View larger
1SDA100833R1
100833
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2357 |
| Environmental Product Declaration - EPD | 9AKK108468A1895 |
| 9AKK108468A4404 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 64.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 938d120b-bb0c-4029-b0ab-af7f28f5d64b Italy |
| Simplified SCIP | 64da3202-f206-4342-bba1-3dc4de88a57b Germany |
| f7bde48c-d693-4f25-83cd-c4819ec966b7 Belgium | |
| 8980f39e-78c3-47c9-9da2-979357e284fe Estonia | |
| 764e7332-6c5d-4064-b5c2-47b28afdafa8 Greece | |
| 957e041a-e468-4958-8e3f-75dcac9d6cdd Portugal | |
| f179e1d2-8fdd-4a87-a260-6cc161bc9e8a Bulgaria | |
| b3e4aa42-32c9-46db-a7df-8fa85ab4e64f Sweden | |
| 72cfd452-e828-4393-abc0-adfcce6d0e57 Hungary | |
| 618cdcd5-324c-4d2a-9bc6-d6652a61d23f Poland | |
| bdbfd276-6f6f-4287-85e6-517cf73a38f1 Norway | |
| 30ec7140-af44-43b1-a5cd-a6aa4128ffc2 Poland | |
| b58a7c51-b535-433a-9581-37ca979360d7 Denmark | |
| 3af11875-89e3-41fc-8d46-c3d00e5c1000 Finland | |
| 975fd852-6aba-41e0-b882-4039fdf484bb France | |
| 4bcf67b0-0834-4263-8b7a-5f85dd82378c Sweden | |
| 3ecb51c3-92b5-41a1-83c4-1fc34c697d34 Croatia | |
| 203a83c3-64a2-4409-95fb-2dfa94d4df24 Germany | |
| 68d8c8db-b15e-478e-92b5-af84019af82c Germany | |
| 4382c240-f3d8-443e-913f-8522e85321d9 Czech Republic | |
| 665a1b50-da68-498d-80db-d352bd54d32b Belgium | |
| 0a3c2c60-41e8-4259-a8ae-e565185ffe83 Netherlands | |
| 4063d69f-b3bc-4580-82d5-ba0f46759b96 Poland | |
| 25589cac-44a9-4ce7-8f3d-e371e6c92348 Germany | |
| dae3c2c9-3f0f-4aa3-a672-ef78fb1fbdac France | |
| 56a03dbf-0ba5-41e2-a00b-d788fb43b771 Spain | |
| d2684dbc-104b-4576-a155-887e4a5b3025 Germany | |
| c7d00536-617e-4b02-ac18-e0a4a1f7db34 Hungary | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... 125 °C |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT7SE316FFFF000XXX |
| E-Number (Norway) | 4380622 |
| EAN | 8056221008877 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 166 mm |
| Product Net Weight | 9.7 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 11.2 kg |
| Package Level 1 EAN | 8056221008877 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1336 |
| 1SDH002065A1338 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 3000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 10000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 94 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT7 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107046A9648 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002013A1101 |
| Wiring Diagram | 1SDM000002A1001 |
| Instructions and Manuals | 1SDH002013A1001 |
| 1SDH002013A1002 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1600 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1600 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |