View larger
AF40-22-00-41 1SBL347501R4100 ABB AF40-22-00-41 24-60V50/60HZ Contactor
AF40-22-00-41
1SBL347501R4100
ABB
1 Pcs.
Automation > Power contactor, AC switching
AF contactors 40A to 100A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Abb AF40-22-00-41 is a multi-pole contactor deployed in industrial automation setups to regulate high-demand electrical machinery and power circuits. These reliable switching components provide automated control over complex production line setups and heavy electrical loads. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of Main Contacts NO: 2
- Number of Main Contacts NC: 2
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 0
- Rated Operational Voltage: Main Circuit 690 V
- Rated Frequency (f): Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (I th ): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
- Rated Operational Current AC-1 (I e ): (690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A
- Maximum Electrical Switching Frequency: AC-1 600 cycles per hour
- Rated Insulation Voltage (U i ): acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
- Rated Impulse Withstand Voltage (U imp ): 6 kV
- Maximum Mechanical Switching Frequency: 3600 cycles per hour
- Rated Control Circuit Voltage (U c ): 50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation - V
- Connecting Capacity-Main Circuit: Flexible with Ferrule 1/2x 4...35 mm² Rigid 1/2x 6...35 mm²
- Connecting Capacity-Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1...2.5 mm²
- Wire Stripping Length: Main Circuit 16 mm
More info
▲AF40 4-pole contactors are used for controlling power circuits up to 690 V AC and 440 V DC. They are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...). AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 2 N.O. + 2 N.C. main poles, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated - Accessories: a wide range of accessories is available.
Ordering
-
- EAN:
- 3471523133808
-
- Minimum Order Quantity:
- 1 piece
-
- Customs Tariff Number:
- 85369085
Dimensions
-
- Product Net Width:
- 70mm
-
- Product Net Depth:
- 113.5mm
-
- Product Net Height:
- 125.5mm
-
- Product Net Weight:
- 1.21kg
Container Information
-
- Package Level 1 Units:
- 1 piece
-
- Package Level 1 Width:
- 150 mm
-
- Package Level 1 Length:
- 150 mm
-
- Package Level 1 Height:
- 103 mm
-
- Package Level 1 Gross Weight:
- 1.32 kg
-
- Package Level 1 EAN:
- 3471523133808
Technical
-
- Number of Main Contacts NO:
- 2
-
- Number of Main Contacts NC:
- 2
-
- Number of Auxiliary Contacts NO:
- 0
-
- Number of Auxiliary Contacts NC:
- 0
-
- Rated Operational Voltage:
- Main Circuit 690 V
-
- Rated Frequency (f):
- Main Circuit 50 / 60 Hz
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
-
- Rated Operational Current AC-1 (Ie):
- (690 V) 40 °C 70 A
(690 V) 60 °C 60 A
(690 V) 70 °C 50 A
-
- Rated Operational Current AC-3 (Ie):
- (220 / 230 / 240 V) 60 °C 40 A
(380 / 400 V) 60 °C 40 A
(415 V) 60 °C 40 A
(440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
-
- Rated Operational Power AC-3 (Pe):
- (220 / 230 / 240 V) 11 kW
(380 / 400 V) 18.5 kW
(415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
-
- Maximum Electrical Switching Frequency:
- AC-1 600 cycles per hour
-
- Rated Insulation Voltage (Ui):
- acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 6 kV
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation - V
-
- Connecting Capacity-Main Circuit:
- Flexible with Ferrule 1/2x 4...35 mm²
Rigid 1/2x 6...35 mm²
-
- Connecting Capacity-Control Circuit:
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1...2.5 mm²
-
- Wire Stripping Length:
- Main Circuit 16 mm
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
-
- Terminal Type:
- Screw Terminals
Environmental
-
- Ambient Air Temperature:
- Close to Contactor for Storage -60...+80 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
-
- Maximum Operating Altitude Permissible:
- 3000 m
Technical UL/CSA
-
- General Use Rating UL/CSA:
- (600 V AC) 60 A
-
- Horsepower Rating UL/CSA:
- (120 V AC) Single Phase 3 Hp
(240 V AC) Single Phase 7-1/2 Hp
(200 ... 208 V AC) Three Phase 10 Hp
(220 ... 240 V AC) Three Phase 15 Hp
(440 ... 480 V AC) Three Phase 30 Hp
(550 ... 600 V AC) Three Phase 40 Hp
Certificates and Declarations (Document Number)
-
- CB Certificate:
- CB_SE_77418
-
- Declaration of Conformity - CE:
- 1SBD250182C1000
Classifications
-
- ETIM 5:
- EC000066 - Magnet contactor, AC-switching
-
- UNSPSC:
- 39121529