ABB 2CSA255103R1204 2CSA255103R1204 ABB DS-ARC1C20A30 Det. Arco + Int. Comb. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

2CSA255103R1204 ABB DS-ARC1C20A30 Det. Arco + Int. Comb.

2CSA255103R1204

255103

ABB

1 Pcs.

DS-ARC1C20A30 Det. Arco + Int. Comb. DS-ARC1 C20 A30 Arc fault detection device integrated with RCBO

Automation > Earth leakage circuit breaker with auxiliary device
Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ABB EcoSolutions
Environmental Product Declaration - EPD9AKK108470A1707
Technical
Type of Residual CurrentType A
Test Voltage (Ut)170 … 264 V
Dielectric Test Voltage2.5 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu)7.5 kA
Rated Residual Breaking Capacity (IΔm)6 kA
Rated Service Short-Circuit Breaking Capacity (Ics)6 kA
Power Supply ConnectionArbitrary
Contact Position IndicationRed ON / Green OFF
Energy Limiting Class3
Electrical Endurance10000 cycle
Mechanical Endurance20000 cycle
Number of Protected Poles1
Number of Poles1P+N
Number of Modular Spacings per DIN Rail3
Fault IndicationBlue Flag on Toggle
Operating CharacteristicInstantaneous
Position of Neutral TerminalsRight
Tightening Torque2.8 N·m
Accessory TypeAuxiliary contact
Auxiliary/Signal contact
Shunt trip
Undervoltage release
Overvoltage release
Bottom fitting auxiliary contact
Actuator TypeToggle -Insulation group II, Orange RAL 2004, sealable in ON-OFF-positions
Housing TypeInsulation group I, RAL 7035
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Accessories AvailableYes
Mounting Position of AccessoriesRight
Number of Batteries0
Connecting CapacityBusbar 10 mm²
Rigid 1…25 mm²
Flexible 1…16 mm²
Wire Stripping Length12 mm
Terminal TypeScrew Terminals
Electrical
Tripping CharacteristicC
Rated Operational Voltage230...240 V AC
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Input Voltage TypeAC
Rated Current (In)20 A
Rated Residual Current30 mA
Rated Short-Circuit Capacity6 kA
Rated Frequency (f)50 … 60 Hz
Power Loss4.2 W
Overvoltage CategoryIII
Design
Number of Modules3
Material Compliance
RoHS Declaration9AKK107046A6530
RoHS InformationFollowing EU Directive 2011/65/EU
RoHS Date20180903
REACH Declaration9AKK108467A9482
REACH InformationTrue - contains substances > 0.1 mass percentage
REACH Date20240429
Conflict Minerals Reporting Template (CMRT)9AKK108468A3363
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Consumer
Environmental
Ambient Air TemperatureOperation -25 ... 55 °C
Storage -40 ... 70 °C
Reference Ambient Air Temperature30 °C
Degree of ProtectionTerminals IP20
Housing IP40
Pollution Degree2
Environmental Conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations20 Cycles with Load 0.8 In: 5g or 0.2mm 5 … 150 Hz
Resistance to Shock acc. to IEC 60068-2-2730g 2 shocks 13 ms
Dimensions
Width in Number of Modular Spacings3
Product Net Width52.5 mm
Product Net Height85 mm
Product Net Depth / Length69 mm
Product Net Weight240 g
Built-In Depth (t2)69 mm
Dimension Diagram9AKK107046A6174
Engineering
EPLAN Data9AAC190691_EPLAN
Ordering
Package Level 1 Unitsbox 1 piece
Package Level 1 Gross Weight0.270 kg
E-Number (Finland)3211096
E-Number (Norway)1683248
Certificates and Declarations
Declaration of Conformity - CE9AKK107046A6529
IMQ Certificate9AKK107046A6176
KC Certificate9AKK108466A5927
VDE Certificate9AKK107046A6538
Installation
Instructions and Manuals9AKK107046A6173
9AKK106930A8986
Mounting TypeDIN-Rail
Mounting PositionAny
Popular Downloads
Data Sheet, Technical Information9AKK107046A7200
Mechanical Drawings9AKK107046A6174
9AKK107046A6175
External Classifications and Standards
ETIM 9EC002695 - Earth leakage circuit breaker with auxiliary device
ETIM 10EC002695 - Earth leakage circuit breaker with auxiliary device
eClassV11.0 : 27142213
Object Classification CodeF
StandardsIEC/EN 62606
IEC/EN 61009-1
IEC/EN 61009-2-1