 °C 90 A
(220 V) 3 Poles in Series, 70 °C 80 A
(72 V) 1-Pole, 40 °C 105 A
(72 V) 1-Pole, 60 °C 90 A
(72 V) 1-Pole, 70 °C 80 A
(72 V) 2 Poles in Series, 40 °C 105 A
(72 V) 2 Poles in Series, 60 °C 90 A
(72 V) 2 Poles in Series, 70 °C 80 A
(72 V) 3 Poles in Series, 40 °C 105 A
(72 V) 3 Poles in Series, 60 °C 90 A
(72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Operate TimeBetween Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 4 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²
Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 16 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal TypeScrew Terminals
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 90 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 5 hp
(200 ... 208 V AC) Three Phase 20 hp
(220 ... 240 V AC) Three Phase 25 hp
(240 V AC) Single Phase 15 hp
(440 ... 480 V AC) Three Phase 50 hp
(550 ... 600 V AC) Three Phase 60 hp
Connecting Capacity Main Circuit UL/CSARigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 35 in·lb
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Resistance to Vibrations3g Closed Position & 3g Open Position 5 ... 300 Hz
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Information2CMT2021-006277
RoHS StatusFollowing EU Directive 2011/65/EU
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Circular Value
End of Life Instructions1SBC101081M6801
Eco Transparency
Environmental Product Declaration - EPD2TFP200016A1001
1SBD250584E1000
Certificates and Declarations
ABS CertificateABS_20-2060694-PDA
BV CertificateBV_2634H36994B1
CB CertificateCB_SE-113324
CCC CertificateCCC_2012010304589737
CCC_2015010304824714
CQC CertificateCQC2015010304824714
CQC2012010304589737
Declaration of Conformity - CCC2020980304001256
2020980304001074
Declaration of Conformity - CE1SBD250000U1000
Declaration of Conformity - UKCA1SBD250031U1000
DNV CertificateDNV_TAE00001AF-4
EAC CertificateEAC_RU_FRME77B03447
KC CertificateKC_HW02016-15003C
LR CertificateLRS_LR23403517TA-02
RINA CertificateRINA_ELE084013XG
RMRS CertificateRMRS_1802705280
UL CertificateUL-US-L312527-1141-10303102-9
UL-CA-L312527-4141-10303102-9
UL Listing CardUL_E312527
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width180 mm
Package Level 1 Depth / Length150 mm
Package Level 1 Height102 mm
Package Level 1 Gross Weight1.16 kg
Package Level 1 EAN3471523132825
Package Level 2 Unitsbox 6 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height300 mm
Package Level 2 Gross Weight6.96 kg
Package Level 3 Units144 piece
Classifications
Object Classification CodeQ
ETIM 4EC000066 - Magnet contactor, AC-switching
ETIM 5EC000066 - Magnet contactor, AC-switching
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3707116

ETIM for 1SBL387001R1222 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 48 V
Rated control supply voltage AC 60 Hz (EF003979) 48 V
Rated control supply voltage DC (EF003980) 48 V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 105 A
Rated operation current Ie at AC-3, 400 V (EF001392) 65 A
Rated operation power at AC-3, 400 V (EF001364) 30 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 2
Number of auxiliary contacts as normally closed contact (EF001377) 2
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.