View larger
1SDA101369R1
101369
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2358 |
| Environmental Product Declaration - EPD | 9AKK108468A1896 |
| 9AKK108468A4411 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 64.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 92e1bab8-1c39-45e9-86ee-330b2aac4e46 Italy |
| Simplified SCIP | f046e85e-2d56-43e3-b760-e075b56f92de Croatia |
| 1424f431-86b5-4bd0-b30a-3cd7178cd372 Germany | |
| 74838bf1-93ac-488c-8adb-af6ef3a4cacf Germany | |
| 8ab75caf-b9c2-48b4-a86d-ebc90908b011 Sweden | |
| 2279bd89-2817-4d83-9b36-f50ca1eb510a Germany | |
| 08de3454-af14-4806-b9bf-d12a2fea445b Czech Republic | |
| b5d18a99-a11a-4d2e-a554-5251508c54ce Estonia | |
| bb68e384-caef-42b9-919f-824bdd8dbecd France | |
| 14cdd8aa-6dba-48e1-bf43-98d679ef0727 Belgium | |
| 6300be00-4fe5-4421-9e1e-39cd8636a223 Spain | |
| 4d123613-9398-4882-880a-f561cca847a7 Portugal | |
| b734d87f-26af-44d3-8895-68ceada6a693 Germany | |
| 4cc36020-e9c8-4069-8c7c-3cdf0ae950ce Germany | |
| 8c114f2c-4a0d-4531-93f1-fd4443e353c3 Greece | |
| d483a882-3d1f-4fd5-9464-88f7555789cd Hungary | |
| 60986015-c01f-4824-87d5-16dc5f520076 France | |
| 1ba52820-1de7-4b12-acb3-6e36fd9fcb18 Poland | |
| 2af57c72-c17c-4cce-a9c4-96c341051b09 Finland | |
| baa50b6d-f2a8-48da-b3fc-44e66b8589a9 Belgium | |
| eae1c82e-32d9-4c33-980d-1051e3bc868e Hungary | |
| f04210c9-a017-4769-ba65-8497292054b7 Denmark | |
| 780f9f1d-550f-4823-ac2d-709753e1ef20 Sweden | |
| 5de8471f-c2df-4a1f-a00c-d0a319a1da71 Netherlands | |
| cd17c839-6210-49ce-933c-5bd53620c534 Norway | |
| e349168a-f36e-4575-8b23-8302bfd981f0 Poland | |
| 29160396-f5a7-4d46-a8e8-74f5d58f45ae Poland | |
| 008ca02e-a7bd-4230-97fc-2c8c08e4be6c Bulgaria | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... 125 °C |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XSELAFAZZAAAA00000 |
| E-Number (Norway) | 4380714 |
| EAN | 8056221011877 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 178 mm |
| Product Net Weight | 14.481 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 15.243 kg |
| Package Level 1 EAN | 8056221011877 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1337 |
| Technical | |
| Current Type | AC |
| Electrical Durability | 3000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 94 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Release | Ekip Dip LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT7M |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107046A9648 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002013A1102 |
| Wiring Diagram | 1SDM000002A1001 |
| Instructions and Manuals | 1SDH002013A1001 |
| 1SDH002013A1002 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1600 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1600 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |