View larger
Images are for illustrative purposes only. Please refer to data sheet for details
2CCF019959R0001 ABB Int. aut. S803S-K4 3p 4A K 50kA
2CCF019959R0001
019959
ABB
1 Pcs.
Int. aut. S803S-K4 3p 4A K 50kA
S803S-K4 High Performance MCB
Automation > Miniature circuit breaker (MCB)
Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Abb 2CCF019959R0001 automatic circuit breaker safeguards electrical circuits by automatically interrupting fault currents to prevent equipment damage. Such components form an essential layer of safety in complex electrical infrastructures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108471A1082
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 86.29 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- End Of Life Disassembling Instructions: 9AKK108470A2575
- Environmental Product Declaration - EPD: 9AKK108470A1695
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (415 V AC) 50 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (415 V AC) 40 kA
- Contact Position Indication: ON / OFF / TRIP
- Energy Limiting Class: 3
- Number of Protected Poles: 3
- Number of Poles: 3P
- Tightening Torque: 3.5 N·m
- Actuator Marking: I / O
- Recommended Screw Driver: Pozidriv 2
- Accessories Available: Yes
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108471A1082 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 86.29 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 9AKK108470A2575 |
| Environmental Product Declaration - EPD | 9AKK108470A1695 |
| 9AKK108470A1696 | |
| Technical | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (415 V AC) 50 kA |
| (440 V AC) 30 kA | |
| (500 V AC) 15 kA | |
| (690 V AC) 6 kA | |
| (375 V DC) 30 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (415 V AC) 40 kA |
| (440 V AC) 22.5 kA | |
| (500 V AC) 11 kA | |
| (690 V AC) 4 kA | |
| (375 V DC) 30 kA | |
| Contact Position Indication | ON / OFF / TRIP |
| Energy Limiting Class | 3 |
| Number of Protected Poles | 3 |
| Number of Poles | 3P |
| Tightening Torque | 3.5 N·m |
| Actuator Marking | I / O |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Remarks | Connection from top and bottom Connecting with CU only IP40 in enclosure with cover Cage terminal with captive screw |
| Connecting Capacity | Flexible 0 … 50 mm² |
| Rigid 0 … 70 mm² | |
| Terminal Type | Screw Terminals |
| Electrical | |
| Tripping Characteristic | K |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V AC |
| acc. to IEC 60947-2 690 V AC | |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 4 A |
| Rated Short-Circuit Capacity | (400 V AC) 25 kA |
| Rated Frequency (f) | 50/60 Hz |
| Power Loss | 6 W |
| at Rated Operating Conditions per Pole 2 W | |
| Overvoltage Category | IV |
| Design | |
| Housing Material | Insulation group I, RAL 7035 |
| Technical UL/CSA | |
| Interrupting Rating acc. to UL1077 | (240 V AC) 30 kA |
| (480Y / 277 V AC) 14 kA | |
| (600Y / 347 V AC) 6 kA | |
| Material Compliance | |
| RoHS Declaration | 2CCC005083D0202 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20211214 |
| REACH Declaration | 9AKK108470A9089 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20250313 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +60 °C |
| Storage -40 ... +70 °C | |
| Degree of Protection | IP20 |
| Pollution Degree | 3 |
| Resistance to Vibrations | 1 mm 7 - 13.2 Hz |
| 0.7g with Load 100% x Ie 13.2 - 100 Hz | |
| Environmental Information | 2CCY413207D0203 |
| Dimensions | |
| Width in Number of Modular Spacings | 4.5 |
| Product Net Width | 81 mm |
| Product Net Height | 95 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 0.735 kg |
| Built-In Depth (t2) | 82.5 mm |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 775 g |
| E-Number (Norway) | 1628526 |
| Certificates and Declarations | |
| CB Certificate | 9AKK107680A0857 |
| CCC Certificate | 9AKK108469A3021 |
| Declaration of Conformity - CE | 2CCC005083D0202 |
| DNV GL Certificate | 2CCC413018D0201 |
| ESTI Certificate | 2CCC413020D0101 |
| KC Certificate | 9AKK107680A0932 |
| LR Certificate | 2CCC413017D0201 |
| UL Certificate | 9AKK107680A2286 |
| VDE Certificate | 2CCC413039D0601 |
| Installation | |
| Instructions and Manuals | 2CCC413016M0008 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position | Any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK108468A9560 |
| 9AKK108468A9561 | |
| 9AKK108468A9562 | |
| External Classifications and Standards | |
| ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
| eClass | V11.0 : 27141901 |
| Object Classification Code | F |
| Standards | IEC/EN 60947-2 |
| IEC/EN 60898-1 | |
| UL 1077 | |