View larger
1SDA100741R1
100741
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2356 |
| Environmental Product Declaration - EPD | 9AKK108468A9752 |
| 9AKK108468A2295 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 60 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | d811a0ca-b52e-40b8-ae93-d660f613d616 Italy |
| Simplified SCIP | c459b1ff-8fb1-48fa-857d-ec86c8da5622 Denmark |
| 694a85fc-7ead-4cb4-8e03-41efb4be218a Germany | |
| 78a795a0-8fdc-4f94-8d3a-f12a863169de Germany | |
| b0a2ebb9-3e57-47b7-8cd7-50eb73ba89ff Poland | |
| 2a31617a-5818-46ea-909c-ebae2ed48197 Germany | |
| c4d4c818-a25d-4aa8-ae2c-b61fd56d4cf5 Finland | |
| d1cd1e7e-0698-4cb7-aa5a-2d03cb34d5c3 Belgium | |
| a396c9d0-f3be-499d-bc08-235a6e0e9454 Czech Republic | |
| c2275b1c-56a1-4d31-8de5-385b0520ab04 Croatia | |
| e8bd0203-14bc-41a4-8ffc-5b2ef17eb5d7 Poland | |
| 59c172eb-18b2-41f9-b3ba-edb7ebf2d0c5 Germany | |
| 16f4765c-9738-433d-8dfb-58f3e6f9ab42 Sweden | |
| 5f45ba0e-bcc0-4df5-aca8-2a9e028b9ff9 France | |
| 0648de52-a65f-44e1-9571-bb8c8fa3d8c9 Portugal | |
| eb008ec7-abd3-4ed4-9d19-4d0e07323c54 Bulgaria | |
| 2df25b62-87aa-4a55-ad0c-7067fa78a079 Sweden | |
| fbcfca45-2bf1-41fa-b766-a4323b4430c7 Poland | |
| 05ca8f0e-5b06-41fe-aa97-aa8d70ad2834 Greece | |
| c634ecba-aed2-4bc6-a63f-888cd8101eab Hungary | |
| 860fa841-c13c-4480-8fc7-0b5965314a73 Germany | |
| 788aec3f-7f11-4aa7-a572-c958b6ce68d8 France | |
| 0f8c6758-79db-44b4-be5e-17d1ceb1d054 Spain | |
| 8fc2b3c3-f0fb-40bb-88d4-980fc1091f2c Belgium | |
| c09340bc-8a2b-42d6-8626-0e3bbf90add3 Netherlands | |
| d9bfd2f7-920b-4361-863f-131118b5ec0d Estonia | |
| 3b99918c-5796-4da5-b8bd-77ec0a7ff816 Hungary | |
| a6d85263-f293-4990-b82c-f3ac73221d8f Norway | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT6SE3800EFF000XXX |
| E-Number (Finland) | 3641881 |
| E-Number (Norway) | 4380524 |
| EAN | 8056221003667 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 9.5 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 305 mm |
| Package Level 1 Height | 285 mm |
| Package Level 1 Depth / Length | 370 mm |
| Package Level 1 Gross Weight | 11 kg |
| Package Level 1 EAN | 8056221003667 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1190 |
| 1SDH002065A1245 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 5000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | 53.4 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (525 V AC) 35 kA | |
| (690 V AC) 22 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 10 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (525 V AC) 35 kA | |
| (690 V AC) 22 kA | |
| (250 V DC) 2 Poles in Series 50 kA | |
| (500 V DC) 2 Poles in Series 35 kA | |
| (750 V DC) 3 Poles in Series 24 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Release | Ekip Dip LS/I |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT6 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2825 |
| Mechanical Drawings | 1SDH002012A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002012A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 800 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 320.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 800 A |
| Adjustment range undelayed short-circuit release (EF007131) | 800 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |