View larger
1SDA104494R1 ABB E2.2H/E9 2500 Ekip Touch LSIG 4p WMP
1SDA104494R1
104494
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Rack "Megamax-Emax"
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A withdrawable air circuit breaker designed for high-voltage applications provides essential circuit protection and isolation in demanding industrial environments. This ABB E2.2H/E9 unit ensures dependable performance and fault clearing capabilities for specialized power networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 2500 A
- Rated voltage (EF003977): 900 V
- Overload release current setting (EF002336): 1000.0 A
- Adjustment range undelayed short-circuit release (EF007131): 3750.0 A
- Integrated earth fault protection (EF007296): Yes
- Type of electrical connection of main circuit (EF006819): Connection at separate chassis part
- Device construction (EF008240): Built-in device slide-in technique (withdrawable)
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): No
- With switched-off indicator (EF007006): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 4
- Position of connection for main current circuit (EF006671): Connection at separate chassis part
- Type of control element (EF006976): Push button
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲- Extended Product Type:
- E2.2H/E9 2500 Ekip Touch LSIG 4p WMP
- Product ID:
- 1SDA104494R1
- EAN:
- 8056221026475
- Catalog Description:
- E2.2H/E9 2500 Ekip Touch LSIG 4p WMP
- Long Description:
- MOVING PART FOR C.BREAKER SACE EMAX2 E2.2H 2500 FOUR-POLE WITH SOLID-STATE RELEASE IN AC EKIP/TOUCH-LSIG R 2500 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED 900V
Ordering
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85362090
Popular Downloads
- Data Sheet, Technical Information:
- 1SDC200023D0209
- Instructions and Manuals:
- 1SDH001000R0002
Dimensions
- Product Net Width:
- 407mm
- Product Net Height:
- 425mm
- Product Net Depth / Length:
- 383mm
- Product Net Weight:
- 55kg
Technical
- Rated Impulse Withstand Voltage (Uimp):
- acc. to IEC 60947-2 12 kV
- Rated Insulation Voltage (Ui):
- AC 1000 V
- Rated Operational Voltage:
- 900 V AC
- Rated Short-Circuit Making Capacity (Icm):
- (800 V AC) 143 kA
(900 V AC) 143 kA
- Rated Short-time Withstand Current (Icw):
- for 1 s 65 kA
for 3 s 65 kA
- Power Loss:
- 550 W
- Standards:
- IEC
- Number of Poles:
- 4
- Mechanical Durability:
- 25000 cycle
60 cycles per hour
Environmental
- Environmental Information:
- ROHS, REACH
Certificates and Declarations (Document Number)
- Declaration of Conformity - CE:
- 1SDL000165R0020
- Environmental Information:
- ROHS, REACH
- Instructions and Manuals:
- 1SDH001000R0002
- Instructions and Manuals (Part 2):
- 1SDH001316R0002
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 515 mm
- Package Level 1 Depth / Length:
- 515 mm
- Package Level 1 Height:
- 610 mm
- Package Level 1 Gross Weight:
- 64 kg
- Package Level 1 EAN:
- 8015644065744
Classifications
- Object Classification Code:
- Q
- ETIM 6:
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
- ETIM 7:
- EC000228 - Power circuit-breaker for trafo/generator/installation protection
- WEEE Category:
- 5. Small Equipment (No External Dimension More Than 50 cm)