Product Overview

Heavy electrical transmission grids and large industrial facilities utilize the Abb 1SDA104605R1 ABB E6.2H/E9 5000 Ekip Dip LSI 3p FHR as a main air circuit breaker. This protective device ensures the reliable interruption of massive fault currents while offering precise electronic trip characteristics for system coordination. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
  • End Of Life Disassembling Instructions: 9AKK108468A2364
  • Environmental Product Declaration - EPD: 9AKK108471A0821
  • REACH Declaration: 9AKK108466A1425
  • RoHS Declaration: 9AKK108466A1424
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • Toxic Substances Control Act - TSCA: 9AKK108467A8326
  • SCIP: 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy
  • Environmental Information: 9AKK108467A6707
  • Order Code US and Canada: 96HXESBB000A000000XX
  • EAN: 8015644066857
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362090
  • Product Net Width: 762 mm

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2364
Environmental Product Declaration - EPD9AKK108471A0821
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIP5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy
Environmental
Environmental Information9AKK108467A6707
Ordering
Order Code US and Canada96HXESBB000A000000XX
EAN8015644066857
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width762 mm
Product Net Height371 mm
Product Net Depth / Length270 mm
Product Net Weight109 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width515 mm
Package Level 1 Height610 mm
Package Level 1 Depth / Length1000 mm
Package Level 1 Gross Weight129 kg
Package Level 1 EAN8015644066857
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionF
Technical
Current TypeAC
Electrical DurabilityUe = 900 V 1000 cycle
10 cycles per hour
Mechanical Durability12000 cycle
60 cycles per hour
Number of Poles3P
Power Loss483 W
Rated Current (In)5000 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage900 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(800 V AC) 90 kA
(900 V AC) 75 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 75 kA
for 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(800 V AC) 90 kA
(900 V AC) 75 kA
Rated Uninterrupted Current (Iu)5000 A
Rated Voltage (Ur)900 V
ReleaseEkip Dip LSI
Release TypeEL
RemarksE9
Short-Circuit Performance LevelH
StandardsIEC
Sub-typeE6.2
Suitable for IT NetworksNo
Terminal Connection TypeRear flat Horizontal
Certificates and Declarations
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK107680A4890
Instructions and Manuals1SDH001000R0002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
WEEE Category4. Large Equipment (Any External Dimension More Than 50 cm)
eClassV11.1 : 27370409