View larger
Images are for illustrative purposes only. Please refer to data sheet for details
1SBL177001R1401 ABB AF16-30-01-14 250-500V50/60HZ-DC Contactor
1SBL177001R1401
177001
ABB
1 Pcs.
AF16-30-01-14 250-500V50/60HZ-DC Contactor
AF16-30-01 CONT.3P BOB 250-500Vac-dc
Automation > Power contactor, AC switching
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Utilized extensively in electrical distribution boards, the 1SBL177001R1401 ABB AF16-30-01-14 250-500V50/60HZ-DC Contactor offers robust switching performance for industrial automation and motor control circuits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC159647_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101027M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 77 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.31 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 1
- Number of Poles: 3P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159647_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.31 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 30 A |
| (690 V) 60 °C 30 A | |
| (690 V) 70 °C 26 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 18 A |
| (440 V) 60 °C 18 A | |
| (500 V) 60 °C 15 A | |
| (690 V) 60 °C 10.5 A | |
| (380 / 400 V) 60 °C 18 A | |
| (220 / 230 / 240 V) 60 °C 18 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 20 A |
| (110 V) 1-Pole, 60 °C 20 A | |
| (110 V) 1-Pole, 70 °C 20 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 20 A | |
| (220 V) 2 Poles in Series, 60 °C 20 A | |
| (220 V) 2 Poles in Series, 70 °C 20 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A |
| (110 V) 1-Pole, 60 °C 8 A | |
| (110 V) 1-Pole, 70 °C 8 A | |
| (110 V) 2 Poles in Series, 40 °C 30 A | |
| (110 V) 2 Poles in Series, 60 °C 30 A | |
| (110 V) 2 Poles in Series, 70 °C 26 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 8 A | |
| (220 V) 2 Poles in Series, 60 °C 8 A | |
| (220 V) 2 Poles in Series, 70 °C 8 A | |
| (220 V) 3 Poles in Series, 40 °C 30 A | |
| (220 V) 3 Poles in Series, 60 °C 30 A | |
| (220 V) 3 Poles in Series, 70 °C 26 A | |
| (72 V) 1-Pole, 40 °C 30 A | |
| (72 V) 1-Pole, 60 °C 30 A | |
| (72 V) 1-Pole, 70 °C 26 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 20 A | |
| (110 V) 2 Poles in Series, 60 °C 20 A | |
| (110 V) 2 Poles in Series, 70 °C 20 A | |
| (110 V) 3 Poles in Series, 40 °C 30 A | |
| (110 V) 3 Poles in Series, 60 °C 30 A | |
| (110 V) 3 Poles in Series, 70 °C 26 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 16 A | |
| (220 V) 3 Poles in Series, 60 °C 16 A | |
| (220 V) 3 Poles in Series, 70 °C 16 A | |
| (72 V) 1-Pole, 40 °C 16 A | |
| (72 V) 1-Pole, 60 °C 16 A | |
| (72 V) 1-Pole, 70 °C 16 A | |
| (72 V) 2 Poles in Series, 40 °C 30 A | |
| (72 V) 2 Poles in Series, 60 °C 30 A | |
| (72 V) 2 Poles in Series, 70 °C 26 A | |
| (72 V) 3 Poles in Series, 40 °C 30 A | |
| (72 V) 3 Poles in Series, 60 °C 30 A | |
| (72 V) 3 Poles in Series, 70 °C 26 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (400 V) 7.5 kW |
| (415 V) 9 kW | |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 9 kW |
| (440 V) 9 kW | |
| (500 V) 9 kW | |
| (690 V) 9 kW | |
| (380 / 400 V) 7.5 kW | |
| (220 / 230 / 240 V) 4 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 300 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 250 ... 500 V |
| 60 Hz 250 ... 500 V | |
| DC Operation 250 ... 500 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 1.2 W | |
| at Rated Operating Conditions AC-3 per Pole 0.35 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 4 mm² | |
| Rigid Stranded 1/2x 1 ... 6 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Control Circuit 10 mm | |
| Main Circuit 10 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 1.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 30 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1-1/2 hp |
| (200 ... 208 V AC) Three Phase 5 hp | |
| (220 ... 240 V AC) Three Phase 5 hp | |
| (240 V AC) Single Phase 3 hp | |
| (440 ... 480 V AC) Three Phase 10 hp | |
| (550 ... 600 V AC) Three Phase 15 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG |
| Rigid Stranded 1/2x 16-10 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 13 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 20 A |
| (200 ... 208 V AC) Three Phase 17.5 A | |
| (220 ... 240 V AC) Three Phase 15.2 A | |
| (240 V AC) Single Phase 17 A | |
| (440 ... 480 V AC) Three Phase 14 A | |
| (550 ... 600 V AC) Three Phase 17 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Open, Shock Direction: B1 5 g | |
| Shock Direction: A 30 g | |
| Shock Direction: B2 15 g | |
| Shock Direction: C1 25 g | |
| Shock Direction: C2 25 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 68025695-965d-4cea-a138-abd9f6a581bc China |
| Simplified SCIP | 1827ab1d-cedb-4bc3-aad7-08ae312a223a Sweden |
| a6a45b81-b007-45c3-add1-aef10ea6dda3 Poland | |
| f5627cca-12dd-4c54-9625-ace50cadbfc8 Portugal | |
| bc67e1ff-e5d7-4cc4-a341-6d47f9972902 Bulgaria | |
| 9180cdd8-fa69-4bf5-9164-a421dd834117 Estonia | |
| af61bbca-9ca7-4f4a-b7cf-6fc04e6c285e Hungary | |
| a9b60459-ebfc-44fc-b02d-4ee7a9855709 Greece | |
| 40a8758a-6ee5-4520-8f87-3bb1d21ebe68 Netherlands | |
| 615564e5-0c01-4dcf-8ea8-9bc45137de3f Croatia | |
| b34a1b3a-d4c5-4d92-a20c-491eec705154 Belgium | |
| 8856388c-fd55-4b9c-94b7-b47bb78b9b53 Germany | |
| 99b33f73-2bfa-4002-be96-dda2b5b9cc3e Denmark | |
| 201267cd-4137-413b-ad79-6ecaf16f3915 Germany | |
| d33bfff1-bd44-4652-96bb-cfb66b357635 Spain | |
| d9bec275-24e5-41e2-97d9-b3999cb298a4 Germany | |
| 828f7200-ea50-40d5-a8c9-6aefb0059697 Poland | |
| 7ae53756-c274-4f8b-8e3b-3b6df74197ca Poland | |
| eef14ce1-f242-4713-aa33-23a61b77b38a France | |
| 6298a348-73b9-4870-b018-6fe55e292010 Belgium | |
| 0f987e5c-83a7-4e2e-8bb4-84064f96e98b Hungary | |
| c250cded-e022-4e30-91db-09bdc931477d Germany | |
| 4b77b079-a4f9-4701-9042-e6bbe3a3b9f3 France | |
| 64052701-07ff-4637-b823-37f1b839dc02 Sweden | |
| ff2651bc-730e-46fd-9c77-0a353ab52d61 Germany | |
| eb01c1a3-603c-42d5-a88c-6ece909b6af5 Czech Republic | |
| 4c17bff8-76b6-421a-ba0e-c50ee7807c58 Norway | |
| acd82cc6-41ab-48fe-a76d-01e314c47995 Finland | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24898C1 |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| CQC2020010304298240 | |
| Declaration of Conformity - CCC | 2020980304001253 |
| 2020980304001082 | |
| Declaration of Conformity - CE | 1SBD250000U1000 |
| Declaration of Conformity - UKCA | 1SBD250031U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15005C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-2150887-5 |
| UL-CA-2142658-5 | |
| UL Listing Card | E312527 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.31 kg |
| Package Level 1 EAN | 3471523110748 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 8.37 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3706247 |
| E-Number (Sweden) | 3211375 |