Request QuoteProduct Overview
Abb 1SFL427002R1100 AF116-30-00B-11 contactor is a high-performance electromechanical switching unit designed to regulate major industrial motor systems and heavy electrical grids. Such contactors provide dependable remote operation and robust durability under intensive operating cycles.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 20 V
- Voltage type for actuating (EF008242): AC/DC
- Rated operation current Ie at AC-1, 400 V (EF001393): 160 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 116 A
- Rated operation power at AC-3, 400 V (EF001364): 55 kW
- Rated operation power NEMA (EF011960): 29.8280 kW
- Modular version (EF001126): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Number of normally open contacts as main contact (EF001374): 3
More info
▲A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Operated with wide control voltage range 24-60 V, 50 and 60 Hz, 20-60 V DC
Ordering
- EAN:
- 7320500476499
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85364900
Dimensions
- Product Net Width:
- 90.0mm
- Product Net Depth:
- 126.0mm
- Product Net Height:
- 150.0mm
- Product Net Weight:
- 1.512kg
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 194 mm
- Package Level 1 Length:
- 115 mm
- Package Level 1 Height:
- 169 mm
- Package Level 1 Gross Weight:
- 1.642 kg
- Package Level 1 EAN:
- 7320500476499
Technical
- Number of Main Contacts NO:
- 3
- Number of Main Contacts NC:
- 0
- Number of Auxiliary Contacts NO:
- 0
- Number of Auxiliary Contacts NC:
- 0
- Rated Operational Voltage:
- Main Circuit 690 V
- Rated Frequency (f):
- Main Circuit 50/60 Hz
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A
- Rated Operational Current AC-1 (Ie):
- (690 V) 55 °C 145 A
(690 V) 40 °C 160 A
(690 V) 70 °C 130 A
- Rated Operational Current AC-3 (Ie):
- (690 V) 55 °C 65 A
(220 / 230 / 240 V) 55 °C 116 A
(415 V) 55 °C 116 A
(440 V) 55 °C 116 A
(380 / 400 V) 55 °C 116 A
(500 V) 55 °C 110 A
- Rated Operational Power AC-3 (Pe):
- (500 V) 75 kW
(220 / 230 / 240 V) 30 kW
(690 V) 55 kW
(380 / 400 V) 55 kW
(440 V) 75 kW
(415 V) 55 kW
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
- 8 x Ie AC-3
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
- 10 x Ie AC-3
- Short-Circuit Protective Devices:
- gG Type Fuses 250 A
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
- Maximum Electrical Switching Frequency:
- AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
- Rated Operational Current DC-1 (Ie):
- (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
- Rated Operational Current DC-3 (Ie):
- (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
- Rated Operational Current DC-5 (Ie):
- (110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
- Rated Insulation Voltage (Ui):
- acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 8 kV
- Mechanical Durability:
- 5 million
- Maximum Mechanical Switching Frequency:
- 300 cycles per hour
- Coil Operating Limits:
- (acc. to IEC 60947-4-1)0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
- Rated Control Circuit Voltage (Uc):
- 60 Hz 24…60 V
50 Hz 24…60 V
DC Operation 20…60 V
- Coil Consumption:
- Pull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 210 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A
- Operate Time:
- Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
- Connecting Capacity-Main Circuit:
- Flexible 2x10…70 mm²
Rigid Cu-Cable 2x10…95 mm²
- Connecting Capacity-Auxiliary Circuit:
- Solid 2x1…4 mm²
Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 1x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 1x0.75…2.5 mm²
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type:
- Main Circuit: Bars
Environmental
- Ambient Air Temperature:
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C
- Maximum Operating Altitude Permissible:
- 3000 m
- RoHS Status:
- Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
- Maximum Operating Voltage UL/CSA:
- Main Circuit 600 V
- General Use Rating UL/CSA:
- (600 V AC) 160 A
- Horsepower Rating UL/CSA:
- (208 V AC) Three Phase 30 Hp
(440 ... 480 V AC) Three Phase 75 Hp
(550 ... 600 V AC) Three Phase 100 Hp
(220 ... 240 V AC) Three Phase 40 Hp
(200 V AC) Three Phase 30 Hp
Certificates and Declarations (Document Number)
- CB Certificate:
- SE-70479
- CCC Certificate:
- CQC_2013010304604055
- Declaration of Conformity - CE:
- 2CMT004242
- RINA Certificate:
- ELE060313XG/002
- RoHS Information:
- 1SFC101055D0202
Classifications
- ETIM 5:
- EC000066 - Magnet contactor, AC-switching
- UNSPSC:
- 39121529