ABB 1SDA104552R1 1SDA104552R1 ABB E6.2X/E9 6300 Ekip Dip LSI 4p WMP View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA104552R1 ABB E6.2X/E9 6300 Ekip Dip LSI 4p WMP

1SDA104552R1

104552

ABB

1 Pcs.

E6.2X/E9 6300 Ekip Dip LSI 4p WMP

Automation > Power circuit-breaker for trafo/generator/installation protection
Rack "Megamax-Emax"

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An ABB 1SDA104552R1 E6.2X/E9 withdrawable air circuit breaker provides maximum level protection and system isolation for massive industrial power facilities. High-capacity withdrawable breakers allow for safe maintenance intervals and reliable clearing of severe electrical faults.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
  • End Of Life Disassembling Instructions: 9AKK108468A2364
  • Environmental Product Declaration - EPD: 9AKK108471A0821
  • REACH Declaration: 9AKK108466A1425
  • RoHS Declaration: 9AKK108466A1424
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • Toxic Substances Control Act - TSCA: 9AKK108467A8326
  • Environmental Information: 9AKK108467A6707
  • EAN: 8015644066321
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362090
  • Product Net Width: 929 mm
  • Product Net Height: 425 mm
  • Product Net Depth / Length: 383 mm

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2364
Environmental Product Declaration - EPD9AKK108471A0821
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental
Environmental Information9AKK108467A6707
Ordering
EAN8015644066321
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width929 mm
Product Net Height425 mm
Product Net Depth / Length383 mm
Product Net Weight134 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width515 mm
Package Level 1 Height610 mm
Package Level 1 Depth / Length1000 mm
Package Level 1 Gross Weight138 kg
Package Level 1 EAN8015644066321
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionW
Technical
Current TypeAC
Electrical DurabilityUe = 900 V 1000 cycle
10 cycles per hour
Mechanical Durability12000 cycle
60 cycles per hour
Number of Poles4P
Power Loss1550 W
Rated Current (In)6300 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage900 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(800 V AC) 100 kA
(900 V AC) 90 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 90 kA
for 3 s 90 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(800 V AC) 100 kA
(900 V AC) 90 kA
Rated Uninterrupted Current (Iu)6300 A
Rated Voltage (Ur)900 V
ReleaseEkip Dip LSI
Release TypeEL
RemarksE9
Short-Circuit Performance LevelX
StandardsIEC
Sub-typeE6.2
Suitable for IT NetworksNo
Terminal Connection TypeRear flat Horizontal
Certificates and Declarations
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK107680A4890
Instructions and Manuals1SDH001000R0002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
WEEE Category4. Large Equipment (Any External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.