View larger
1SBL137001R1310 ABB AF09-30-10-13 100-250V50/60HZ-DC Contactor
1SBL137001R1310
137001
ABB
1 Pcs.
Automation > Power contactor, AC switching
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Abb AF09-30-10-13 100-250V50/60HZ-DC Contactor is an electromechanical switching device utilized for repeatedly establishing and interrupting electrical power circuits in industrial machinery and motor control systems. These components provide reliable remote switching for heavy electrical loads within control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC159656_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101027M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 77 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.27 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 0
- Number of Poles: 3P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159656_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 25 A |
| (690 V) 60 °C 25 A | |
| (690 V) 70 °C 22 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 9 A |
| (440 V) 60 °C 9 A | |
| (500 V) 60 °C 9.5 A | |
| (690 V) 60 °C 7 A | |
| (380 / 400 V) 60 °C 9 A | |
| (220 / 230 / 240 V) 60 °C 9 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 9 A |
| (440 V) 60 °C 9 A | |
| (500 V) 60 °C 9.5 A | |
| (690 V) 60 °C 7 A | |
| (380 / 400 V) 60 °C 9 A | |
| (220 / 230 / 240 V) 60 °C 9 A | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 40 °C 10 A |
| (110 V) 1-Pole, 60 °C 10 A | |
| (110 V) 1-Pole, 70 °C 10 A | |
| (110 V) 2 Poles in Series, 40 °C 25 A | |
| (110 V) 2 Poles in Series, 60 °C 25 A | |
| (110 V) 2 Poles in Series, 70 °C 22 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 10 A | |
| (220 V) 2 Poles in Series, 60 °C 10 A | |
| (220 V) 2 Poles in Series, 70 °C 10 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 22 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 22 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 6 A |
| (110 V) 1-Pole, 60 °C 6 A | |
| (110 V) 1-Pole, 70 °C 6 A | |
| (110 V) 2 Poles in Series, 40 °C 25 A | |
| (110 V) 2 Poles in Series, 60 °C 25 A | |
| (110 V) 2 Poles in Series, 70 °C 22 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 6 A | |
| (220 V) 2 Poles in Series, 60 °C 6 A | |
| (220 V) 2 Poles in Series, 70 °C 6 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 22 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 22 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A |
| (110 V) 1-Pole, 60 °C 4 A | |
| (110 V) 1-Pole, 70 °C 4 A | |
| (110 V) 2 Poles in Series, 40 °C 10 A | |
| (110 V) 2 Poles in Series, 60 °C 10 A | |
| (110 V) 2 Poles in Series, 70 °C 10 A | |
| (110 V) 3 Poles in Series, 40 °C 25 A | |
| (110 V) 3 Poles in Series, 60 °C 25 A | |
| (110 V) 3 Poles in Series, 70 °C 22 A | |
| (220 V) 2 Poles in Series, 40 °C 4 A | |
| (220 V) 2 Poles in Series, 60 °C 4 A | |
| (220 V) 2 Poles in Series, 70 °C 4 A | |
| (220 V) 3 Poles in Series, 40 °C 9 A | |
| (220 V) 3 Poles in Series, 60 °C 9 A | |
| (220 V) 3 Poles in Series, 70 °C 9 A | |
| (72 V) 1-Pole, 40 °C 9 A | |
| (72 V) 1-Pole, 60 °C 9 A | |
| (72 V) 1-Pole, 70 °C 9 A | |
| (72 V) 2 Poles in Series, 40 °C 25 A | |
| (72 V) 2 Poles in Series, 60 °C 25 A | |
| (72 V) 2 Poles in Series, 70 °C 22 A | |
| (72 V) 3 Poles in Series, 40 °C 25 A | |
| (72 V) 3 Poles in Series, 60 °C 25 A | |
| (72 V) 3 Poles in Series, 70 °C 22 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Operational Power AC-3 (Pe) | (400 V) 4 kW |
| (415 V) 4 kW | |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 4 kW | |
| (220 / 230 / 240 V) 2.2 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 4 kW |
| (440 V) 4 kW | |
| (500 V) 5.5 kW | |
| (690 V) 5.5 kW | |
| (380 / 400 V) 4 kW | |
| (220 / 230 / 240 V) 2.2 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | |
| for 0.1 s 140 A | |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 1200 cycles per hour | |
| (AC-2 / AC-4) 300 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V |
| 60 Hz 100 ... 250 V | |
| DC Operation 100 ... 250 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| at Rated Operating Conditions AC-1 per Pole 0.8 W | |
| at Rated Operating Conditions AC-3 per Pole 0.1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 4 mm² | |
| Rigid Stranded 1/2x 1 ... 6 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Control Circuit 10 mm | |
| Main Circuit 10 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Main Circuit 1.5 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| NEMA Size | 00 |
| Continuous Current Rating NEMA | 9 A |
| Horsepower Rating NEMA | (115 V AC) Single Phase 1/3 Hp |
| (200 V AC) Three Phase 1-1/2 Hp | |
| (230 V AC) Single Phase 1 Hp | |
| (230 V AC) Three Phase 1-1/2 Hp | |
| (460 V AC) Three Phase 2 Hp | |
| (575 V AC) Three Phase 2 Hp | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 25 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3/4 hp |
| (200 ... 208 V AC) Three Phase 2 hp | |
| (220 ... 240 V AC) Three Phase 2 hp | |
| (240 V AC) Single Phase 1-1/2 hp | |
| (440 ... 480 V AC) Three Phase 5 hp | |
| (550 ... 600 V AC) Three Phase 7-1/2 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG |
| Rigid Stranded 1/2x 16-10 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Main Circuit 13 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 13.8 A |
| (200 ... 208 V AC) Three Phase 7.8 A | |
| (220 ... 240 V AC) Three Phase 6.8 A | |
| (240 V AC) Single Phase 10 A | |
| (440 ... 480 V AC) Three Phase 7.6 A | |
| (550 ... 600 V AC) Three Phase 9 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Open, Shock Direction: B1 5 g | |
| Shock Direction: A 30 g | |
| Shock Direction: B2 15 g | |
| Shock Direction: C1 25 g | |
| Shock Direction: C2 25 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 985c900c-1c52-441e-9ef8-189ad537734b China |
| Simplified SCIP | c0fe3a39-f91c-4e98-9560-ae259339e14b Belgium |
| 3ef78294-3403-47aa-9821-b709595ce32c Bulgaria | |
| 55393582-02e7-4351-90ec-d7f12e1c42b1 Estonia | |
| f5cad04b-2a5e-4fc7-9dd8-f168a618bd4d Finland | |
| 1714317d-48cd-4bfa-8178-7576c107755a Belgium | |
| def4f81c-b690-4481-95c3-f85fe209323f Portugal | |
| ac2d33e0-b054-4de1-903d-b12ae377a944 Spain | |
| 87cd9ee0-e9d2-4f9a-b1cd-6c38fc30d6cc Greece | |
| d180bc1c-8501-4867-8bee-8ea533c68bf1 Norway | |
| ce1df4b3-2ced-4709-b052-07d587a3f491 Hungary | |
| 87c7b1db-75f2-4a5d-abfc-b74f9d3c8f6b Hungary | |
| 9a35863b-2625-4170-bc84-0f7975eb33a7 Germany | |
| 837a0c89-60e8-47f5-8be2-1ea44f0dd374 Germany | |
| b74d9cda-c1aa-4e44-b534-e41cfb48f1ee Sweden | |
| 30dfc167-dbd5-4812-919a-8056c0c1f743 Germany | |
| 00910b0b-0300-439b-9723-2f2bbcb41e58 Denmark | |
| b6ecffbd-8a09-4fcc-92a5-09cf7dcf2c13 Netherlands | |
| 785aed0c-6c62-42bb-80c3-f5c47b3b2282 Poland | |
| b7c1e8c7-a3e4-4104-982f-8dffb0ef39a2 Poland | |
| 0ba340ef-9f44-421f-8cb8-8b855a0fcba5 Germany | |
| d9c2504e-33d8-43a3-806d-4e8f5005591e Poland | |
| 01dae348-827b-4a1f-8034-9a8afb315ff6 France | |
| a6d0aa88-03d7-470d-87f8-c450c45cf3bc Sweden | |
| b045c12b-2dfa-4a33-a8d6-07d8e1b17d58 Germany | |
| 94110c54-a437-4795-a9f8-a07ccb04d598 France | |
| 64f0f64c-3a77-4b18-9b44-7d3b1c0ca93b Czech Republic | |
| ec3df316-8078-4484-a2b3-dcf266e83097 Croatia | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| 2TFP200035A1001 | |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 86 % |
| Sustainable Material Content in Product (wt. %) | Recycled Metal - 28 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4875 |
| 9AKK108469A4879 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24898C0 |
| CB Certificate | CB_SE-113345 |
| CCC Certificate | CCC_2024010304656669 |
| CQC Certificate | CQC2010010304445624 |
| CQC2020010304298240 | |
| Declaration of Conformity - CCC | 2020980304001253 |
| 2020980304001082 | |
| Declaration of Conformity - CE | 1SBD250000U1000 |
| Declaration of Conformity - UKCA | 1SBD250031U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| GOST Certificate | GOST_POCCFR.ME77.B07175.pdf |
| KC Certificate | KC_HW02016-15004C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-2150887-5 |
| UL-CA-2142658-5 | |
| UL Listing Card | E312527 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.27 kg |
| Package Level 1 EAN | 3471523110038 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 7.29 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3706201 |
| E-Number (Sweden) | 3210009 |