View larger
1SDA100918R1
100918
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2357 |
| Environmental Product Declaration - EPD | 9AKK108468A1895 |
| 9AKK108468A4404 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 64.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 80ceb91e-e726-4d1c-865e-5aac36b528f3 Italy |
| Simplified SCIP | 7a08ed49-dd52-43ce-ba30-deae9d37db2f Bulgaria |
| 40cefaec-7962-44ec-a7e8-b12731ac3382 France | |
| a6303aee-f5e3-4fcb-8c9a-8001706fd97a Sweden | |
| 2a42106a-fbd8-46d8-b533-5ee1e19c17dc Germany | |
| 5b475e45-2ea4-4189-93c3-e9b2e921d4ef Portugal | |
| 235e6737-84e4-4062-8a17-4851bf0ee453 Germany | |
| 9e22fba9-a4e1-417c-8924-236452b08f32 Hungary | |
| 5f517601-d210-496f-b71a-073839d11286 Spain | |
| eaa23657-0392-4802-9938-d8495add9eb8 Hungary | |
| f140fc48-9f0f-451b-9fd5-424696544978 Germany | |
| d9224269-4d2e-4e11-8057-868631ba85cc Czech Republic | |
| 06877fe0-848a-44ab-8193-b90c2cb11601 Belgium | |
| f03ae02f-a551-4caa-829d-fa611664cfef Denmark | |
| f5260193-38fe-43c1-a3a9-315fa33d7cfe Germany | |
| 8030b32e-52b6-4758-8379-9e69538b1dd3 Greece | |
| d144deaa-8897-4414-8101-f1d318ed2873 Estonia | |
| ec5b782a-2bab-4200-939b-4d78bb1712a3 Poland | |
| 72f0d345-5eaf-46c7-9ace-389c96ef96b4 Sweden | |
| fa4a236c-aaa1-4663-a2bd-8f1dd484dde7 Poland | |
| 371a13e7-b7b4-4513-a799-0b1f324e0f06 Netherlands | |
| 57218125-f756-47fc-b80f-cc268d616caf Croatia | |
| e8153a9c-9236-4423-a3c9-0cd0881dcce0 France | |
| 4e22c60a-6906-4920-8968-f8299a7433ca Germany | |
| 1ee10c2d-a66a-456a-9a13-576e5cb432f5 Poland | |
| b2efec7d-af24-41f3-81f5-6ec04631f51f Finland | |
| fa1a6027-9dbc-45f7-b618-160211502590 Norway | |
| 6b5f6c1c-d195-4349-8bb2-5616dc6b0a90 Belgium | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... 125 °C |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT7HE380CTFF000XXX |
| E-Number (Norway) | 4380671 |
| EAN | 8056221009720 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 166 mm |
| Product Net Weight | 9.7 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 11.2 kg |
| Package Level 1 EAN | 8056221009720 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1336 |
| 1SDH002065A1338 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 3000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 10000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 24 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 42 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Release | Ekip Hi-Touch LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC60947-2 |
| Sub-type | XT7 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107046A9648 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002013A1101 |
| Wiring Diagram | 1SDM000002A1001 |
| Instructions and Manuals | 1SDH002013A1001 |
| 1SDH002013A1002 | |
| 1SDH001821A1001 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 800 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 320.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 480.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1200.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |