View larger
1SDA100929R1
100929
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2357 |
| Environmental Product Declaration - EPD | 9AKK108468A1895 |
| 9AKK108468A4404 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 64.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 30a0320b-37c7-42cd-b319-91e67b6f6767 China |
| Simplified SCIP | 925bb387-78d5-46c7-bf92-755d596d0775 Poland |
| 28745365-53ad-473c-9a46-7f815b3255b4 Czech Republic | |
| 8c9e228e-d5c0-4e61-9b46-ed8eb1fa5952 Denmark | |
| 44e286d7-f195-4d9a-ab33-eb8b59b87e48 Hungary | |
| 6628552a-48b1-4c9c-b943-6298eb9a96d9 Croatia | |
| 2735212d-6791-4fd6-8b41-cf9f9723eb0e Greece | |
| 17afd852-36a2-451a-be59-6d51e3a394b0 Netherlands | |
| 3d28f7b5-401d-4fc1-8da8-640e25c41c34 Poland | |
| 43b212b5-ba56-473b-8b63-5a0d7b9e0887 Estonia | |
| a5a76f3a-380d-4169-a419-7bab6fb79674 Germany | |
| a5b84428-a533-4b70-9671-da1b60369e10 Norway | |
| 11b2f783-61cb-4aa9-8a78-72eadf6a1d41 Germany | |
| e5288163-6333-403d-a96c-9b6c8e49dfa6 Germany | |
| f50bf30e-f920-4aa4-8be0-334a83c03ab1 Finland | |
| ce2313cb-d803-4dd8-83b1-9d45db8d3b08 Sweden | |
| ebdb46f9-abc2-4af1-afc0-3f21af80d218 Portugal | |
| 6b4324bf-1cee-4ad4-954a-45e54cd53f42 Germany | |
| 4004a671-350b-4b07-9b39-74a7947e36a9 Bulgaria | |
| 8f8c7d40-b389-4826-b65d-4ffe9731a718 Hungary | |
| 2b2de302-a4b7-42ea-9cf4-afb037f08eff Poland | |
| a9fee520-b039-4802-b7af-82b2a36d7aa8 Sweden | |
| 4b9a703e-64f0-4d18-a945-82e49efff8bb France | |
| 4d8f2381-fda7-4c24-aae1-f872021efcb6 Spain | |
| 07f4c925-26e9-4966-97ed-cf4d210960dc Belgium | |
| c1f69b14-f4ec-4bc7-9643-0755fb9807e6 Germany | |
| 5fb5b6d4-fbe6-49e6-97b8-4f509d274c3a France | |
| bf88bb81-4e04-429d-b860-bc7f4cfa5e1c Belgium | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... 125 °C |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT7HE316FKFF000XXX |
| E-Number (Norway) | 4380658 |
| EAN | 8056221009836 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 166 mm |
| Product Net Weight | 9.7 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 11.2 kg |
| Package Level 1 EAN | 8056221009836 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Motor Protection |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1336 |
| 1SDH002065A1338 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 3000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 10000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 94 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 42 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Release | Ekip M Dip I |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC60947-2 |
| Sub-type | XT7 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107046A9648 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002013A1101 |
| Wiring Diagram | 1SDM000002A1001 |
| Instructions and Manuals | 1SDH002013A1001 |
| 1SDH002013A1002 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Adjustment range short-term delayed short-circuit release (EF007129) | 16000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1600 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |