ABB 1SBL276001R2300 1SBL276001R2300 ABB AF30Z-30-00-23 100-250V50/60HZ-DC Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SBL276001R2300 ABB AF30Z-30-00-23 100-250V50/60HZ-DC Contactor

1SBL276001R2300

276001

ABB

1 Pcs.

AF30Z-30-00-23 100-250V50/60HZ-DC Contactor AF30Z-30-00 CONT.3P BOB 100-250Vac-dc

Automation > Power contactor, AC switching
AF contactors to 38 A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
EPLAN Data9AAC159660_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals1SBC101027M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width45 mm
Product Net Depth / Length86 mm
Product Net Height86 mm
Product Net Weight0.35 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 50 A
(690 V) 60 °C 42 A
(690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 32 A
(440 V) 60 °C 32 A
(500 V) 60 °C 28 A
(690 V) 60 °C 21 A
(380 / 400 V) 60 °C 32 A
(220 / 230 / 240 V) 60 °C 33 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 32 A
(440 V) 60 °C 32 A
(500 V) 60 °C 28 A
(690 V) 60 °C 21 A
(380 / 400 V) 60 °C 32 A
(220 / 230 / 240 V) 60 °C 33 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 50 A
(110 V) 2 Poles in Series, 60 °C 42 A
(110 V) 2 Poles in Series, 70 °C 37 A
(110 V) 3 Poles in Series, 40 °C 50 A
(110 V) 3 Poles in Series, 60 °C 42 A
(110 V) 3 Poles in Series, 70 °C 37 A
(220 V) 3 Poles in Series, 40 °C 50 A
(220 V) 3 Poles in Series, 60 °C 42 A
(220 V) 3 Poles in Series, 70 °C 37 A
(72 V) 1-Pole, 40 °C 50 A
(72 V) 1-Pole, 60 °C 42 A
(72 V) 1-Pole, 70 °C 37 A
(72 V) 2 Poles in Series, 40 °C 50 A
(72 V) 2 Poles in Series, 60 °C 42 A
(72 V) 2 Poles in Series, 70 °C 37 A
(72 V) 3 Poles in Series, 40 °C 50 A
(72 V) 3 Poles in Series, 60 °C 42 A
(72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 50 A
(110 V) 2 Poles in Series, 60 °C 42 A
(110 V) 2 Poles in Series, 70 °C 37 A
(110 V) 3 Poles in Series, 40 °C 50 A
(110 V) 3 Poles in Series, 60 °C 42 A
(110 V) 3 Poles in Series, 70 °C 37 A
(220 V) 3 Poles in Series, 40 °C 50 A
(220 V) 3 Poles in Series, 60 °C 42 A
(220 V) 3 Poles in Series, 70 °C 37 A
(72 V) 1-Pole, 40 °C 50 A
(72 V) 1-Pole, 60 °C 42 A
(72 V) 1-Pole, 70 °C 37 A
(72 V) 2 Poles in Series, 40 °C 50 A
(72 V) 2 Poles in Series, 60 °C 42 A
(72 V) 2 Poles in Series, 70 °C 37 A
(72 V) 3 Poles in Series, 40 °C 50 A
(72 V) 3 Poles in Series, 60 °C 42 A
(72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 50 A
(110 V) 2 Poles in Series, 60 °C 42 A
(110 V) 2 Poles in Series, 70 °C 37 A
(110 V) 3 Poles in Series, 40 °C 50 A
(110 V) 3 Poles in Series, 60 °C 42 A
(110 V) 3 Poles in Series, 70 °C 37 A
(220 V) 3 Poles in Series, 40 °C 25 A
(220 V) 3 Poles in Series, 60 °C 25 A
(220 V) 3 Poles in Series, 70 °C 25 A
(72 V) 1-Pole, 40 °C 25 A
(72 V) 1-Pole, 60 °C 25 A
(72 V) 1-Pole, 70 °C 25 A
(72 V) 2 Poles in Series, 40 °C 50 A
(72 V) 2 Poles in Series, 60 °C 42 A
(72 V) 2 Poles in Series, 70 °C 37 A
(72 V) 3 Poles in Series, 40 °C 50 A
(72 V) 3 Poles in Series, 60 °C 42 A
(72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Power AC-3 (Pe)(400 V) 15 kW
(415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
Rated Operational Power AC-3e (Pe)(415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Power Lossat Rated Operating Conditions AC-1 per Pole 2.4 W
at Rated Operating Conditions AC-3 per Pole 0.9 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M4 Screws Placed Diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²
Flexible with Insulated Ferrule 2x 1.5 ... 4 mm²
Rigid Solid 1/2x 2.5 ... 4 mm²
Rigid Stranded 1/2x 2.5 ... 10 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthControl Circuit 10 mm
