ABB 1SBL177001R1110 1SBL177001R1110 ABB AF16-30-10-11 24-60V50/60HZ 20-60VDC Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SBL177001R1110 ABB AF16-30-10-11 24-60V50/60HZ 20-60VDC Contactor

1SBL177001R1110

177001

ABB

1 Pcs.

AF16-30-10-11 24-60V50/60HZ 20-60VDC Contactor AF16-30-10 CONT.3P BOB 24-60Vac 20-60Vdc

Automation > Power contactor, AC switching
AF contactors to 38 A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
EPLAN Data9AAC159647_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals1SBC101027M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.27 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC0
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Control Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 30 A
(690 V) 60 °C 30 A
(690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 18 A
(440 V) 60 °C 18 A
(500 V) 60 °C 15 A
(690 V) 60 °C 10.5 A
(380 / 400 V) 60 °C 18 A
(220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 18 A
(440 V) 60 °C 18 A
(500 V) 60 °C 15 A
(690 V) 60 °C 10.5 A
(380 / 400 V) 60 °C 18 A
(220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 40 °C 20 A
(110 V) 1-Pole, 60 °C 20 A
(110 V) 1-Pole, 70 °C 20 A
(110 V) 2 Poles in Series, 40 °C 30 A
(110 V) 2 Poles in Series, 60 °C 30 A
(110 V) 2 Poles in Series, 70 °C 26 A
(110 V) 3 Poles in Series, 40 °C 30 A
(110 V) 3 Poles in Series, 60 °C 30 A
(110 V) 3 Poles in Series, 70 °C 26 A
(220 V) 2 Poles in Series, 40 °C 20 A
(220 V) 2 Poles in Series, 60 °C 20 A
(220 V) 2 Poles in Series, 70 °C 20 A
(220 V) 3 Poles in Series, 40 °C 30 A
(220 V) 3 Poles in Series, 60 °C 30 A
(220 V) 3 Poles in Series, 70 °C 26 A
(72 V) 1-Pole, 40 °C 30 A
(72 V) 1-Pole, 60 °C 30 A
(72 V) 1-Pole, 70 °C 26 A
(72 V) 2 Poles in Series, 40 °C 30 A
(72 V) 2 Poles in Series, 60 °C 30 A
(72 V) 2 Poles in Series, 70 °C 26 A
(72 V) 3 Poles in Series, 40 °C 30 A
(72 V) 3 Poles in Series, 60 °C 30 A
(72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 40 °C 8 A
(110 V) 1-Pole, 60 °C 8 A
(110 V) 1-Pole, 70 °C 8 A
(110 V) 2 Poles in Series, 40 °C 30 A
(110 V) 2 Poles in Series, 60 °C 30 A
(110 V) 2 Poles in Series, 70 °C 26 A
(110 V) 3 Poles in Series, 40 °C 30 A
(110 V) 3 Poles in Series, 60 °C 30 A
(110 V) 3 Poles in Series, 70 °C 26 A
(220 V) 2 Poles in Series, 40 °C 8 A
(220 V) 2 Poles in Series, 60 °C 8 A
(220 V) 2 Poles in Series, 70 °C 8 A
(220 V) 3 Poles in Series, 40 °C 30 A
(220 V) 3 Poles in Series, 60 °C 30 A
(220 V) 3 Poles in Series, 70 °C 26 A
(72 V) 1-Pole, 40 °C 30 A
(72 V) 1-Pole, 60 °C 30 A
(72 V) 1-Pole, 70 °C 26 A
(72 V) 2 Poles in Series, 40 °C 30 A
(72 V) 2 Poles in Series, 60 °C 30 A
(72 V) 2 Poles in Series, 70 °C 26 A
(72 V) 3 Poles in Series, 40 °C 30 A
(72 V) 3 Poles in Series, 60 °C 30 A
(72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 40 °C 4 A
(110 V) 1-Pole, 60 °C 4 A
(110 V) 1-Pole, 70 °C 4 A
(110 V) 2 Poles in Series, 40 °C 20 A
(110 V) 2 Poles in Series, 60 °C 20 A
(110 V) 2 Poles in Series, 70 °C 20 A
(110 V) 3 Poles in Series, 40 °C 30 A
(110 V) 3 Poles in Series, 60 °C 30 A
(110 V) 3 Poles in Series, 70 °C 26 A
(220 V) 2 Poles in Series, 40 °C 4 A
(220 V) 2 Poles in Series, 60 °C 4 A
(220 V) 2 Poles in Series, 70 °C 4 A
(220 V) 3 Poles in Series, 40 °C 16 A
(220 V) 3 Poles in Series, 60 °C 16 A
(220 V) 3 Poles in Series, 70 °C 16 A
(72 V) 1-Pole, 40 °C 16 A
(72 V) 1-Pole, 60 °C 16 A
(72 V) 1-Pole, 70 °C 16 A
(72 V) 2 Poles in Series, 40 °C 30 A
(72 V) 2 Poles in Series, 60 °C 30 A
(72 V) 2 Poles in Series, 70 °C 26 A
(72 V) 3 Poles in Series, 40 °C 30 A
(72 V) 3 Poles in Series, 60 °C 30 A
(72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)(400 V) 7.5 kW
(415 V) 9 kW
(440 V) 9 kW
(500 V) 9 kW
(690 V) 9 kW
(380 / 400 V) 7.5 kW
(220 / 230 / 240 V) 4 kW
Rated Operational Power AC-3e (Pe)(415 V) 9 kW
(440 V) 9 kW
(500 V) 9 kW
(690 V) 9 kW
(380 / 400 V) 7.5 kW
(220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 690 V
acc. to IEC 60947-5-1 690 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Power Lossat 6 A per Pole 0.1 W
at Rated Operating Conditions AC-1 per Pole 1.2 W
at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M4 Screws Placed Diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Rigid Solid 1/2x 1 ... 4 mm²
Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid Solid 1/2x 1 ... 2.5 mm²
Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening TorqueAuxiliary Circuit 1.2 N·m
Control Circuit 1.2 N·m
Main Circuit 1.5 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 30 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 1-1/2 hp
(200 ... 208 V AC) Three Phase 5 hp
(220 ... 240 V AC) Three Phase 5 hp
(240 V AC) Single Phase 3 hp
(440 ... 480 V AC) Three Phase 10 hp
(550 ... 600 V AC) Three Phase 15 hp
Connecting Capacity Main Circuit UL/CSARigid Solid 1/2x 16-10 AWG
Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG
Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 13 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 20 A
(200 ... 208 V AC) Three Phase 17.5 A
(220 ... 240 V AC) Three Phase 15.2 A
(240 V AC) Single Phase 17 A
(440 ... 480 V AC) Three Phase 14 A
(550 ... 600 V AC) Three Phase 17 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Resistance to Vibrations4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree3
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIPf7ff6eaf-0746-41f7-8f81-a89add39cd4b China
Simplified SCIPec002f2f-11b8-4c80-8d70-7fd838b2dc73 Sweden
1b4c195f-bc19-469d-b9d5-e4c5be9bcc97 Belgium
3732b39e-b39b-4943-a687-3f541333d931 Czech Republic
a453984b-8a6b-4eab-9f0d-718f0dd02815 Croatia
eeb611e8-e754-46de-a90d-67628e9b7cd6 Germany
69f44487-7f35-49eb-ba77-b2916e1db7b6 Spain
cee654eb-bbaa-4df2-85aa-087a580a70e1 Greece
9ad84e8d-53d8-4698-8be7-d47ccc9ffcb9 Bulgaria
ffbc558e-f7e6-4bad-a048-d99c6acd438d Germany
41333280-34d8-42eb-8861-8b54bc62fa74 Belgium
188b5e51-96a0-45c4-82df-6839792050df Portugal
83ad28e8-5fc3-4751-a118-cc4b28261fe0 Denmark
25f55f3e-8f32-48a9-ac05-8fd500e052f8 Germany
3b62af72-c664-40f1-8945-325c6aaa631f Sweden
fd6432d9-8cb8-46df-b974-42d93c1acf31 Poland
363cf6ca-f302-42dd-a5ed-47be4e9db020 Poland
3fb84022-cf83-4ff7-8570-ff78e849b002 Norway
a42fe505-8332-4882-89b3-219c9e139e96 Netherlands
36cbfde9-9e75-44a2-af0f-88d6f851e714 Estonia
7e11b1c7-8318-4ed4-8517-5cda17eea558 Hungary
8abf08c8-49cd-426d-b8e5-6a15ebaf7834 Hungary
43dcc3c8-5b02-4676-beb3-6370648b6ee9 Finland
d873af9a-ce14-4361-8c97-487a8f0528c6 France
a6183616-8302-4a0b-b713-27bd3e8044d5 Poland
6f622098-3e6e-4775-bb65-74cf164e08d7 Germany
d4123054-94eb-4095-9348-377b72fdd293 France
60a1ed29-63d4-4dc1-956f-77c310073b31 Germany
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
End Of Life Disassembling Instructions1SBC101080M6801
Environmental Product Declaration - EPD1SBD250584E3000
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 92.7 %
Certificates and Declarations
A2L Certificate – UL9AKK108469A4875
9AKK108469A4879
ABS CertificateABS_20-2060694-PDA
BV CertificateBV_2634H24898C1
CB CertificateCB_SE-113345
CCC CertificateCCC_2024010304656669
CQC CertificateCQC2010010304445624
CQC2020010304298240
Declaration of Conformity - CCC2020980304001253
2020980304001082
Declaration of Conformity - CE1SBD250000U1000
Declaration of Conformity - UKCA1SBD250031U1000
DNV CertificateDNV_TAE00001AF-4
GOST CertificateGOST_POCCFR.ME77.B07175.pdf
KC CertificateKC_HW02016-15005C
LR CertificateLRS_LR23403517TA-02
RINA CertificateRINA_ELE142224XG
RMRS CertificateRMRS_1802705280
UL CertificateUL-US-2150887-5
UL-CA-2142658-5
UL Listing CardE312527
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length79 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.27 kg
Package Level 1 EAN3471523110618
Package Level 2 Unitsbox 27 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height315 mm
Package Level 2 Gross Weight7.29 kg
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3705804
E-Number (Sweden)3211343

ETIM for 1SBL177001R1110 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 24 V
Rated control supply voltage AC 60 Hz (EF003979) 24 V
Rated control supply voltage DC (EF003980) 20 V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 30 A
Rated operation current Ie at AC-3, 400 V (EF001392) 18 A
Rated operation power at AC-3, 400 V (EF001364) 7.5 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 0
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Product Datasheet