View larger
1SDA100508R1
100508
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2354 |
| Environmental Product Declaration - EPD | 9AKK108468A1899 |
| 9AKK108468A9748 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 59.6 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 06965c54-1c7d-4814-9391-3a0a719005ec China |
| Simplified SCIP | a8029685-f950-42b9-9508-4f7b66722ad9 Sweden |
| 19937da1-9846-4d51-809c-f25e8cb6b28e Spain | |
| 011fa9f3-ae28-4d11-9e75-656362690964 Hungary | |
| c83266d2-181f-4a48-b587-a5aa3cd39902 Portugal | |
| 3757bbf8-ecbb-4b63-8c12-904062dc1389 Germany | |
| d20f29da-ba6d-4193-9381-42077d390e68 Germany | |
| b7124db9-288c-4664-8f0f-cf7c0d2f0296 Germany | |
| e3129452-5069-473e-b61d-ebd02fda6295 Denmark | |
| b43e58d5-b6c6-440e-8db2-2a644b7babbd Belgium | |
| a1e20c4e-0652-4469-ac45-85e926a008b0 Greece | |
| 991d9272-968f-4a93-8269-bd57727f8e89 France | |
| 60a5b4f5-7dda-40ad-bc87-1b34252c7a41 Hungary | |
| aa8f06d9-0bc1-4279-b001-aa0617d176b1 Belgium | |
| 35447f65-652f-4e55-9e82-3a6609e0af3d Estonia | |
| f8317d8c-249a-43bd-b713-62ca23eb30c0 Netherlands | |
| 62189bac-edc5-4d0e-a49d-86241fafdb98 Poland | |
| de9b996e-83ae-43bf-80be-b77baca18b3e Sweden | |
| 8f7fbd51-05fd-4e29-a14a-a7f141ad59f0 Czech Republic | |
| 466fbd5a-7ecc-4b7d-b33e-f5d61b84b86f Germany | |
| 18f9757c-18d8-48a8-bd32-20123cd50dc9 Norway | |
| c2b0dac4-41d6-4e87-b2b0-cf2a383d75bf Finland | |
| 92ed1a9f-706b-4914-93c6-08ce97983f7d Croatia | |
| e8f0df01-6ff0-4094-b504-5b6ddf23f418 Poland | |
| ee808e75-c6c0-4a0d-ad0d-37533a8117ee Germany | |
| fd0b5263-3ead-42d0-89f3-2527016cde85 France | |
| 55025c06-1de0-4bbd-bb5d-a9975d99116a Poland | |
| e27635c3-025c-436a-b10b-f24e878de197 Bulgaria | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT5HE340ALFF000XXX |
| E-Number (Norway) | 4380315 |
| EAN | 8056221005852 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 140 mm |
| Product Net Height | 205 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 4.82 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| Package Level 1 Height | 245 mm |
| Package Level 1 Depth / Length | 285 mm |
| Package Level 1 Gross Weight | 5.308 kg |
| Package Level 1 EAN | 8056221005852 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Motor Protection |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1115 |
| 1SDH002065A1131 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 7000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | 19 W |
| Rated Current (In) | 400 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 40 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 40 kA | |
| Rated Uninterrupted Current (Iu) | 400 A |
| Release | Ekip M Dip LIU |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC60947-2 |
| Sub-type | XT5 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107680A2824 |
| Mechanical Drawings | 1SDH002011A1101 |
| Wiring Diagram | 1SDM000005A1001 |
| Instructions and Manuals | 1SDH002011A1001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 400 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 160.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 2400 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |