View larger
1SDA104424R1 ABB E6.2X/E9 6300 Ekip Touch LSIG 3p FHR
1SDA104424R1
104424
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Rack "Megamax-Emax"
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An air circuit breaker provides massive fault-clearing capabilities and precise electronic trip unit coordination for primary industrial substations and heavy power distribution systems. This high-capacity ABB E6.2X/E9 6300 Ekip Touch LSIG 3p FHR model safely handles extreme current loads. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 9AKK108468A2364
- Environmental Product Declaration - EPD: 9AKK108471A0821
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK108467A6707
- EAN: 8015644065041
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 762 mm
- Product Net Height: 371 mm
- Product Net Depth / Length: 270 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108471A0821 |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| EAN | 8015644065041 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 762 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 109 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1000 mm |
| Package Level 1 Gross Weight | 129 kg |
| Package Level 1 EAN | 8015644065041 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Technical | |
| Current Type | AC |
| Electrical Durability | Ue = 900 V 1000 cycle |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 767 W |
| Rated Current (In) | 6300 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 900 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (800 V AC) 100 kA |
| (900 V AC) 90 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 90 kA |
| for 3 s 90 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (800 V AC) 100 kA |
| (900 V AC) 90 kA | |
| Rated Uninterrupted Current (Iu) | 6300 A |
| Rated Voltage (Ur) | 900 V |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Remarks | E9 |
| Short-Circuit Performance Level | X |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | No |
| Terminal Connection Type | Rear flat Horizontal |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK107680A4890 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |