ABB 1SDA104500R1 1SDA104500R1 ABB E4.2S/E9 3200 Ekip Hi-Touch LSIG 3p WMP View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA104500R1 ABB E4.2S/E9 3200 Ekip Hi-Touch LSIG 3p WMP

1SDA104500R1

104500

ABB

1 Pcs.

E4.2S/E9 3200 Ekip Hi-Touch LSIG 3p WMP E4.2S/E9 3200 EkipHi-Tch LSIG 3pWMP 900V

Automation > Power circuit-breaker for trafo/generator/installation protection
Rack "Megamax-Emax"

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Operating as a critical safety component, the ABB 1SDA104500R1 air circuit breaker protects large electrical installations from overcurrents and short-circuit faults. Such equipment ensures continuous facility operations through dependable fault clearance.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
  • End Of Life Disassembling Instructions: 9AKK108468A2363
  • Environmental Product Declaration - EPD: 9AKK108471A0821
  • Extended Product Lifetime: Lifetime Extension Services are Offered
  • REACH Declaration: 9AKK108466A1425
  • RoHS Declaration: 9AKK108466A1424
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • Toxic Substances Control Act - TSCA: 9AKK108467A8326
  • Environmental Information: 9AKK108467A6707
  • Order Code US and Canada: 94SVENAK200A000000XX
  • EAN: 8056221026512
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362090
  • Product Net Width: 425 mm

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2363
Environmental Product Declaration - EPD9AKK108471A0821
Extended Product LifetimeLifetime Extension Services are Offered
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental
Environmental Information9AKK108467A6707
Ordering
Order Code US and Canada94SVENAK200A000000XX
EAN8056221026512
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width425 mm
Product Net Height425 mm
Product Net Depth / Length383 mm
Product Net Weight60 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width515 mm
Package Level 1 Height610 mm
Package Level 1 Depth / Length615 mm
Package Level 1 Gross Weight67 kg
Package Level 1 EAN8056221026512
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionW
Technical
Current TypeAC
Electrical DurabilityUe = 900 V 1000 cycle
10 cycles per hour
Mechanical Durability20000 cycle
60 cycles per hour
Number of Poles3P
Power Loss743 W
Rated Current (In)3200 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage900 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(800 V AC) 65 kA
(900 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 65 kA
for 3 s 65 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(800 V AC) 65 kA
(900 V AC) 65 kA
Rated Uninterrupted Current (Iu)3200 A
Rated Voltage (Ur)900 V
ReleaseEkip Hi-Touch LSIG
Release TypeEL
RemarksE9
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeE4.2
Suitable for IT NetworksNo
Terminal Connection TypeRear flat Horizontal
Certificates and Declarations
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK107680A4889
Instructions and Manuals1SDH001000R0002
Instructions and Manuals (Part 2)1SDH001316R1002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet