View larger
1SDA100557R1 ABB XT5S 630 INTERRUPTIVE PART 4p F F
1SDA100557R1
100557
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Molded case "Isomax-Tmax"
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
ABB XT5S 630 INTERRUPTIVE PART 4p F F serves as a core interrupting module for high-capacity molded case circuit breaker assemblies in industrial networks. Interrupting units house the specialized contact structures and arc-quenching chambers necessary to safely clear heavy fault currents. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 9AKK108468A2353
- Environmental Product Declaration - EPD: 9AKK108468A9746
- Extended Product Lifetime: Product Modularity
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 59.6 %
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK108467A6707
- E-Number (Finland): 3641410
- E-Number (Norway): 4380451
- EAN: 8056221006330
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2353 |
| Environmental Product Declaration - EPD | 9AKK108468A9746 |
| 9AKK108468A1893 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| E-Number (Finland) | 3641410 |
| E-Number (Norway) | 4380451 |
| EAN | 8056221006330 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85389099 |
| Dimensions | |
| Product Net Width | 186 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 4.15 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 248 mm |
| Package Level 1 Height | 240 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 4.5 kg |
| Package Level 1 EAN | 8056221006330 |
| Additional Information | |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Breaking Part |
| Version | F |
| Technical | |
| Electrical Durability | 5000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 4P |
| Order Multiple | 1 piece |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| 750 V DC | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 30 kA | |
| (690 V AC) 25 kA | |
| (250 V DC) 2 Poles in Series 35 kA | |
| (500 V DC) 2 Poles in Series 35 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 6 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 30 kA | |
| (525 V AC) 30 kA | |
| (690 V AC) 25 kA | |
| (250 V DC) 2 Poles in Series 35 kA | |
| (500 V DC) 2 Poles in Series 35 kA | |
| Rated Uninterrupted Current (Iu) | 630 A |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 2CDC210017C0101 |
| 1SDC210100D0206 | |
| 1SXF210033C2001 | |
| 1SDC210099D0206 | |
| 1SXF210034C2001 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| Wiring Diagram | |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |