View larger
1SDA102081R1 ABB XT2H 125 Ekip Dip LSIG In25 3p FF UL/CSA
1SDA102081R1
1SDA102081R1
ABB
1 Pcs.
Automation > Shunt release (for power circuit breaker)
Molded Case Circuit Breakers ≤ 250 A Xtmax
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for precise circuit protection, the 1SDA102081R1 ABB XT2H 125 Ekip Dip LSIG In25 3p FF UL/CSA houses sophisticated electronic release capabilities inside a compact molded case breaker frame. Facilities implement these units to monitor complex electrical loads and interrupt fault currents effectively.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Environmental Product Declaration - EPD: 9AKK108468A1897
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 55.70 %
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- EAN: 8056221021241
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 90 mm
- Product Net Height: 130 mm
- Product Net Depth / Length: 82.5 mm
- Product Net Weight: 1.2 kg
- Package Level 1 Units: box 1 piece
- Package Level 1 Width: 130 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| Environmental Product Declaration - EPD | 9AKK108468A1897 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 55.70 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Ordering | |
| EAN | 8056221021241 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 90 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.2 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 130 mm |
| Package Level 1 Height | 208 mm |
| Package Level 1 Depth / Length | 145 mm |
| Package Level 1 Gross Weight | 1.22 kg |
| Package Level 1 EAN | 8056221021241 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 |
| Technical | |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3P |
| Opening Time | CB with SOR 30 ms |
| CB with UVR 30 ms | |
| Power Loss | at Rated Operating Conditions per Pole 0.80 W |
| Rated Current (In) | 25 A |
| Rated Frequency (f) | 50/60 Hz |
| Rated Insulation Voltage (Ui) | 1000 V AC |
| Rated Operational Voltage | 690 V AC |
| Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V AC |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | UL |
| Sub-type | XT2 |
| Technical UL/CSA | |
| Interrupting Rating acc. to UL489 | (240 V AC) 150 A |
| (480 V AC) 65 A | |
| (600 V AC) 25 A | |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210200D0206 |
| 1SDC210199D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5901 |
| UL Certificate | 1SDL000163R0112 |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000721R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000721R0003 |
| 1SDH000721R0510 | |
| External Classifications and Standards | |
| ETIM 9 | EC001023 - Shunt release (for power circuit breaker) |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |