View larger
Images are for illustrative purposes only. Please refer to data sheet for details
1SBL297001R1322 ABB AF38-30-22-13 100-250V50/60HZ-DC Contactor
1SBL297001R1322
297001
ABB
1 Pcs.
AF38-30-22-13 100-250V50/60HZ-DC Contactor
AF38-30-22-13 CONT. 3P BOB 100-250VAC-DC
Automation > Power contactor, AC switching
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Contactor 1SBL297001R1322 by ABB is an advanced industrial switching unit deployed in automation networks for precise motor control and auxiliary signal routing. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC159650_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101027M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 119.5 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.36 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 2
- Number of Auxiliary Contacts NC: 2
- Number of Poles: 3P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159650_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 119.5 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.36 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 50 A |
| (690 V) 60 °C 42 A | |
| (690 V) 70 °C 37 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 38 A |
| (440 V) 60 °C 38 A | |
| (500 V) 60 °C 33 A | |
| (690 V) 60 °C 24 A | |
| (380 / 400 V) 60 °C 38 A | |
| (220 / 230 / 240 V) 60 °C 40 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 38 A |
| (440 V) 60 °C 38 A | |
| (500 V) 60 °C 33 A | |
| (690 V) 60 °C 24 A | |
| (380 / 400 V) 60 °C 38 A | |
| (220 / 230 / 240 V) 60 °C 40 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 25 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 25 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (400 V) 18.5 kW |
| (415 V) 18.5 kW | |
| (440 V) 22 kW | |
| (500 V) 22 kW | |
| (690 V) 22 kW | |
| (380 / 400 V) 18.5 kW | |
| (220 / 230 / 240 V) 11 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 18.5 kW |
| (440 V) 22 kW | |
| (500 V) 22 kW | |
| (690 V) 22 kW | |
| (380 / 400 V) 18.5 kW | |
| (220 / 230 / 240 V) 11 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V |
| 60 Hz 100 ... 250 V | |
| DC Operation 100 ... 250 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 2.4 W | |
| at Rated Operating Conditions AC-3 per Pole 1.3 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1.5 ... 10 mm² |
| Flexible with Insulated Ferrule 1x 1.5 ... 10 mm² | |
| Flexible with Insulated Ferrule 2x 1.5 ... 4 mm² | |
| Rigid Solid 1/2x 2.5 ... 4 mm² | |
| Rigid Stranded 1/2x 2.5 ... 10 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Control Circuit 10 mm | |
| Main Circuit 14 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 2.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 50 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 2 hp |
| (200 ... 208 V AC) Three Phase 10 hp | |
| (220 ... 240 V AC) Three Phase 10 hp | |
| (240 V AC) Single Phase 5 hp | |
| (440 ... 480 V AC) Three Phase 25 hp | |
| (550 ... 600 V AC) Three Phase 30 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 14-10 AWG |
| Rigid Stranded 1/2x 14-8 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 22 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 24 A |
| (200 ... 208 V AC) Three Phase 32.2 A | |
| (220 ... 240 V AC) Three Phase 28 A | |
| (240 V AC) Single Phase 28 A | |
| (440 ... 480 V AC) Three Phase 34 A | |
| (550 ... 600 V AC) Three Phase 32 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Open, Shock Direction: B1 5 g | |
| Shock Direction: A 30 g | |
| Shock Direction: B2 15 g | |
| Shock Direction: C1 25 g | |
| Shock Direction: C2 25 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E4000 |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 86 % |
| Sustainable Material Content in Product (wt. %) | Recycled Metal - 28 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24898C0 |
| CB Certificate | CB_SE-116364 |
| CCC Certificate | CCC_2024010304656668 |
| CQC Certificate | CQC2010010304445623 |
| CQC2020010304294316 | |
| Declaration of Conformity - CCC | 2020980304001254 |
| 2020980304001052 | |
| Declaration of Conformity - CE | 1SBD250000U1000 |
| Declaration of Conformity - UKCA | 1SBD250031U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15001C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-2150887-5 |
| UL-CA-2142658-5 | |
| UL Listing Card | E312527 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 90 mm |
| Package Level 1 Depth / Length | 125 mm |
| Package Level 1 Height | 48 mm |
| Package Level 1 Gross Weight | 0.36 kg |
| Package Level 1 EAN | 3471523111738 |
| Package Level 2 Units | box 18 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 12.96 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |