View larger
1SDA100749R1 ABB C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC..
1SDA100749R1
100749
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Molded case "Isomax-Tmax"
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This Abb 1SDA100749R1 circuit breaker delivers high-capacity protection for industrial power networks, guarding against overloads and short circuits. It ensures safe operational workflows by quickly disconnecting faulty circuits when unexpected electrical surges occur. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Abb
- Manufacturer part number: 1SDA100749R1
- Catalogue code: 100749
- Catalogue title: 1SDA100749R1 ABB C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC..
- Product description: b' General Information Extended Product Type: XT6S 800 Ekip M Dip LIU In=800A 3p F F Product ID: 1SDA100749R1 EAN: 8056221008037 Catalog Description: XT6S 800 Ekip M Dip LIU In=800A 3p F F Long Description: C.BREAKER TMA; Manufacturer summary: C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP M DIP LIU R 800
- Manufacturer summary: C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP M DIP LIU R 800
More info
▲b'
General Information
XT6S 800 Ekip M Dip LIU In=800A 3p F F
1SDA100749R1
8056221008037
XT6S 800 Ekip M Dip LIU In=800A 3p F F
C.BREAKER TMAX XT6S 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP M DIP LIU R 800
Ordering
8056221008037
1 piece
85362090
Dimensions
210 mm
268 mm
103.5 mm
9.5 kg
Container Information
1 piece
305 mm
285 mm
370 mm
11 kg
8056221008037
Additional Information
Motor Protection
AC
120 cycles per hour
5000 cycle
240 cycles per hour
20000 cycle
3
1 piece
53.4 W
SACE Tmax XT
Moulded Case Circuit Breaker
CB
800 A
8 kV
1000 V
690 V AC
(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 35 kA
(525 V AC) 35 kA
(690 V AC) 22 kA
10 kA
(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 35 kA
(525 V AC) 35 kA
(690 V AC) 22 kA
800 A
Ekip M Dip LIU
EL
S
IEC 60947
XT6
Fixed Circuit-Breakers
F
Certificates and Declarations (Document Number)
Classifications
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Q