View larger
2CSR752140R1104 ABB I.com.DS202CR 2p C 10A 10kA 30mA
2CSR752140R1104
752140
ABB
1 Pcs.
Automation > Earth leakage circuit breaker
Tertiary / Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Abb 2CSR752140R1104 residual current circuit breaker with overcurrent protection is designed to shield electrical circuits from short circuits, overloads, and ground faults. These compact protection units are deployed in commercial and industrial distribution boards to prevent equipment failure and ensure operator safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108471A9845
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 76.95 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- Extended Product Lifetime: Product Durability
- Offered with Takeback Services: Take Back for Recycling
- End Of Life Disassembling Instructions: 9AKK108469A0544
- Environmental Product Declaration - EPD: 9AKK108467A5738
- Type of Residual Current: Type A
- Test Voltage (Ut): Minimum 150 V
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): 10 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): 6 kA
- Maximum Surge Current: 0.25 kA
- Power Supply Connection: Arbitrary
- Energy Limiting Class: 3
- Electrical Endurance: 10000 operations
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108471A9845 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.95 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| UL 2799 Zero Waste To Landfill Validation available | |
| Extended Product Lifetime | Product Durability |
| Offered with Takeback Services | Take Back for Recycling |
| End Of Life Disassembling Instructions | 9AKK108469A0544 |
| Environmental Product Declaration - EPD | 9AKK108467A5738 |
| Technical | |
| Type of Residual Current | Type A |
| Test Voltage (Ut) | Minimum 150 V |
| Maximum 254 V | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 10 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 6 kA |
| Maximum Surge Current | 0.25 kA |
| Power Supply Connection | Arbitrary |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 operations |
| Mechanical Endurance | 20000 operations |
| Number of Protected Poles | 2 |
| Number of Poles | 2P |
| Fault Indication | Blue Flag on Window |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Left | |
| Tightening Torque | 4 N·m |
| Accessory Type | Auxiliary contact |
| Signal contact / auxiliary contact | |
| Earthing Switch Type | Undelayed |
| Accessories Available | Yes |
| Number of Batteries | 0 |
| Connecting Capacity | Busbar 10…10 mm² |
| Flexible 1...25 mm² | |
| Rigid Solid 1…35 mm² | |
| Rated Cross-Section | 1 - Solid-Core 1 … 35 mm² |
| 4 - Multi-Wired 1 … 25 mm² | |
| Wire Stripping Length | 11 mm |
| Electrical | |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 230 V |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 10 A |
| Rated Residual Current | 30 mA |
| Rated Short-Circuit Capacity | 6 kA |
| Rated Frequency (f) | 50 Hz |
| Power Loss | Total 3.28 W |
| Overvoltage Category | III |
| Material Compliance | |
| RoHS Declaration | 9AKK108466A5162 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20220211 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20220525 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| SCIP | 16d43f0f-58e2-46e4-9af9-ecaae7a78c5e Poland |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Environmental | |
| Ambient Air Temperature | Operation -25 … 55 °C |
| Degree of Protection | IP20 |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycle |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Dimensions | |
| Width in Number of Modular Spacings | 2 |
| Product Net Width | 36 mm |
| Product Net Height | 86 mm |
| Product Net Depth / Length | 72 mm |
| Product Net Weight | 0.220 kg |
| Built-In Depth (t2) | 72 mm |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.245 kg |
| E-Number (Finland) | 3217322 |
| E-Number (Norway) | 1629922 |
| Certificates and Declarations | |
| ABS Certificate | 9AKK108467A7630 |
| Declaration of Conformity - CE | 9AKK108470A7536 |
| IMQ Certificate | 9AKK108467A6463 |
| NF Certificate | 9AKK108467A7736 |
| VDE Certificate | 9AKK108467A7823 |
| Installation | |
| Instructions and Manuals | 9AKK108466A5165 |
| Mounting Type | DIN-Rail |
| Mounting Position | Any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK108467A1864 |
| External Classifications and Standards | |
| ETIM 9 | EC000905 - Earth leakage circuit breaker |
| ETIM 10 | EC000905 - Earth leakage circuit breaker |
| UNSPSC | 39121601 |
| eClass | V11.0 : 27142207 |
| Object Classification Code | F |
| Standards | IEC/EN 61009-1 |
| IEC/EN 61009-2-1 | |