Product Overview

Protect sensitive power circuits against complex residual currents using the ABB 2CSF202568R3250 residual current device. Type B units are essential in installations containing variable frequency drives and photovoltaic systems where smooth DC fault currents might occur alongside AC leakage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • EcoSolutions Profile: 9AKK108469A3795
  • Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 77.05 %
  • ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
  • Sustainable Material Content in Packaging (wt. %): Recycled Cardboard - 29.08 %
  • Extended Product Lifetime: Product Durability
  • Offered with Takeback Services: Take Back for Recycling
  • End Of Life Disassembling Instructions: 9AKK108470A1744
  • Environmental Product Declaration - EPD: 9AKK108468A5757
  • Type of Residual Current: Type B
  • Test Voltage (Ut): 110 ... 253 V
  • Dielectric Test Voltage: 2500 kV
  • Impulse Current: I (max, 8 / 20 µs) 3000 A
  • Maximum Surge Current: 3 kA
  • Leakage Current Type: B
  • Electrical Endurance: 10000 cycle

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
EcoSolutions Profile9AKK108469A3795
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 77.05 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
UL 2799 Zero Waste To Landfill Validation available
Sustainable Material Content in Packaging (wt. %)Recycled Cardboard - 29.08 %
Recycled Cardboard - 61.23 %
Recycled Cardboard - 2.66 %
Recycled Paper - 0 %
Recycled Paper - 0 %
Extended Product LifetimeProduct Durability
Offered with Takeback ServicesTake Back for Recycling
End Of Life Disassembling Instructions9AKK108470A1744
Environmental Product Declaration - EPD9AKK108468A5757
Technical
Type of Residual CurrentType B
Test Voltage (Ut)110 ... 253 V
Dielectric Test Voltage2500 kV
Impulse CurrentI (max, 8 / 20 µs) 3000 A
Maximum Surge Current3 kA
Leakage Current TypeB
Electrical Endurance10000 cycle
Mechanical Endurance20000 cycle
Number of Poles2P
Number of Modular Spacings per DIN Rail2
Operating Characteristic10ms Delay (High Immunity)
Tightening Torque2.8 N·m
Delay Time (τ)10 ms
Accessory TypeAuxiliary contact
Signal contact/auxiliary contact
Shunt trip
Undervoltage release
Overvoltage release
Motor operating device
Auto reclosing unit
Actuator TypeToggle - Insulation group I - II, RAL 5015
Housing TypeInsulation group I - II, RAL 7035
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Options ProvidedNone
Accessories AvailableYes
Number of Batteries0
Cable Size25 mm²
Connecting CapacityBusbar 10 mm²
Flexible 1 ... 25 mm²
Stranded 1 ... 25 mm²
Rated Cross-Section1 - Solid-Core 1 ... 25 mm²
Wire Stripping Length12 mm
Terminal TypeScrew Terminals
Electrical
Rated Voltage (Ur)230 V
Rated Operational Voltage230 V AC
Rated Insulation Voltage (Ui)440 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Input Voltage TypeAC
Rated Current (In)25 A
Rated Residual Current300 mA
Rated Conditional Short-Circuit Current (Inc)(Typ gG/gLfuse, 500 V) 100 A
Selective MCB S750-E 63A or S750DR-E/K 100 A
Frequency (f)50/60 Hz
Rated Frequency (f)50 … 60 Hz
Power LossTotal 1.6 W
Overvoltage CategoryIII
Design
RAL NumberSimilar to RAL 7035
Number of Modules2
Material Compliance
RoHS Declaration9AKK106713A5610
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date20211115
REACH Declaration9AKK108467A9482
REACH InformationTrue - contains substances > 0.1 mass percentage
REACH Date20240429
Conflict Minerals Reporting Template (CMRT)9AKK108468A3363
SCIP10b8311e-47e3-4a9c-bc31-a2d09986d074 Italy
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Consumer
Environmental
Ambient Air TemperatureOperation -25...+70 °C
Storage -40…+70 °C
Degree of ProtectionTerminals IP20
Housing IP40
Pollution Degree2
Environmental Conditions28 cycle
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Dimensions
Width in Number of Modular Spacings2
Product Net Width35 mm
Product Net Height85 mm
Product Net Depth / Length69 mm
Product Net Weight220 g
Built-In Depth (t2)69 mm
Dimension Diagram9AKK106354A0758
Engineering
EPLAN Data9AAF619163_EPLAN
Ordering
Package Level 1 Unitsbox 1 piece
Package Level 1 Gross Weight0.236 kg
E-Number (Finland)3214060
E-Number (Norway)1672367
E-Number (Sweden)2160153
Replaced Product ID (OLD)2CSF202592R3250
Certificates and Declarations
Declaration of Conformity - CE9AKK106713A5610
Installation
Instructions and Manuals9AKK107992A0195
Mounting TypeDIN-Rail
Mounting PositionAny
Popular Downloads
Data Sheet, Technical Information9AKK107991A7569
External Classifications and Standards
ETIM 9EC000003 - Residual current circuit breaker (RCCB)
ETIM 10EC000003 - Residual current circuit breaker (RCCB)
UNSPSC39121601
eClassV11.0 : 27142201
IDEA Granular Category Code (IGCC)4875 >> Residual current circuit breaker (RCCB)
Object Classification CodeF
StandardsIEC/EN 61008-1, IEC/EN 61008-2-1, IEC/EN 62423

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.