Abb 1SFA896212R7000 PSRC60-600-70 soft compressor arrangement is designed to manage compressor motor acceleration cycles and limit mechanical shock in fluid or gas processing systems. This specialized controller integrates into heavy-duty electrical control panels to ensure smooth operational transitions.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85371091
- Data Sheet, Technical Information: 1SFC132012C0201
- Instructions and Manuals: 1SFC132044M0001
- Instructions and Manuals (Part 3): 1SFC132060M0201
- CAD Dimensional Drawing: 2CDC001079B0201
- EPLAN Data: 9AAC172775_EPLAN
- Wiring Diagram: N/A
- Product Net Width: 180 mm
- Product Net Height: 220 mm
- Product Net Depth / Length: 70 mm
- Product Net Weight: 2.1 kg
- Rated Operational Voltage: 208 ... 600 V AC
- Rated Control Supply Voltage (U s ): 100 ... 240 V AC
- Rated Control Circuit Voltage (U c ): 24 V DC
- Rated Frequency (f): 50/60 Hz
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85371091 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SFC132012C0201 |
| Instructions and Manuals | 1SFC132044M0001 |
| Instructions and Manuals (Part 3) | 1SFC132060M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| EPLAN Data | 9AAC172775_EPLAN |
| Wiring Diagram | N/A |
| Dimensions | |
| Product Net Width | 180 mm |
| Product Net Height | 220 mm |
| Product Net Depth / Length | 70 mm |
| Product Net Weight | 2.1 kg |
| Technical | |
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us) | 100 ... 240 V AC |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz |
| Main Circuit 50 / 60 Hz | |
| Rated Operational Power - In-Line Connection (Pe) | (230 V) 15 kW |
| (400 V) 30 kW | |
| (500 V) 37 kW | |
| Rated Operational Current - In-Line Connection (Ie) | 60 A |
| Service Factor Percentage | 100 % |
| Overload Protection | Recommended MS495 45 ... 63 |
| Integrated Electronic Overload | No |
| Starting Capacity at Maximum Rated Current Ie | 4xIe for 6s |
| Ramp Time | Fixed setting |
| Fixed setting | |
| Initial Voltage During Start | Fixed setting |
| Step Down Voltage Special Ramp | Fixed setting |
| Current Limit Function | No |
| Switch for Inside Delta Connection | No |
| Run Signal Relay | Yes |
| By-pass Signal Relay | Yes |
| Fault Signal Relay | No |
| Overload Signal Relay | No |
| Signal Indication Completed Start Ramp (LED) | Green |
| Signal Indication Ready to Start/Standby ON (LED) | Green |
| Signal Indication Running R (LED) | Green |
| Signal Indication Ramping Up/Down (LED) | Green |
| Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time | 10 |
| Communication | FiledBusPlug(Optional) |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Terminal Type | Main Circuit: Bars |
| Connecting Capacity Main Circuit | Rigid 2 x 0.75 ... 1.5 mm² |
| Connecting Capacity Supply Circuit | Rigid 2 x 0.75 ... 1.5 |
| Tightening Torque | Control Circuit 0.6 N·m |
| Main Circuit 8 N·m | |
| Supply Circuit 0.6 N·m | |
| Product Main Type | PSRC60 |
| Function | Soft start with voltage ramp |
| Soft stop with voltage ramp | |
| Technical UL/CSA | |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 20 Hp |
| (220 ... 240 V AC) Three Phase 20 Hp | |
| (440 ... 480 V AC) Three Phase 40 Hp | |
| (550 ... 600 V AC) Three Phase 50 Hp | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Tightening Torque UL/CSA | Control Circuit 5.3 in·lb |
| Main Circuit 70.8 | |
| Supply Circuit 5.3 in·lb | |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +60 °C |
| Storage -40 ... +70 °C | |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2022-006481 |
| RoHS Declaration | 2CMT2022-006500 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006524 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Certificates and Declarations | |
| CQC Certificate | CQC2008010304295498 |
| Declaration of Conformity - CCC | 2020980304001090 |
| Declaration of Conformity - CE | 2CMT003878 |
| Container Information | |
| Package Level 1 Width | 195 mm |
| Package Level 1 Depth / Length | 86 mm |
| Package Level 1 Height | 230 mm |
| Package Level 1 Gross Weight | 2.3 kg |
| Package Level 1 EAN | 7320500465561 |
| Package Level 1 Units | box 1 piece |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000640 - Soft starter |
| ETIM 8 | EC000640 - Soft starter |
| ETIM 9 | EC000640 - Soft starter |
| eClass | V11.0 : 27370907 |
| UNSPSC | 39121521 |
| IDEA Granular Category Code (IGCC) | 4740 >> Soft starter |