View larger
1SBL176060R2110 ABB AF16ZB-30-10RTCONT.TR.24-60VAC20-60VDC
1SBL176060R2110
176060
ABB
1 Pcs.
Automation > Power contactor, AC switching
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Industrial control panels use devices like the ABB 1SBL176060R2110 contactor to securely establish and break power connections for automated machinery and motor circuits. These robust switches bridge control system logic with high-power industrial equipment to ensure efficient electrical distribution.
Exact pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 1SBC100220C0201
- Instructions and Manuals: 1SBC101035M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 77 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.32 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 0
- Number of Poles: 3P
- Rated Operational Voltage: Auxiliary Circuit 690 V
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100220C0201 |
| Instructions and Manuals | 1SBC101035M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.32 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 30 A |
| (690 V) 60 °C 30 A | |
| (690 V) 70 °C 26 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 20 A |
| (110 V) 1-Pole, 60 °C 20 A | |
| (110 V) 1-Pole, 70 °C 20 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 20 A | |
| (220 V) 2 Poles in Series, 60 °C 20 A | |
| (220 V) 2 Poles in Series, 70 °C 20 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A |
| (110 V) 1-Pole, 60 °C 8 A | |
| (110 V) 1-Pole, 70 °C 8 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 8 A | |
| (220 V) 2 Poles in Series, 60 °C 8 A | |
| (220 V) 2 Poles in Series, 70 °C 8 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 20 A | |
| (110 V) 2 Poles in Series, 60 °C 20 A | |
| (110 V) 2 Poles in Series, 70 °C 20 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 16 A | |
| (220 V) 3 Poles in Series, 60 °C 16 A | |
| (220 V) 3 Poles in Series, 70 °C 16 A | |
| (72 V) 1-Pole, 40 °C 16 A | |
| (72 V) 1-Pole, 60 °C 16 A | |
| (72 V) 1-Pole, 70 °C 16 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 300 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V |
| 60 Hz 24 ... 60 V | |
| DC Operation 20 ... 60 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 1.2 W | |
| at Rated Operating Conditions AC-3 per Pole 0.35 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 1.5 N·m | |
| Terminal Type | Ring-Tongue Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 30 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1-1/2 hp |
| (200 ... 208 V AC) Three Phase 5 hp | |
| (220 ... 240 V AC) Three Phase 5 hp | |
| (240 V AC) Single Phase 3 hp | |
| (440 ... 480 V AC) Three Phase 10 hp | |
| (550 ... 600 V AC) Three Phase 15 hp | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 13 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 20 A |
| (200 ... 208 V AC) Three Phase 17.5 A | |
| (220 ... 240 V AC) Three Phase 15.2 A | |
| (240 V AC) Single Phase 17 A | |
| (440 ... 480 V AC) Three Phase 14 A | |
| (550 ... 600 V AC) Three Phase 17 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 663d75b3-6128-4298-a9f8-e776806b4561 China |
| Simplified SCIP | 04ee4b9b-1246-478f-bb6a-f81e6a0030cf Sweden |
| 126aca7a-289c-4c32-a82f-b7645dc5bf0f Bulgaria | |
| 16798836-4535-4d14-995d-e937c796b089 Estonia | |
| 1bedd849-9bc0-4392-891c-832084ba631f Finland | |
| 2088f5a8-6dd0-4732-86ed-11c83e0b5ee2 Norway | |
| 2244f1d9-74fe-4de8-883d-a1d13d62fc93 Netherlands | |
| 2f15c381-c305-41b1-81fc-d5eb56f46421 Denmark | |
| 38af7d39-75c7-4315-ad6a-f9ecda419b46 Germany | |
| 47fb6762-fecf-4ed4-99bc-88f48b49b4ff Hungary | |
| 524d25e1-a6f3-43bf-85a9-2e9c9edce320 Greece | |
| 77875c99-106c-4dcb-92a6-cd6d041d59f8 Portugal | |
| 7ab6d916-809f-4cdb-95d9-766e89288a92 Czech Republic | |
| 913fd2db-800f-4b33-9fca-3cf7d5eb3690 Belgium | |
| bf9f1717-5164-4da9-b428-ec4c3b32c795 Spain | |
| d7d68474-6f2d-492e-a77a-e9188cd88694 France | |
| d8d4b9c3-c3d1-461c-888e-db83381c34d2 Poland | |
| fdac633e-3bea-47d3-848c-01df3e80e2f5 Croatia | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| Declaration of Conformity - CCC | 2020980304001253 |
| Declaration of Conformity - CE | 1SBD250004U1000 |
| Declaration of Conformity - UKCA | 1SBD250035U1000 |
| UL Listing Card | UL_E312527 |
| UR Certificate | UL_20121122-E312527_9_5 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.32 kg |
| Package Level 1 EAN | 3471523128217 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 17.28 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |