View larger
2CTB812122R1001 ABB Prot. About t. OVRPVT1-T212.5-1000MCQS
2CTB812122R1001
2CTB812122R1001
ABB
1 Pcs.
Automation > Surge protection device for power supply systems
Other modular devices
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The 2CTB812122R1001 ABB Prot. About t. OVRPVT1-T212.5-1000MCQS manufactured by Abb functions as a critical safety component designed to absorb high-energy electrical impulses and transient surges. Units of this type are routinely installed within complex industrial electrical grids and energy systems to isolate valuable equipment from destructive line fluctuations.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Suitable For: To protect the systems against the transient overvoltage (lightning)
- Voltage Rating DC: 1000 V
- Maximum Power Point (MPP) Voltage: 1000 V
- Rated Service Short-Circuit Breaking Capacity (I cs ): 11 kA
- Discharge Current: Nominal (8 / 20 µs) 20 kA
- Arrester Class: I
- Number of Protected Poles: 2
- Number of Conductors: 2
- Transmission Standard: Optic
- Version: Plug-in
- Product Type: QS
- Options Provided: Solar
- Preventive Maintenance Feature: No
- Status Indicator: Yes
- Number of Batteries: 0
- Fuse Size: 3 modular spacing
More info
▲| Technical | |
|---|---|
| Suitable For | To protect the systems against the transient overvoltage (lightning) |
| Voltage Rating DC | 1000 V |
| Maximum Power Point (MPP) Voltage | 1000 V |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 11 kA |
| Discharge Current | Nominal (8 / 20 µs) 20 kA |
| I (max, 8 / 20 µs) 40 kA | |
| I (total, 10 / 350 µs) 12.5 kA | |
| Arrester Class | I |
| II | |
| Number of Protected Poles | 2 |
| Number of Conductors | 2 |
| Transmission Standard | Optic |
| Version | Plug-in |
| Product Type | QS |
| Options Provided | Solar |
| Preventive Maintenance Feature | No |
| Status Indicator | Yes |
| Number of Batteries | 0 |
| Fuse Size | 3 modular spacing |
| Cross-Section (Across) | Maximum Conductor Solid-Stranded 35 mm² |
| Maximum Conductor Flexible 25 mm² | |
| Electrical | |
| Rated Voltage (Ur) | 1000 V DC |
| Voltage Protection Level ( Up) | 3.8 kV |
| Material Compliance | |
| RoHS Declaration | 9AKK107991A6344 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20230707 |
| REACH Declaration | 9AKK107492A1906 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20231212 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Degree of Protection | IP20 |
| Dimensions | |
| Product Net Width | 24 mm |
| Product Net Height | 45 mm |
| Product Net Depth / Length | 74 mm |
| Product Net Weight | 0.071 kg |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.071 kg |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 9AKK107991A6344 |
| UL Certificate | 2CTC431021G1701 |
| Installation | |
| Instructions and Manuals | 2CTC431032M1701 |
| Mounting Type | DIN-Rail |
| Popular Downloads | |
| Mechanical Drawings | 2CTC812000F0300 |
| External Classifications and Standards | |
| ETIM 9 | EC000941 - Surge protection device for power supply systems |
| ETIM 10 | EC000941 - Surge protection device for power supply systems |
| UNSPSC | 39121610 |
| eClass | V11.0 : 27130805 |
| Object Classification Code | 141DCC |
| Standards | IEC 61 643-11 / EN 50539-11 / UL 1449 4th ed |