View larger
Images are for illustrative purposes only. Please refer to data sheet for details
1SBL347001R1200 ABB AF40-30-00-12 48-130V50/60HZ-DC Contactor
1SBL347001R1200
347001
ABB
1 Pcs.
AF40-30-00-12 48-130V50/60HZ-DC Contactor
AF40-30-00-12 CONT. 3P B. 48-130VAC-DC
Automation > Power contactor, AC switching
AF contactors 40A to 100A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The ABB AF40-30-00-12 power contactor acts as a robust switching device for managing electric motors and heavy industrial loads. These units are commonly integrated into comprehensive automation panels to ensure safe power regulation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC175972_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101036M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 55 mm
- Product Net Depth / Length: 111 mm
- Product Net Height: 125.5 mm
- Product Net Weight: 0.97 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 0
- Number of Poles: 3P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC175972_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101036M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 55 mm |
| Product Net Depth / Length | 111 mm |
| Product Net Height | 125.5 mm |
| Product Net Weight | 0.97 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 70 A |
| (690 V) 60 °C 60 A | |
| (690 V) 70 °C 50 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 40 A |
| (440 V) 60 °C 40 A | |
| (500 V) 60 °C 35 A | |
| (690 V) 60 °C 25 A | |
| (380 / 400 V) 60 °C 40 A | |
| (220 / 230 / 240 V) 60 °C 40 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 40 A |
| (440 V) 60 °C 40 A | |
| (500 V) 60 °C 35 A | |
| (690 V) 60 °C 25 A | |
| (380 / 400 V) 60 °C 40 A | |
| (220 / 230 / 240 V) 60 °C 40 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 70 A |
| (110 V) 2 Poles in Series, 60 °C 60 A | |
| (110 V) 2 Poles in Series, 70 °C 50 A | |
| (110 V) 3 Poles in Series, 40 °C 70 A | |
| (110 V) 3 Poles in Series, 60 °C 60 A | |
| (110 V) 3 Poles in Series, 70 °C 50 A | |
| (220 V) 3 Poles in Series, 40 °C 70 A | |
| (220 V) 3 Poles in Series, 60 °C 60 A | |
| (220 V) 3 Poles in Series, 70 °C 50 A | |
| (72 V) 1-Pole, 40 °C 70 A | |
| (72 V) 1-Pole, 60 °C 60 A | |
| (72 V) 1-Pole, 70 °C 50 A | |
| (72 V) 2 Poles in Series, 40 °C 70 A | |
| (72 V) 2 Poles in Series, 60 °C 60 A | |
| (72 V) 2 Poles in Series, 70 °C 50 A | |
| (72 V) 3 Poles in Series, 40 °C 70 A | |
| (72 V) 3 Poles in Series, 60 °C 60 A | |
| (72 V) 3 Poles in Series, 70 °C 50 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 70 A |
| (110 V) 2 Poles in Series, 60 °C 60 A | |
| (110 V) 2 Poles in Series, 70 °C 50 A | |
| (110 V) 3 Poles in Series, 40 °C 70 A | |
| (110 V) 3 Poles in Series, 60 °C 60 A | |
| (110 V) 3 Poles in Series, 70 °C 50 A | |
| (220 V) 3 Poles in Series, 40 °C 70 A | |
| (220 V) 3 Poles in Series, 60 °C 60 A | |
| (220 V) 3 Poles in Series, 70 °C 50 A | |
| (72 V) 1-Pole, 40 °C 70 A | |
| (72 V) 1-Pole, 60 °C 60 A | |
| (72 V) 1-Pole, 70 °C 50 A | |
| (72 V) 2 Poles in Series, 40 °C 70 A | |
| (72 V) 2 Poles in Series, 60 °C 60 A | |
| (72 V) 2 Poles in Series, 70 °C 50 A | |
| (72 V) 3 Poles in Series, 40 °C 70 A | |
| (72 V) 3 Poles in Series, 60 °C 60 A | |
| (72 V) 3 Poles in Series, 70 °C 50 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 70 A |
| (110 V) 2 Poles in Series, 60 °C 60 A | |
| (110 V) 2 Poles in Series, 70 °C 50 A | |
| (110 V) 3 Poles in Series, 40 °C 70 A | |
| (110 V) 3 Poles in Series, 60 °C 60 A | |
| (110 V) 3 Poles in Series, 70 °C 50 A | |
| (220 V) 3 Poles in Series, 40 °C 70 A | |
| (220 V) 3 Poles in Series, 60 °C 60 A | |
| (220 V) 3 Poles in Series, 70 °C 50 A | |
| (72 V) 1-Pole, 40 °C 70 A | |
| (72 V) 1-Pole, 60 °C 60 A | |
| (72 V) 1-Pole, 70 °C 50 A | |
| (72 V) 2 Poles in Series, 40 °C 70 A | |
| (72 V) 2 Poles in Series, 60 °C 60 A | |
| (72 V) 2 Poles in Series, 70 °C 50 A | |
| (72 V) 3 Poles in Series, 40 °C 70 A | |
| (72 V) 3 Poles in Series, 60 °C 60 A | |
| (72 V) 3 Poles in Series, 70 °C 50 A | |
| Rated Operational Power AC-3 (Pe) | (400 V) 18.5 kW |
| (415 V) 22 kW | |
| (440 V) 22 kW | |
| (500 V) 22 kW | |
| (690 V) 22 kW | |
| (380 / 400 V) 18.5 kW | |
| (220 / 230 / 240 V) 11 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 22 kW |
| (440 V) 22 kW | |
| (500 V) 22 kW | |
| (690 V) 22 kW | |
| (380 / 400 V) 18.5 kW | |
| (220 / 230 / 240 V) 11 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Coil Consumption | Average Holding Value 50 / 60 Hz 4 V·A |
| Average Holding Value 50 Hz 4 V·A | |
| Average Holding Value 60 Hz 4 V·A | |
| Average Holding Value DC 2 W | |
| Average Holding Value, from Warm State 2 W | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 3 W |
| at Rated Operating Conditions AC-3 per Pole 1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 19 ... 105 ms |
| Between Coil De-energization and NO Contact Opening 17 ... 100 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 95 ms | |
| Between Coil Energization and NO Contact Closing 42 ... 100 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 4 ... 35 mm² |
| Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | |
| Rigid Stranded 1/2x 6 ... 35 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 16 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Recommended Screw Driver | Pozidriv PZ |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 4 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| NEMA Size | 2 |
| Continuous Current Rating NEMA | 45 A |
| Horsepower Rating NEMA | (115 V AC) Single Phase 3 Hp |
| (200 V AC) Three Phase 10 Hp | |
| (230 V AC) Single Phase 7-1/2 Hp | |
| (230 V AC) Three Phase 15 Hp | |
| (460 V AC) Three Phase 25 Hp | |
| (575 V AC) Three Phase 25 Hp | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 60 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3 hp |
| (200 ... 208 V AC) Three Phase 10 hp | |
| (220 ... 240 V AC) Three Phase 15 hp | |
| (240 V AC) Single Phase 7-1/2 hp | |
| (440 ... 480 V AC) Three Phase 30 hp | |
| (550 ... 600 V AC) Three Phase 40 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Stranded 1/2x 10-2 AWG |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 35 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 34 A |
| (200 ... 208 V AC) Three Phase 32.2 A | |
| (220 ... 240 V AC) Three Phase 42 A | |
| (240 V AC) Single Phase 40 A | |
| (440 ... 480 V AC) Three Phase 41 A | |
| (550 ... 600 V AC) Three Phase 40 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 25 g |
| Closed, Shock Direction: B1 25 g | |
| Closed, Shock Direction: B2 15 g | |
| Closed, Shock Direction: C1 25 g | |
| Closed, Shock Direction: C2 25 g | |
| Open, Shock Direction: B1 5 g | |
| Resistance to Vibrations | 3g Closed Position & 3g Open Position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 00ca9296-890b-4fa4-abb5-b4df29c70367 China |
| Simplified SCIP | bc05a665-551b-417d-a89d-36aa73d81674 Spain |
| 5b0eceb7-ed9d-4b39-a96f-1f91d3e7a48b Greece | |
| ec99eba3-5f2f-4acb-ade6-08957b1cd354 Bulgaria | |
| dbec6e3a-ae4c-46f2-bd6f-6c68a59f4c40 Belgium | |
| 2b18ac2b-f36d-4d71-8bcc-5518f3504733 Portugal | |
| 2fcdc47b-c2fc-465d-8ec6-6ebb8a2cf2e5 Germany | |
| 2f45fec8-5e13-4191-b463-1cf3101d048d Sweden | |
| 5ac10831-fe03-4c9a-bca5-f1415147bb06 Denmark | |
| b3fed76d-2c0e-4615-9b84-1b8fcf76d909 Germany | |
| 04311304-5436-4fdf-a44c-f2e5ec81d5be Germany | |
| ddc22b66-99e0-45e2-8fdd-bf4b8d451fb2 Poland | |
| fd6c7358-0d1d-475f-a5c2-c7bde9bcc8b4 Sweden | |
| 3b05454a-b2b3-4ff2-aecc-a2ef58e83b3d France | |
| db22add5-bd4c-48e5-9452-53efbf03a824 Germany | |
| 0a7afa7c-ae13-43b3-878e-c11dad4167b5 France | |
| 914a9a98-ff76-484e-b368-2ed8a71aab0a Hungary | |
| 1b018304-2b57-4d06-9810-c6e11de1e769 Estonia | |
| ab9365f3-ab05-4625-84d7-920e2b4fb096 Norway | |
| ec0502df-e334-44eb-8a73-72e91342948f Netherlands | |
| 6516d5c9-dff2-49fc-a01b-e77c6c2812ed Czech Republic | |
| c8952d74-57fe-42d2-aa4b-9154fcc4e99a Croatia | |
| 07b73775-e646-40fb-84fb-27c43550d206 Germany | |
| c1c0445c-bd4b-44ee-8d28-7ff11db0d7d9 Poland | |
| 1ff77a48-3052-4559-bd94-d73f6f7b772f Poland | |
| b1281de6-7c53-46a9-8b5f-b8280b814fd6 Belgium | |
| 86f158a8-30ed-4617-aec7-f92ba6d6be2c Finland | |
| e25ee646-b3df-4131-a9f1-6e36cb653e5a Hungary | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101081M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E1000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 91.9 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4890 |
| 9AKK108469A4892 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H36994B2 |
| CB Certificate | SE-115941 |
| CCC Certificate | CCC_2024010304648524 |
| Declaration of Conformity - CCC | 2020980304001256 |
| 2020980304001074 | |
| Declaration of Conformity - CE | 1SBD250000U1000 |
| Declaration of Conformity - UKCA | 1SBD250031U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| KC Certificate | KC_HW02016-15006C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE084013XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-L312527-1141-10303102-19 |
| UL-CA-L312527-4141-10303102-19 | |
| UL Listing Card | UL_E312527 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 150 mm |
| Package Level 1 Depth / Length | 150 mm |
| Package Level 1 Height | 97 mm |
| Package Level 1 Gross Weight | 1.07 kg |
| Package Level 1 EAN | 3471523132023 |
| Package Level 2 Units | box 10 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 300 mm |
| Package Level 2 Gross Weight | 10.7 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3706598 |
| E-Number (Sweden) | 3210032 |