Main Circuit 14 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening TorqueControl Circuit 1.2 N·m
Main Circuit 2.5 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 50 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 2 hp
(200 ... 208 V AC) Three Phase 10 hp
(220 ... 240 V AC) Three Phase 10 hp
(240 V AC) Single Phase 5 hp
(440 ... 480 V AC) Three Phase 20 hp
(550 ... 600 V AC) Three Phase 25 hp
Connecting Capacity Main Circuit UL/CSARigid Solid 1/2x 14-10 AWG
Rigid Stranded 1/2x 14-8 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAControl Circuit 11 in·lb
Main Circuit 22 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 24 A
(200 ... 208 V AC) Three Phase 32.2 A
(220 ... 240 V AC) Three Phase 28 A
(240 V AC) Single Phase 28 A
(440 ... 480 V AC) Three Phase 27 A
(550 ... 600 V AC) Three Phase 27 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic Withstandaccording to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Resistance to Vibrations4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree3
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIPfec29fdf-4b73-4cc1-8c39-b0f1238d5dc4 China
Simplified SCIP0a2d9dd6-1adb-414f-935f-84dfb185b1b3 Finland
1eff5d5e-78c1-4aa6-8ef6-1331e2286e91 Hungary
2b0ef7e9-6e52-4872-b844-977f5b69aa39 Sweden
47500d6a-2877-4b7d-aa40-4c7d4e0a22e7 Germany
47c79001-197f-422d-809e-2df22b52f4d0 Netherlands
4dac8c07-ec25-40e9-af5e-d1afe6c97eb8 Bulgaria
4f7b988e-05da-4525-a1e6-6b9bc1a0c184 Spain
694031cd-0fe6-4a41-9952-1e79f463963f Belgium
7796ab05-48ed-486c-86e7-137f3d89c888 Denmark
96700f74-1f1d-4254-a5f7-39a022da4cb0 Croatia
a29a6373-1bed-43a6-847f-bd55b754be34 Portugal
aeb04b0f-198f-424a-b2ce-594890251b49 Estonia
b9d9e9d7-8c4b-441c-86a9-8797e97b7b6c Norway
dab52459-993a-49bb-a34e-09e66c78ae6d France
e399a3cb-fe83-4965-8876-141d2fe91114 Greece
ecc683c2-671e-41f9-865e-fcb5b942eb85 Czech Republic
fe243dfa-ac18-4bac-8ef1-c0d3145eeb0a Poland
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
End Of Life Disassembling Instructions1SBC101080M6801
Environmental Product Declaration - EPD1SBD250584E4000
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 94.3 %
Certificates and Declarations
A2L Certificate – UL9AKK108469A4875
9AKK108469A4879
ABS CertificateABS_20-2060694-PDA
BV CertificateBV_2634H24898C1
CB CertificateCB_SE-116364
CCC CertificateCCC_2024010304656668
CQC CertificateCQC2010010304445623
CQC2020010304294316
Declaration of Conformity - CCC2020980304001254
2020980304001052
Declaration of Conformity - CE1SBD250000U1000
Declaration of Conformity - UKCA1SBD250031U1000
DNV CertificateDNV_TAE00001AF-4
GOST CertificateGOST_POCCFR.ME77.B07175.pdf
KC CertificateKC_HW02016-15001C
LR CertificateLRS_LR23403517TA-02
RINA CertificateRINA_ELE142224XG
RMRS CertificateRMRS_1802705280
UL CertificateUL-US-2150887-5
UL-CA-2142658-5
UL Listing CardE312527
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length87 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.35 kg
Package Level 1 EAN3471523114432
Package Level 2 Unitsbox 21 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height315 mm
Package Level 2 Gross Weight15.75 kg
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3706296

ETIM for 1SBL276001R2300 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 100 V
Rated control supply voltage AC 60 Hz (EF003979) 100 V
Rated control supply voltage DC (EF003980) 100 V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 50 A
Rated operation current Ie at AC-3, 400 V (EF001392) 32 A
Rated operation power at AC-3, 400 V (EF001364) 15 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as normally closed contact (EF001377) 0
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.