View larger
1SBL237501R1400 ABB AF26-22-00-14 250-500V50/60HZ-DC Contactor
1SBL237501R1400
237501
ABB
1 Pcs.
Automation > Power contactor, AC switching
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for multi-pole power routing, the ABB AF26-22-00-14 250-500V50/60HZ-DC Contactor facilitates the automated control of complex industrial electrical systems. These switching units are routinely mounted in electrical enclosures to manage motors, resistive loads, and auxiliary control circuits safely. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC159659_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101027M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 101 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.4 kg
- Number of Main Contacts NO: 2
- Number of Main Contacts NC: 2
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 0
- Number of Poles: 4P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159659_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 101 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.4 kg |
| Technical | |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 45 A |
| (690 V) 60 °C 40 A | |
| (690 V) 70 °C 32 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 21.2 A |
| (440 V) 60 °C 20 A | |
| (500 V) 60 °C 17.6 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 22 A | |
| (220 / 230 / 240 V) 60 °C 23.2 A | |
| Rated Operational Power AC-3 (Pe) | (400 V) 11 kW |
| (415 V) 11 kW | |
| (440 V) 11 kW | |
| (500 V) 11 kW | |
| (690 V) 9 kW | |
| (220 / 230 / 240 V) 5.5 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 250 ... 500 V |
| 60 Hz 250 ... 500 V | |
| DC Operation 250 ... 500 V | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.6 W |
| at Rated Operating Conditions AC-3 per Pole 0.42 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1.5 ... 16 mm² |
| Flexible with Insulated Ferrule 1/2x 1.5 ... 16 mm² | |
| Rigid Solid 1/2x 1.5 ... 4 mm² | |
| Rigid Stranded 1/2x 1.5 ... 16 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 12 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 2.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 45 A |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG |
| Rigid Stranded 1/2x 16-6 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 22 in·lb | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 30 g |
| Closed, Shock Direction: B1 25 g | |
| Closed, Shock Direction: B2 15 g | |
| Closed, Shock Direction: C1 25 g | |
| Closed, Shock Direction: C2 25 g | |
| Open, Shock Direction: A 25 g | |
| Open, Shock Direction: B1 5 g | |
| Open, Shock Direction: B2 10 g | |
| Open, Shock Direction: C1 20 g | |
| Open, Shock Direction: C2 20 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E4000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 94.3 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24898C1 |
| CB Certificate | CB_SE-116363 |
| CCC Certificate | CCC_2024010304656668 |
| CQC Certificate | CQC2010010304445623 |
| CQC2020010304294316 | |
| Declaration of Conformity - CCC | 2020980304001254 |
| 2020980304001052 | |
| Declaration of Conformity - CE | 1SBD250001U1000 |
| Declaration of Conformity - UKCA | 1SBD250032U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15002C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE084013XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-L319322-13-72119002-5 |
| UL-CA-L319322-43-72119002-6 | |
| UL Listing Card | UL_E319322 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 103 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.4 kg |
| Package Level 1 EAN | 3471523116443 |
| Package Level 2 Units | box 18 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 14.4 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3705847 |
| E-Number (Sweden) | 3211517 |