View larger
AF40-40-00-41 1SBL347201R4100 ABB AF40-40-00-41 24-60V50/60HZ Contactor
AF40-40-00-41
1SBL347201R4100
ABB
1 Pcs.
Automation > Power contactor, AC switching
AF contactors 40A to 100A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed as a contactor, this ABB AF40-40-00-41 device manages the connection and interruption of heavy electrical currents in industrial power circuits. Contactors are widely deployed in manufacturing facilities to automate motor control, heating systems, and high-capacity lighting arrays safely.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of Main Contacts NO: 4
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 0
- Rated Operational Voltage: Main Circuit 690 V
- Rated Frequency (f): Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (I th ): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
- Rated Operational Current AC-1 (I e ): (690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A
- Maximum Electrical Switching Frequency: AC-1 600 cycles per hour
- Rated Insulation Voltage (U i ): acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
- Rated Impulse Withstand Voltage (U imp ): 6 kV
- Maximum Mechanical Switching Frequency: 3600 cycles per hour
- Rated Control Circuit Voltage (U c ): 50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation - V
- Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 4...35 mm² Rigid 1/2x 6...35 mm²
- Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1...2.5 mm²
- Wire Stripping Length: Main Circuit 16 mm
More info
▲AF40 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated - Accessories: a wide range of accessories is available.
Ordering
- EAN:
- 3471523133501
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85369085
Dimensions
- Product Net Width:
- 70mm
- Product Net Depth:
- 113.5mm
- Product Net Height:
- 125.5mm
- Product Net Weight:
- 1.21kg
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 150 mm
- Package Level 1 Length:
- 150 mm
- Package Level 1 Height:
- 103 mm
- Package Level 1 Gross Weight:
- 1.32 kg
- Package Level 1 EAN:
- 3471523133501
- Package Level 2 Units:
- 10 piece
- Package Level 2 Width:
- 300 mm
- Package Level 2 Length:
- 320 mm
- Package Level 2 Height:
- 500 mm
Technical
- Number of Main Contacts NO:
- 4
- Number of Main Contacts NC:
- 0
- Number of Auxiliary Contacts NO:
- 0
- Number of Auxiliary Contacts NC:
- 0
- Rated Operational Voltage:
- Main Circuit 690 V
- Rated Frequency (f):
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 70 A
(690 V) 60 °C 60 A
(690 V) 70 °C 50 A
- Rated Operational Current AC-3 (Ie):
- (220 / 230 / 240 V) 60 °C 40 A
(380 / 400 V) 60 °C 40 A
(415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
- Rated Operational Power AC-3 (Pe):
- (220 / 230 / 240 V) 11 kW
(380 / 400 V) 18.5 kW
(415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
- Maximum Electrical Switching Frequency:
- AC-1 600 cycles per hour
- Rated Insulation Voltage (Ui):
- acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
- Rated Impulse Withstand Voltage (Uimp):
- 6 kV
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
- Rated Control Circuit Voltage (Uc):
- 50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation - V
- Connecting Capacity-Main Circuit:
- Flexible with Ferrule 1/2x 4...35 mm²
Rigid 1/2x 6...35 mm²
- Connecting Capacity-Control Circuit:
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1...2.5 mm²
- Wire Stripping Length:
- Main Circuit 16 mm
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
- Terminal Type:
- Screw Terminals
Environmental
- Ambient Air Temperature:
- Close to Contactor for Storage -60...+80 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
- Maximum Operating Altitude Permissible:
- 3000 m
Technical UL/CSA
- General Use Rating UL/CSA:
- (600 V AC) 60 A
- Horsepower Rating UL/CSA:
- (120 V AC) Single Phase 3 Hp
(240 V AC) Single Phase 7-1/2 Hp
(200 ... 208 V AC) Three Phase 10 Hp
(220 ... 240 V AC) Three Phase 15 Hp
(440 ... 480 V AC) Three Phase 30 Hp
(550 ... 600 V AC) Three Phase 40 Hp
Certificates and Declarations (Document Number)
- ABS Certificate:
- ABS_15-GE1349500-PDA_90682247
- CB Certificate:
- CB_SE_77418
- Declaration of Conformity - CE:
- 1SBD250182C1000
- LR Certificate:
- LRS_1300087E1
- RMRS Certificate:
- RMRS_1400682124
Classifications
- ETIM 5:
- EC000066 - Magnet contactor, AC-switching
- UNSPSC:
- 39121529