View larger
1SDA100723R1
100723
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2356 |
| Environmental Product Declaration - EPD | 9AKK108468A9752 |
| 9AKK108468A2295 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 60 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 9a59db99-48cb-4819-ac9b-1ecece461d8a China |
| Simplified SCIP | e2666fd4-9eca-405b-9d6f-ad39c6d2baf6 Sweden |
| 95adab21-fe4a-44d7-8d2a-4b5209e19e71 Portugal | |
| a6474f88-fc81-44a1-9f76-cb81427095ca Belgium | |
| 61520ef1-7705-4f19-9e8d-31b39209ef9c Bulgaria | |
| aa7bc97c-0e3b-4dbc-a47d-ff5882f61ff9 Poland | |
| 3187becb-e8f8-4984-bd53-5466c46a3527 Czech Republic | |
| 9e553566-bc9e-43fc-80bb-70f2eb2d4b42 Poland | |
| 149b83a0-f365-4f5f-a27b-9f2307b3bc7e Finland | |
| 6e97eacd-b978-4f1c-8eaf-15f51634930f Estonia | |
| 3f233ea9-59a2-482d-bc19-48b7e7beed53 France | |
| e0f64a4e-70fd-4096-906c-3c0683ee4ec2 Belgium | |
| 2d5023a5-6c6f-47e0-86b0-dde1bc5da5fa Spain | |
| 6995dadd-4408-4e07-a55b-1e089e9e556f Hungary | |
| 474c0db3-b379-4aca-9a85-ac6236f90b7d Germany | |
| e961659d-90de-4e57-aa96-6370424f3398 Denmark | |
| 736288a4-c38d-41aa-9a87-3db7d98d0657 Germany | |
| f100a3bc-7be0-4f6c-a5f1-cc9b8e8bf4af Croatia | |
| 98bb0447-8ce1-4bfd-ab73-2a3069e78e7f France | |
| c534c0ce-20c9-4eec-9471-9998fd1b0adc Norway | |
| 305e0662-7d0b-4c87-9ef4-cc5da5d999ac Poland | |
| 8568aefb-d1fb-4666-b6d1-51dcde72b6bb Sweden | |
| bfd008cf-8adb-4eeb-9561-56c0accdc91e Germany | |
| c163a365-e361-4c8c-979b-21a8e460207c Greece | |
| 1078c0f7-b9cd-4cfa-9b20-8997ea3a01e2 Hungary | |
| 8bf78ca9-d17b-4566-a228-a6615eeb45c6 Netherlands | |
| 8545a1cc-fb2d-4a20-851e-b37ec4a421cb Germany | |
| fe502231-2bfe-4d4b-b607-eff1f14edd3e Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT6NE3800GFF000XXX |
| EAN | 8056221007993 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 9.5 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 305 mm |
| Package Level 1 Height | 285 mm |
| Package Level 1 Depth / Length | 370 mm |
| Package Level 1 Gross Weight | 11 kg |
| Package Level 1 EAN | 8056221007993 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1190 |
| 1SDH002065A1245 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 5000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | 53.4 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 30 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 10 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA |
| (230 V AC) 70 kA | |
| (240 V AC) 70 kA | |
| (380 V AC) 36 kA | |
| (415 V AC) 36 kA | |
| (440 V AC) 30 kA | |
| (500 V AC) 25 kA | |
| (525 V AC) 25 kA | |
| (690 V AC) 20 kA | |
| (250 V DC) 2 Poles in Series 36 kA | |
| (500 V DC) 2 Poles in Series 20 kA | |
| (750 V DC) 3 Poles in Series 18 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC60947-2 |
| Sub-type | XT6 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2825 |
| Mechanical Drawings | 1SDH002012A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002012A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 800 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 320.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 800 A |
| Adjustment range undelayed short-circuit release (EF007131) | 800 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |