ABB 1SDA100750R1 1SDA100750R1 ABB XT6S 800 Ekip Dip LIG In 800 3p F F View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA100750R1 ABB XT6S 800 Ekip Dip LIG In 800 3p F F

1SDA100750R1

100750

ABB

1 Pcs.

XT6S 800 Ekip Dip LIG In=800 3p F F C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LIG R 800

Automation > Power circuit-breaker for trafo/generator/installation protection
Molded case "Isomax-Tmax"

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

b'

General Information

Extended Product Type:
XT6S 800 Ekip Dip LIG In=800 3p F F
Product ID:
1SDA100750R1
EAN:
8056221008044
Catalog Description:
XT6S 800 Ekip Dip LIG In=800 3p F F
Long Description:
C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LIG R 800
\n

Ordering

EAN:
8056221008044
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362090

Dimensions

Product Net Width:
210 mm
Product Net Height:
268 mm
Product Net Depth / Length:
103.5 mm
Product Net Weight:
12.379 kg

Container Information

Package Level 1 Units:
1 piece
Package Level 1 Width:
305 mm
Package Level 1 Height:
285 mm
Package Level 1 Depth / Length:
370 mm
Package Level 1 Gross Weight:
13.03 kg
Package Level 1 EAN:
8056221008044

Additional Information

Circuit Breaker Type to be Associated:
Power Distribution
Current Type:
AC
Electrical Durability:
120 cycles per hour

5000 cycle
Mechanical Durability:
240 cycles per hour

20000 cycle
Number of Poles:
3
Order Multiple:
1 piece
Power Loss:
53.4 W
Product Main Type:
SACE Tmax XT
Product Name:
Moulded Case Circuit Breaker
Product Type:
CB
Rated Current (In):
800 A
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Insulation Voltage (Ui):
1000 V
Rated Operational Voltage:
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 85 kA

(230 V AC) 85 kA

(240 V AC) 85 kA

(380 V AC) 50 kA

(415 V AC) 50 kA

(440 V AC) 45 kA

(500 V AC) 35 kA

(525 V AC) 35 kA

(690 V AC) 22 kA
Rated Short-time Withstand Current (Icw):
10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220 V AC) 85 kA

(230 V AC) 85 kA

(240 V AC) 85 kA

(380 V AC) 50 kA

(415 V AC) 50 kA

(440 V AC) 45 kA

(500 V AC) 35 kA

(525 V AC) 35 kA

(690 V AC) 22 kA
Rated Uninterrupted Current (Iu):
800 A
Release:
Ekip Dip LIG
Release Type:
EL
Short-Circuit Performance Level:
S
Standards:
IEC 60947
Sub-type:
XT6
Terminal Connection Type:
Fixed Circuit-Breakers
Version:
F

Certificates and Declarations (Document Number)

Data Sheet, Technical Information:\n1SDC210100D0205
1SDC210099D0205
Declaration of Conformity - CE:\n9AKK107680A2825
Instructions and Manuals:\n1SDH002012A1001

Classifications

ETIM 7:
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code:
Q
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
\n
'

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.