S-ARC1MC40 Det. Arco + Int. Autom. S-ARC1 M C40 Arc fault detection device integrated with MCB

Automation > Miniature circuit breaker (MCB) with auxiliary device
Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An ABB S-ARC1MC40 Det. Arco + Int. Autom. is an electrical protection device designed to monitor distribution lines and trip upon registering potentially hazardous electrical arcs and overcurrents.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • EcoSolutions Profile: 9AKK108471A1002
  • Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 81.91 %
  • ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
  • Extended Product Lifetime: Product Durability
  • End Of Life Disassembling Instructions: 9AKK108469A4799
  • Environmental Product Declaration - EPD: 9AKK108468A8866
  • Dielectric Test Voltage: 2.5 kV
  • Rated Ultimate Short-Circuit Breaking Capacity (I cu ): 10 kA
  • Rated Service Short-Circuit Breaking Capacity (I cs ): 7.5 kA
  • Power Supply Connection: Arbitrary
  • Contact Position Indication: Red ON / Green OFF
  • Energy Limiting Class: 3
  • Electrical Endurance: 10000 cycle
  • Mechanical Endurance: 20000 cycle
  • Number of Protected Poles: 1

More info

ABB EcoSolutions
ABB EcoSolutionsYes
EcoSolutions Profile9AKK108471A1002
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 81.91 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
UL 2799 Zero Waste To Landfill Validation available
Extended Product LifetimeProduct Durability
End Of Life Disassembling Instructions9AKK108469A4799
Environmental Product Declaration - EPD9AKK108468A8866
Technical
Dielectric Test Voltage2.5 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu)10 kA
Rated Service Short-Circuit Breaking Capacity (Ics)7.5 kA
Power Supply ConnectionArbitrary
Contact Position IndicationRed ON / Green OFF
Energy Limiting Class3
Electrical Endurance10000 cycle
Mechanical Endurance20000 cycle
Number of Protected Poles1
Number of Poles1P+N
Number of Modular Spacings per DIN Rail2
Operating CharacteristicInstantaneous
Position of Neutral TerminalsRight
Tightening Torque2.8 N·m
Accessory TypeAuxiliary contact
Auxiliary/Signal contact
Shunt trip
Undervoltage release
Overvoltage release
Actuator TypeToggle - Insulation group II,Orange RAL 2004, sealable in ON-OFF-positions
Housing TypeInsulation group I, RAL 7035
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
IncludesFire protection switch
Accessories AvailableYes
Mounting Position of AccessoriesRight
Number of Batteries0
Connecting CapacityBusbar 10 mm²
Rigid 1…25 mm²
Flexible 1…16 mm²
Wire Stripping Length12 mm
Terminal TypeScrew Terminals
Electrical
Tripping CharacteristicC
Rated Operational Voltage230...240 V AC
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Input Voltage TypeAC
Rated Current (In)40 A
Rated Short-Circuit Capacity10 kA
Rated Frequency (f)50 Hz
Power Loss6.2 W
Overvoltage CategoryIII
Design
Number of Modules2
Material Compliance
RoHS Declaration9AKK107045A1564
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date20170621
REACH Declaration9AKK108467A9482
REACH InformationTrue - contains substances > 0.1 mass percentage
REACH Date20240429
Conflict Minerals Reporting Template (CMRT)9AKK108468A3363
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Consumer
Environmental
Ambient Air TemperatureOperation -25 ... 55 °C
Storage -40 ... 70 °C
Reference Ambient Air Temperature30 °C
Degree of ProtectionTerminals IP20
Housing IP40
Pollution Degree2
Environmental Conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations20 Cycles with Load 0.8 In: 5g or 0.2mm 5 … 150 Hz
Resistance to Shock acc. to IEC 60068-2-2730g 2 shocks 13 ms
Dimensions
Width in Number of Modular Spacings2
Product Net Width35 mm
Product Net Height85 mm
Product Net Depth / Length69 mm
Product Net Weight180 g
Built-In Depth (t2)69 mm
Dimension Diagram9AKK106930A8989
Ordering
Package Level 1 Unitsbox 1 piece
Package Level 1 Gross Weight0.200 kg
Certificates and Declarations
Declaration of Conformity - CE9AKK107045A1563
IMQ Certificate9AKK107045A4216
KC Certificate9AKK108466A5925
VDE Certificate9AKK107045A7202
Installation
Instructions and Manuals9AKK106930A8985
9AKK106930A8986
Mounting TypeDIN-Rail
Mounting PositionAny
Popular Downloads
Data Sheet, Technical Information2CDC420032D0201
Mechanical Drawings9AKK106930A8988
9AKK106930A8989
External Classifications and Standards
ETIM 9EC002694 - Miniature circuit breaker (MCB) with auxiliary device
ETIM 10EC002694 - Miniature circuit breaker (MCB) with auxiliary device
eClassV11.0 : 27141906
Object Classification CodeF
StandardsIEC/EN 62606
IEC/EN 60898-1

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.